Cambridge
Air
Solutions
10/31/2022
BACnet
Controller
EVAP
Technical
Manual
Version
4.0.2.0002
ANALOG VALUE OBJECTS
Object
Description
Writable
Units
Range
Default
AV:29501 Device Address
True
NA
4 - 127
4
AV:29502 Device Object ID
True
NA
0 - 4194302
NA
AV:29510 DAT Sensor Offset
True
°F
-10 – 10
0°F
AV:29512 Deadband
True
°F
0 – 20
0°F
AV:29513 High Drain Threshold
True
μ
S/cm 0-10,000 X
AV:29514 Drain Delay Time
True
Minutes
0 - 120
X min
AV:29515 Drying Time
True
Minutes
0 - 120
X min
AV:29516 Valve Delay
True
Minutes
0 - 120
X min
AV:29517 Fan Fault Delay
True
seconds
0 - 300
60 sec
AV:29518 Water Flush System
True
μ
S/cm 0-10,000 X
AV:29519 OAT Sensor Offset
True
°F
-10 – 10
0°F
AV:29520 Low OA Lockout Setpoint
True
°F
40 – 160
40°F
AV:29521 Pump Down Time
True
Minutes
0 - 120
X min
AV:29522 Fan Start Delay
True
Minutes
0 - 120
X min
AV:29524 ZNT Sensor Offset
True
°F
-10 – 10
0°F
AV:29534 Supply Fan Cycle Count
False
Counts
NA
NA
AV:29535 Supply Fan Runtime
False
hours
NA
NA
AV:29536 Supply Fan Speed
(optional)
True
%
0 - 100
100%
AV:29537 Effective Cooling Setpoint
False
°F
NA
NA
AV:29538 OA Econ Lockout Setpoint
True
°F
40 – 160
65°F
AV:29539 Unoccupied Discharge Air Flow Setpoint
True
°F
40 – 160
65°F
AV:29540 Occupied Discharge Air Flow Setpoint
True
°F
40 – 160
65°F
AV:29541 Occupied Zone Cooling Set Point
True
°F
40 – 160
75°F
AV:29542 Unoccupied Zone Cooling Set Point
True
°F
40 – 160
85°F
AV:29543 Freeze Stat Setpoint
True
°F
40 – 160
65°F
AV:29544 Netsensor Temp
False
°F
32 – 104
NA
AV:29545 Netsensor Humidity
False
%
0 – 100
NA
AV:29546 RH
Setpoint
True
%
0-100
60%
AV:29547 Inlet Air Cooler
True
NA
1-2
AV:29548 Number of Pumps
True
NA
1-2
AV:29549 Stage Up Delay
True
Minutes
0 - 30
X min
AV:29552 OA Heating Lockout Setpoint
True
°F
0 – 130
65°F
AV:29553 Discharge Air High Set Point
True
°F
40 – 160
160°F
AV:29554 Discharge Air Low Set Point
True
°F
40 – 160
70°F
AV:29555 Occupied Zone Heating Set Point
True
°F
60 – 90
60°F
AV:29556 Unoccupied Zone Heating Set Point
True
°F
40 - 80
55°F
AV:29557 Burner Modulation Set Point
False
%
NA
NA
AV:29560 Burner Fault Delay
True
seconds
0 - 300
60 sec
AV:29561 Low Temperature Cutout Setpoint
True
°F
45 - 55
45°F
AV:29562 Low Temperature Cutout Delay
True
seconds
0 - 300
60 sec
AV:29563 Effective Heating Set Point
False
°F
NA
NA
AV:29564 Effective Discharge Air Set Point
False
°F
NA
NA
AV:29565 Burner
Runtime
False
hours
NA
NA
AV:29566 Burner Cycle Count
False
Counts
NA
NA