7
Irregular Cabinet and Countertop Heights
Countertops such as ceramic tile tops cause cabinet and
countertop to be higher than 36 inches. Follow instructions
below when countertop is higher than 36 inches.
1.
Raise leveling legs to maximum height.
2.
Measure from floor to rangetop. If measurement is
less than height of countertop, floor must be
shimmed.
3.
Shim floor using a piece of plywood same size as
range opening. Secure plywood to floor. Plywood
must be as secure as original flooring.
4.
Install anti-tip bracket and slide range into place.
Line Voltage Requirements
Line voltage must not exceed rated voltage. See rating plate
attached to range for kilowatt rating. Line voltage less than
rated voltage will result in slow heating. Wiring system must
conform to Underwriters Laboratories, Inc. standards and
National Electrical Code. Installation must conform to all
local, municipal and state building codes, and local utility
regulations. Range must be connected only to a supply
circuit as specified on rating plate wiring diagram of range.
This range requires 3 wires, 120/240 VAC, 40 Amp
minimum, 60 Hertz, single phase electrical supply (refer
to rating label). Wiring system and grounding must
conform with the latest edition of Underwriters
Laboratories, Inc. Standards, the National Electric Code,
ANSI/NFPA 70, or the Canadian Electrical Code, CAS
C22.1. Installation must conform to all local, municipal
and state building codes, and local utility regulations.
Connect range to power supply with MAXIMUM RATED
VOLTAGE listed on the ratingplate. Line voltage must not
exceed rated voltage.
Power Supply Location
Shaded area shows range clearance for electrical
connection.
B
C
D
C
A
A
A—3 inches
B—6 inches
C—6 inches
D—3 inches
Power Cord Requirements
Power cord is not supplied with range. Power cord must
be U.L. Listed and meet NEC and Mobile Home
Manufacturers Association Standards. Cord must be
rated at a minimum 250V 40 AMP, equipped with a plug
configuration in accordance with NEMA. Conductors
must end with closed loop (ring) terminals at the range.
• Three-conductor cord plug NEMA 10-50P allowed for
residential.
• Four-conductor cord plug NEMA 14-50P required for
most mobile home installations but can be used for
residential.
NOTE: Only a power cord suitable for use with ranges
may be used. For installation in a mobile home, or
area where local codes do not permit grounding
through the neutral terminal, a 4-wire cord must be
used.
Range Terminal Block
Connection block is located at bottom rear of range
behind rear cover panel. Remove rear cover screw.
Directly below terminal block is a hole for a power supply
service cord. Power cord is not supplied with range.
Installing Power Cord
Installation
(cont.)