OWNER/INSTALLATION MANUAL

11�1 START UP PROCEDURE AFTER WINTERISATION

1.  Replace covers (if not fitted).
2.  Remove front grille – using soft brush clean finned 

surfaces of heat pump. Replace panel.

3.  Remove plastic covers on water connections and 

reconnect water piping or close drain valve.

4.  Start up water circulating pump and leave running 

for at least ¼ hour to establish flow and enable any 
air in system to escape.

5.  Replace fuses to heat pump circuit.
6.  Switch on heat pump.
7.  Check control thermostat is set to required pool 

temperature.

8.  Check daily to ensure pool water is at correct pH 

and has correct chemical balance. 
See section 3.3 Plumbing.

11�0 WINTERISATION PROCEDURE

WARNING. Isolate machine before opening! As heat pump embodies electrical and rotational 

equipment, it is recommended for your own safety that a competent person carries out the 

following procedure.

(Drain Down Procedure)

ALL MODELS

Objective

To provide frost protection

To eliminate corrosion problems

To inhibit electrical components

1.  Switch off electrical supply to heat pump.
2.  Remove external fuses and keep in safe place away 

from heat pump to prevent accidental operation of 
heat pump.

3.  Ensure water circulation pump is switched off.

4.  Drain water from heat pump by:
a) Drain valve if fitted.
b) Disconnecting pipework to and from heat pump.
c) Remove condenser drain down cover.
d) Flush through water circuit in heat pump by using 
CLEAN TAP WATER (NOT POOL WATER) via hose into 
outlet connection – run for 10 minutes minimum, use 
spray nozzle if available.
e) Allow to drain – fit plastic bags secured by elastic 
bands over water connections.
5.  Uncover electrical enclosure (page 14) and 

liberally spray interior of unit, with moisture repellant 
aerosol WD-40 or similar, reseal enclosure.

6.  If heat pump located outside, protect from weather 

by covering with VENTILATED cover. A bespoke 
cover is available. Do not use plastic sheet as 
condensation can occur within unit.

If this procedure is not adopted and frost or corrosion damage results 

then the warranty will become invalid.

Содержание I-PAC IPT 12

Страница 1: ...I PAC inverter heat pump IPT 8 12 16 22 28 Owner Installation Manual 1005494 iss 1...

Страница 2: ...This appliance can be used by children from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision...

Страница 3: ...12 4 0 ELECTROLYTIC CORROSION IN SWIMMING POOLS 13 4 1 ELECTRIC WIRING AND SUPPLY 13 4 2 CONNECTING THE MACHINE TO THE POWER SUPPLY 14 5 0 USING YOUR HEAT PUMP 16 5 1 THE KEY PAD 16 5 2 OPERATING INST...

Страница 4: ...nt is environmentally friendly but safety instructions must be strictly adhered to The WARNING sign denotes a hazard It calls attention to a procedure or practice which if not adhered to could result...

Страница 5: ...not place obstructions that will block air flow near the inlet or outlet Do not use or store combustible gas or liquids near the heat pump The heating performance can be improved by insulating the fl...

Страница 6: ...ways keep the heat pump upright Do not lift the heat pump by the water inlet or outlet connections If this is done the titanium heat exchanger inside the heat pump could be damaged 2 2 ACCESSORIES The...

Страница 7: ...1 2 3 OPTIONAL ACCESSORIES The following items are additional accessories available for purchase Rubber mounting kit pack of 4 mounts Remote LED control kit for indoor installation 10m extension cable...

Страница 8: ...tage application Stable inverter control system 2 4 OPERATING CONDITIONS AND RANGE Air temperature operating range 5 43 C X 10 43 C Y Heating temperature setting range 18 C 40 C Cooling temperature se...

Страница 9: ...red by the wall Connect to Remote control panel or Wi Fi before installing the heat pump in position Required free areas to provide air flow to and from heat pumps when installed in an enclosed area o...

Страница 10: ...positioned in a well ventilated area Minimum distances between the heat pump and any obstructions are shown below The heat pump must be fixed by M10 bolts to a concrete base or mounting brackets These...

