INTRODUCTION

The LCT-485 is an RS-485 network interface module for the ExTemp infrared temperature
sensor.

This unit, when connected on the safe side of an Intrinsically Safe isolator or barrier, allows
the measured temperature to be read from the ExTemp sensor via the open Modbus RTU
protocol. The sensor’s configuration parameters may also be examined and changed.

Each LCT-485 unit allows communication with one ExTemp sensor. The chosen isolator or
barrier must be compatible with the transmission of digital data superimposed over an
analogue 4-20 mA signal. This allows the LCT-485 to communicate digitally with the ExTemp.

The LCT-485 is a Slave device; up to 224 devices may be connected to a third-party Modbus
Master.

IMPORTANT INFORMATION FOR USE:

The LCT-485 is not suitable for use in a hazardous area. It MUST ONLY be connected in the

safe area, and protected by a suitable Intrinsically Safe isolator or barrier.

Do not attempt to repair a faulty unit. Contact the vendor to arrange a return.

MODEL NUMBERS

LCT-485

RS-485 network interface module for ExTemp sensor

SPECIFICATIONS

Mounting

DIN rail (35 mm)

Communications

Isolated RS-485 Modbus RTU Slave

Dimensions

114(d) x 18(w) x 107(h) mm approx

Connections

Screw terminals for RS-485, power, and sensor loop
(suitable for conductors 0.2 to 2.5 mm²)

Supply voltage

24 V DC (6 V DC min / 28 V DC max)

Max current draw

50 mA

Baud rate

1200 bps to 57600 bps, detected automatically

Bit format

Parity: Odd / Even / None
Stop bits: 1 or 2

Ambient temperature

-20°C to 70°C

Loop resistor

270 Ω, built-in

EMC Conformity

BS EN 61326-1:2013, BS EN 61326-2-3:2013

Max. No. of Devices

Up to 224 x LCT-485 Slave devices per Modbus Master

Reply Delay (at 9600 baud)

ExTemp registers: 1 s max
LCT-485 registers:
30 ms (single register)
50 ms (whole address space)

PREPARATION FOR INSTALLATION
Ambient Temperature

This network interface is designed to operate in ambient temperatures from -20°C to 70°C.

Electrical Interference

To minimise electromagnetic interference or ‘noise’, the network interface should be mounted
away from motors, generators and such like.

Wiring

Check the distances between the Intrinsically Safe isolator or barrier, the Modbus Master, and
the LCT-485 network interface. The LCT-485 conforms to industrial standards for
electromagnetic compatibility with up to 30 m cable attached on the RS-485 side, and 30 m
cable on the 4-20 mA side.

Power Supply

Be sure to use a 24 V DC power supply.

Содержание LCT-485

Страница 1: ...LCT 485 RS 485 Network Interface for ExTemp Infrared Temperature Sensor Operator s Guide...

Страница 2: ...mm Communications Isolated RS 485 Modbus RTU Slave Dimensions 114 d x 18 w x 107 h mm approx Connections Screw terminals for RS 485 power and sensor loop suitable for conductors 0 2 to 2 5 mm Supply v...

Страница 3: ...dbus repeater allows longer cable on the Master side Connections with Intrinsically Safe Isolator Connections with Zener Barrier LCT 485 LCT 485 4 270 1 13 14 13 14 12 12 11 11 2 3 IS Isolator Power S...

Страница 4: ...onnections RS 485 Modbus Network All the below connections are on the safe side of the Intrinsically Safe isolator or barrier 4 Ensure the distance between each device and the network bus is as short...

Страница 5: ...peration by completing the following simple steps 1 Turn on the power supply 2 Turn on the indicator if fitted 3 Send a test message to confirm communications with LCT 485 are good we recommend readin...

Страница 6: ...Reserved Bit 2 Hold processing on 1 off 0 Bit 3 Hold peaks 1 valleys 0 Bits 4 6 Reserved Bit 7 Reflected energy compensation on 1 off 0 Bits 8 15 Reserved 3 0x0D 13 R W Average period 1 LSB 250 ms 1...

Страница 7: ...will automatically measure and set the baud rate It will then try all the possible combinations of stop bit and parity settings until it finds the correct values 4 The LCT 485 will detect when good co...

Страница 8: ...help contact us for further advice TROUBLESHOOTING Symptom Probable Cause Solution No communications No power to the device Check the power supply and wiring Incorrect Modbus Slave address Check the...