Problem
Possible Cause
Corrective Action
II. BLOWER RUNS;
NO HEAT;
FLAME SAFEGUARD
RELAY DOESN’T
LOCK OUT
1. Mode Selector Switch
a) Switch in VENT position
a) Place switch in HEAT position.
2. Burner Service Switch
a) Switch in OFF position
a) Place switch in REMOTE position.
3. Multi-Functional PC Board
a) No input voltage on Terminal W (RCS)
b) Thermostat satisfied
c) Improper wiring
d) Defective board
a) Check voltage in RCS.
b) Adjust thermostat.
c) Check wiring to multi-functional PC
board.
d) Replace multi-functional PC board.
4. Airflow Switch
a) Blower running backwards
b) Belts slipping
c) Blocked intake or discharge
d) Clogged airflow tubing or pickup ports
e) Defective switch
a) Reverse motor direction.
b) Tighten and/or replace belts.
c) Find and remove obstruction.
d) Clean or replace tubing or pickup ports.
e) Replace switch.
5. Flame Safeguard Relay (FSR)
a) No input voltage
b) Defective FSR
a) Check wiring.
b) Replace FSR.
6. Entering Air Thermostat (EAT)
a) EAT set too low
a) Increase EAT setting.
III. BLOWER RUNS;
NO HEAT;
FLAME SAFEGUARD
RELAY LOCKS OUT
1. Igniter
a) No current (open igniter)
b) No voltage
During trial for ignition:
a) Check igniter current.
b) Check FSR output to igniter.
2. High Limit
a) High limit tripped
a) See Problem Number VI.
3. High or Low Gas Pressure Switches
a) Low gas pressure switch tripped
b) High gas pressure switch tripped
c) Defective gas pressure switch
a) Check gas supply for low gas pressure or
no gas.
b1) Check. manifold gas pressure for high
pressure reading and reset pressure
regulator.
b2) Check gas supply pressure against name
plate.
b3) Verify the high pressure regulator is a
lock-up type.
c) Replace gas pressure switch.
4. Gas Valve
a) No input voltage
b) Gas valve does not open
c) Defective solenoid
a1) Check FSR output to R1 relay
during ignition trial.
a2) Check gas valve circuit and wiring.
b1) Compare supply voltage to nameplate
voltage.
b2) Clean and/or replace gas valve parts.
c) Replace solenoid or valve assembly.
5. Modulating Valve
a) Minimum fire set too low
a) Adjust minimum fire on modulating valve.
6. Multi-Functional PC Board
a) Low fire start set too low
b) Thermistor open or not connected
a) Adjust modulating valve voltage between
10 and 13 Volts DC.
b) Properly install or replace thermistor.
TROUBLESHOOTING GUIDE
Содержание M Series
Страница 82: ...Cambridge Air Solutions 80 M Series Technical Manual ELECTRICAL CONTROL ENCLOSURE ISOMETRIC DRAWING M140 ...
Страница 106: ...Cambridge Air Solutions 104 M Series Technical Manual MODEL NO SERIAL NO Date Activity Technician MAINTENANCE LOG ...
Страница 107: ...M Series Technical Manual 105 Cambridge Air Solutions MODEL NO SERIAL NO Date Activity Technician MAINTENANCE LOG ...
Страница 108: ...Cambridge Air Solutions 106 M Series Technical Manual ...
Страница 109: ...M Series Technical Manual 107 Cambridge Air Solutions ...
Страница 110: ...Cambridge Air Solutions 108 M Series Technical Manual ...
Страница 112: ...760 Long Road Crossing Dr Chesterfield MO 63005 Phone 636 532 2233 800 899 1989 Fax 636 530 6133 www cambridgeair com ...