Страница 11: ...r fitted Non return valve Sanitiser or chemical dosing device If fitted Aux heater If fitted Filter Pump To waste for winterising drain down 100mm Condensate water to waste Spare port for winterising...

Страница 12: ...removed from the pool water in out connections These should drop out when the adaptors are unscrewed 1 Ensure that bypass is installed and set to achieve the recommended flow rates stated in the data...

Страница 13: ...ould be bonded together using 10mm bonding cable This includes non electrical items such as metal filters pump strainer boxes heat exchangers steps and handrails It is highly recommended that bonding...

Страница 14: ...able clamps and feed through cable entry points in machine Cable clamp L3 N Fuses MCB Earthed Power Supply 400V 50Hz L3 N P1 P2 Power terminals Pump terminals Single phase Terminals in Heat Pump Elect...

Страница 15: ...tched fuse isolator within 2m of heat pump and sized in accordance with datasheet Single phase supply to suit capacity Water pump more than 3 4 HP Single Phase Minimum 2 Pole N O starter with overload...

Страница 16: ...period if the heat pump detects a need for water heating it will continue to over ride the time clock until the pool water temperature is satisfied If water heating is not required the over ride will...

Страница 17: ...lock Screen Mode switching for heating cooling or automatic heat cool Speed Mode Two mode for switching Boost or Whisper Up Down Temperature Setting and Display Attention a Standby mode or Screen lock...

Страница 18: ...tion Connect Wi Fi on mobile phone and input password then control equipment by Wi FIi When APP connects Wi Fi successfully light is on When setting by APP flashes Clear Wi Fi setting history When scr...

Страница 19: ...p before the filtration pump Note Heat pump must be turned off prior to backwashing Before staring the heat pump please check for any leakage of water and set the required temperature on the thermosta...

Страница 20: ...FAULTS Requirements for service personnel Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry accredited assessme...

Страница 21: ...information and your model number Don t try to repair it yourself NO Display Reason Solution 1 E3 No water flow through the heat pump Check water circuit and pool pump 2 E4 Three phase rotation prote...

Страница 22: ...s exhaust temp sensor failure 11 P4 Evaporator coil pipe temp sensor failure 12 P5 Gas return temp sensor failure 13 P6 Cooling coil pipe temp sensor failure 14 P7 Ambient temp sensor failure 15 P8 Co...

Страница 23: ...1 82 10 8 2 60 14 61 3 16 19 32 Maximum input current A 9 5 12 5 19 5 20 Rated RCD A 30 30 30 30 Rated fuse MCB type C A 16 25 25 25 Sound level at 10m dB A 19 6 31 5 21 9 32 0 24 3 36 1 24 9 36 7 Ad...

Страница 24: ...d input power kW 0 27 2 28 0 41 3 15 0 408 3 91 0 48 3 91 0 64 5 20 Rated input current A 1 17 9 91 1 78 13 69 2 08 17 00 0 69 5 66 0 92 7 53 Maximum input current A 13 5 17 20 7 9 5 Rated RCD A 30 30...

Страница 25: ...18 359 864 320 74 648 IPT16 ALX 334 590 318 359 954 390 74 748 IPT22 ALX 404 720 388 429 1084 640 74 948 A B C D E F G H IPT12 ALY 334 590 318 359 954 74 648 IPT16 ALY 404 590 388 429 954 460 74 755 I...

Страница 26: ...ve To provide frost protection To eliminate corrosion problems To inhibit electrical components 1 Switch off electrical supply to heat pump 2 Remove external fuses and keep in safe place away from hea...

Страница 27: ...he air flow to and from the machine is outside the specified limits If in doubt or if advice is required please contact the Dantherm Group UK Service Department by calling 44 0 1621 856 611 option 4 o...

Страница 28: ...Dantherm Ltd Unit 12 Galliford Road Maldon CM9 4XD United Kingdom 44 0 1621 856 611 sales uk dantherm com Calorex is a brand of danthermgroup com...

Отзывы: