Page 25
SD092750 ISSUE 34
REMOTE CONDENSING UNITS (RCU) FOR USE WITH CALOREX
VARIHEAT MODELS AC500/800/1200/1400/1800 SINGLE AND THREE
PHASE AND MODEL AC4000 THREE PHASE
RCU MODEL
100
200
300
Performance
Cooling Output kW
(Sensible/Total/Rejected to External Ambient)
Model 550 VH
2.0/3.6/5.6
-
-
Model 800 VH
2.65/4.8/7.5
-
-
Model 1200 VH
-
3.3/6.0/9.5
-
Model 1400 VH
-
3.5/6.4/10.6
-
Model 1800 VH
-
-
5.75/10.4/14
Model 4000 VH (2 units required)
-
-
12.1/22/30
Electrical Input
kW
0.36
0.72
0.72
Supply/Fuse 1
Amps
Power supplied from VH unit
Fan Amps
Amps
1.5
2 x 1.5
2 x 1.5
Air Flow
m³/h
2000
3700
3700
External Resistance
mm wg
2
2
2
Noise Level @ 3M
dbA
58
62
64
(Max Fan Speed)
Dimensions
Width
mm
630
1010
1010
Depth
mm
690
690
690
Height
mm
580
580
580
NOTES
(1) Performance data is based on pool Hall air at 28°C, 60%RH, Ambient Air 35°C.
(2) Fan Speed Controller Fitted.
(3) Weight Dimensions Nett.
(4) Calorex reserve the right to change or modify models without prior notice.