CX-12 PLUS DOOR INTERFACE RELAY

INSTALLATION INSTRUCTIONS

Momentary Operation

In the Momentary position, even a stuck switch input will allow 
the door to time out and close, thereby providing security to 
occupants. The CX-12 PLUS will however, still operate normally if 
one of the other inputs is activated. Essentially, it ignores the faulty 
activation source, as all inputs are isolated.

The inputs to the CX-12 PLUS may be either dry or wet (powered), 
meaning that 3-terminal radio receivers may be connected directly 
to the CX-12 PLUS without fear of malfunction. See Diagram 1.

Additionally, we provide a direct connection from an apartment 
interphone panel. Only Relay #1 (strike) will operate when a 
voltage is applied to this input. A vestibule courtesy switch will be 
energized for the time set by Pot. 1. See Diagram 2b or 2c

Maintained Operation

Select Relay 1 Maintained for an Access Control application. 
When a maintained signal is applied to WET 1 input, the lock will 
remain energized, while the DRY 2 input allows a wall switch to 
open the door.

An input on DRY 1 will always unlock and open the door. 
See Diagram 2a.

Select Relay 2 Maintained if you are connecting the CX-12 PLUS 
to a fire alarm panel, or to a presence sensor.

In this mode the lock will fire momentarily but the operator relay 
will be held in as long as the input is maintained. See Diagram 3.

Latching/Ratchet Operation

In this mode the CX-12 PLUS will latch Relay2 with a momentary 
activation on Dry/Wet1.  Relay2 is released when Dry/Wet1 are 
activated a second time.  If Dry/Wet2 are activated, Relay1 and 
Relay2 are latched until Dry/Wet2 are activated again.

Washroom Door Controller

In this mode, complete control of a single occupant barrier-free 
washroom is obtained. It allows the user lock and secure the 
door from the inside by depressing a Push-to-Lock button. The 
exterior wall switch is removed electronically from the circuit. 
To exit the washroom, simply exit manually via the lever-handle 
set (the Door Contact Switch resets the relay), or, press the 
interior wall switch to unlock and activate the door operator. 
The door remains unlocked upon closure. 

Another feature is the ability to use the CX-12 PLUS on 
“Normally Secure” washrooms. In this mode, the door is usually 
locked. To gain access, the user must first swipe a card, or enter 
a code into the Access System (ie. Keypad), which then signals 
the  CX-12 PLUS to unlock and open the door. Once inside, the 
occupant presses the Push-to-Lock button, which removes the 
exterior wall switch from the circuit.

Exiting may be accomplished manually via the lever-handle set 
(the Door Contact Switch resets the relay), or, by pressing the 
interior switch to unlock and activate the door operator. 
The door will re-lock upon closure.
Note: We highly recommend the use of a regulated power 
supply when powering strikes for barrier-free washroom 
applications where the strike power may be maintained 
from a few minutes to many hours.
We offer a low-cost board-only regulated power supply 
- CX-PS13 V3, which can be powered from a small 24VAC 
transformer, (or the auxiliary power on the door control) 
and will supply clean, filtered & regulated 24VDC power for 
the strike.

Bi-Directional Door Sequencer

In this mode, the relay will sequence two Automatic doors, in 
both directions. Upon a switch closure from one side, a signal is 
sent to the first door (relay 1), then after an adjustable delay, the 
second door (relay 2) receives a signal. When a switch closure is 
made from the opposite side, the sequence is reversed – Relay 
2 is activated, then after the adjustable delay, relay 1 activates.  

When used as a door sequencer the user can select either 
momentary position for the inputs, or maintained position. 
In the momentary position, even a stuck switch input will allow 
the door to time out and close, thereby providing security to 
the occupants.

The CX-12 PLUS will however, still operated normally if one 
of the other inputs is activated. Essentially, it ignores the 
faulty activation source, as all the inputs are isolated. In the 
maintained position, a switch that is held on will cause its 
respective relay (operator) to be held on. So switch #1 would 
hold in relay #1, and switch #2 would hold in relay #2. 

If an emergency (or anti-entrapment) switch is desired in the 
vestibule, then wire that switch directly to one of the operator 
inputs. Usually the exterior door is used in this case.
IMPORTANT: Do not apply power until you have read the 
instructions fully and made the required adjustments. 

4. INSTALLATION

Mounting

The LED’s are visible through the wrap-around sleeve, which also 
has cutouts for adjusting the potentiometers, and setting the dip 
switch. Once the unit has been adjusted, it may be tucked up 
into the operator header or affixed using the supplied Velcro.

Wiring

Wiring of this unit is dependent on the mode desired, however 
the following commonalities apply.

Содержание CX-12 PLUS

Страница 1: ...Rating 3 Amps 30 VDC Current Draw 20 mA Idle 60 mA Operating Response Time 0 3 Seconds Inputs 2 Wet 2 Dry N O 3 30V AC DC Optically isolated non polarity sensitive Outputs 2 x Form C SPDT Electrical...

Страница 2: ...o the Access System ie Keypad which then signals the CX 12 PLUS to unlock and open the door Once inside the occupant presses the Push to Lock button which removes the exterior wall switch from the cir...

Страница 3: ...red therefore connect to WET 1 Terminals 9 10 The exterior activating switch is wired to DRY 2 Terminals 15 16 This input signals the door operator Relay 2 and is only active when the strike relay is...

Страница 4: ...h the interior wall switch This also resets the relay for the next person to use 2 Manual use The door may also be used manually To exit the washroom turn the lever handle and pull push the door open...

Страница 5: ...mm 0 12 3mm 2 31 59mm 3 25 83mm 0 61 15 5mm 0 71 18mm L4W 2T7 CX 12 CAMDEN DOOR CONTROLS 3 3 1 Power Input 12 24V AC DC Non Polarized 2 Power Input 3 Relay 1 NO FORM C 4 Relay 1 COM 5 Relay 1 NC 6 Rel...

Страница 6: ...11 16 09 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 12 24 V AC DC Power Wet Input ie Radio Receiver Dry Input ie Push Switch Electric Strike Door Operator Wire MOV supplied directly to strike or...

Страница 7: ...r Electric Strike If Mag lock used wire to Terminals 4 5 Exterior Switch in circuit only while Lock Relay is active Interior Switch always unlocks and opens door Access Control Time Clock sends a powe...

Страница 8: ...Electric Strike If Mag lock used wire to Terminals 4 5 Interior Switch Unlocks and opens door Optional Vestibule Mounted Convenience Switch Only active when Lock Relay energized Switch opens door Wir...

Страница 9: ...locks and opens door Optional Vestibule Mounted Convenience Switch Only active when Lock Relay energized Switch opens door Wire MOV supplied directly to strike or magnet Power for Strike DRY2 WET2 DRY...

Страница 10: ...lea Blvd Mississauga Ontario L4W 2T7 Presence Sensor Dry contact output Fire Alarm Panel Shown with maintained powered signal wet Power for Strike DRY2 WET2 DRY1 WET1 POWER NO NO NC NC COM COM Relay2...

Страница 11: ...TE 11 16 09 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 Electric Strike Dry Input ie Push Switch Wet Input ie Radio Receiver Wire MOV supplied directly to strike or magnet Power for Strike DRY2 WE...

Страница 12: ...LE NONE DRAWN BY DGW REVISED 1 28 2020 DATE 02 08 09 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 Door Push Switch CAMDEN DOOR CONTROLS 1 5 2 3 4 6 7 8 9 10 11 12 13 14 15 16 RL1 RL2 DOR RL1 DOO RL...

Страница 13: ...ario L4W 2T7 Door 1 Push Switch Door 2 Push Switch DRY2 WET2 DRY1 WET1 POWER NO NO NC NC COM COM Relay2 Relay1 CX 12 PLUS CAMDEN DOOR CONTROLS 1 5 2 3 4 6 7 8 9 10 11 12 13 14 15 16 RL1 RL2 DOR RL1 DO...

Страница 14: ...COM Relay2 Relay1 CX 12 PLUS CAMDEN DOOR CONTROLS Note Optional annunciators may be used to indicate the door status A CM 9600 piezo switch uses optional harness for remote LED control B CM AF500 LED...

Страница 15: ...Ontario L4W 2T7 Outside Wall Switch Inside Wall Switch Magnetic Contact Switch Inside Push to Lock Switch DRY2 WET2 DRY1 WET1 POWER NO NO NC NC COM COM Relay2 Relay1 CX 12 PLUS CAMDEN DOOR CONTROLS F...

Отзывы: