UV” condition. Additionally, at this point, the controller also provides a signal to
de-‐activate the flow of water if implimented in the system. When the system
registers a low UV condition, the only way to silence the alarms is to correct the
reason for this low UV condition. This may be the result of an aged lamp, or a
fouled sleeve and/or sensor, or perhaps a change in water quality. Please refer
to other sections in this manual for direction on remedying these situations.
CALULTRA Lamp Countdown Sequence
The CALULTRA control panel displays a countdown feature that displays the number of hours remaining
until a lamp change is required. At 512 hours until lamp change the numerical lamp change value will
begin to flash indicating that lamp expiration is near. At “zero hours remaining”, the system register an
audible alarm. If you wish to silence this audible alarm condition, simply press and hold down the button
located directly beneath the top LED screen for a period of three seconds. PLEASE NOTE: During the
condition of lamp expiration, the water may be unsafe for consumption and should not be consumed
without another form of disinfection.
CALULTRA Lamp Countdown Reset Sequence
After changing the lamp on the CALULTRA systems, the control panel must be reset in order for the
system to begin its countdown function on the newly installed lamp. To reset, simply press and hold down
the button located directly beneath the top LED screen for a period of fifteen seconds. Release the button
and the lamp countdown feature has now been reset.
CALULTRA Failure Modes
The CALULTRA control panel continuously monitors your UV system and if there is a problem with the
system the panel will provide both a visual and audible signal indicating the specific fault that may be
adversely affecting the operation of your system. The fault conditions are listed in a priority sequence as
follows:
LAMP FAILURE:
If at any time during the operation of the system, the UV
lamp fails to be illuminated, the controller will return both an audible and
visual signal indicating lamp failure. In addition, a constant audible buzzer will
sound during lamp failure.
Page
16