background image

Safety thermostat

press to reset

(red button)

FIG 3

MODEL

TTW33(7)/& 

TTW30(7)A

TTW33(7)/& 

TTW30(7)AX

TTW30(7)AP/& 

TTW30(7)AXP

TTW55(7)/& 

TTW60(7)A

TTW55(7)/& 

TTW60(7)AX

TTW50(7)AP/& 

TTW60(7)AXP

Dehumidification

L/hr

1.25

1.25

1.25

2.5

2.5

2.5

L/day

30

30

30

60

60

60

Total Heat to Air
Dehumidifier only

kW

1.9

1.9

1.9

3.5

3.5

3.5

Dehum & Resistance heater

kW

n/a

n/a

2.89

n/a

n/a

5.55

Resistance heater only

kW

n/a

n/a

2.0

n/a

n/a

4

Dehum & LPHW

kW

3.9

3.9

n/a

6.5

6.5

n/a

LPHW only

kW

3.0

3.0

n/a

5

5

n/a

Nominal Power Consumed
Fan only

kW

0.05

0.05

0.05

0.1

0.1

0.1

Dehum (Comp & Fan)

kW

0.75

0.75

0.75

1.2

1.2

1.2

Dehum & Heater

kW

n/a

n/a

2.75

n/a

n/a

5.2

Heater & Fan

kW

n/a

n/a

2.05

n/a

n/a

4.1

Supply

230V 50Hz

230V 50Hz

230V 50Hz

230V 50Hz

230V 50Hz

230V 50Hz

Fuse

A

10

20

20

13

13

32

Nominal Running Amps

A

3.4

3.4

11.7

5.6

5.6

22.3

Full Load Amps

A

4.4

4.4

12.7

7.5

7.5

24.2

Compressor LRA

A

15.8

15.8

15.8

30

30

30

Air Flow

m

3

/h

420

420

420

750

750

750

Noise Level @3m

dB/A

46

46

46

47

47

47

Water Flow Rate

L/min

5.0

5.0

n/a

5.0

5.0

n/a

Pressure Drop

m hd

1.1

1.1

n/a

1.8

1.8

n/a

LPHW Flow Rate

L/min

n/a

n/a

n/a

5.0

5.0

n/a

LPHW Pressure Drop

m hd

n/a

n/a

n/a

1.1

1.1

n/a

HERMETIC SYSTEM

Refrigerant Charge ‘A’ Dehumidifiers

kg R407c

0.5

0.4

0.5

0.75

0.8

0.75

Refrigerant Charge ‘AX’ Dehumidifiers

kg

0.5

0.5

0.45

0.75

0.8

0.8

R407c Global Warming Potential (GWP) 1774

NOTES:-

a) These performance figures are based on air @ 30ºC and 60% RH & pool water @ 28ºC, Boiler water at 80°C

b) Humidistat adjustable from 20% to 80%

c) Minimum air temperature on standard models 15°C and 0°C on defrost 'X' models

d) Reduced LPHW output when TTW operating is 1kW less on 33 model and 2kW less on 55 model

e) IP rating for all models is IP45 

f) Maximum operating conditions air temp 35°C and 90% RH 1L/min = 0.22 gal/min

g) Maximum operating conditions for AP versions air temp 32°C and 62% RH

1mm Wg = 9.8 Pa

1m hd = 1.4 psi

1L/min = 0.22 gal/min