Page 25
WARRANTY CONDITIONS.
The following exclusions apply to the Warranty given by Calorex Heat Pumps Ltd. No claims will be accepted if : -
1. The heat pump is incorrectly sized for the application.
2. The heat pump is installed in any way that is not in accordance with the current procedures as defined by
Calorex Heat Pumps Ltd.
3. The heat pump has been worked upon or is adjusted by anyone other than a person authorised to do so
by Calorex Heat Pumps Ltd.
4. The air flow to and from the machine is outside the specified limits.
5. The water flow through the machine is outside the specified limits.
6. The water pH level and/or chemical balance is outside the following limits:-
Acidity
pH:
7.4 ± 0.4
Total Alkalinity, as CaCo
3
ppm
80 -120
Total Hardness, as CaCo
3
ppm
100-300
Total Dissolved Solids:
ppm
MAX 3000
Maximum Salt Content:
wt/wt
6%
Free Chlorine Range:
ppm
1.0 - 3.0
Superchlorination:
ppm
MAX 30 for MAX 24hrs
Bromine:
ppm
2-3
Baquacil:
ppm
25 - 50
Ozone:
ppm
0.8 - 1.0
*Maximum Copper Content:
ppm
MAX 2
*Aquamatic Ionic Purifier:
ppm
MAX 2
*Tarn Pure Purifier:
ppm
MAX 2
*Sherwood Purifier:
ppm
MAX 2
7. The heat pump has suffered frost damage.
8. The electrical supply is insufficient or in anyway incorrect.
Содержание 29 Series
Страница 1: ...Page 1 Owner Installation Manual for AW629 829 AIR WATER HEAT PUMPS SD546250 Issue a...
Страница 27: ...Page 1 Manual d utilisation pour LES POMPES A CHALEUR AIR EAU AW629 829 SD546250 Issue a...
Страница 53: ...Seite 1 Gebrauchsanweisung f r AW629 829 LUFT WASSER W RMEPUMPEN SD546250 Ausgabe a...
Страница 54: ......
Страница 56: ......
Страница 82: ......
Страница 84: ......
Страница 109: ...Pagina 1 Gebruikers en installatiehandleiding voor AW629 829 LUCHT WATER WARMTEPOMPEN SD546250uitgave a...
Страница 110: ......
Страница 112: ......