background image

6

Temperature adjustment

Set the desired recirculation system temperature by turning 
the adjustment knob. The graduated scale shows the 
temperatures at which the indicator can be set. 

Adjustment locking

After adjusting the temperature, the setting can be locked 
at the desired value using the adjustment knob. Unscrew 
the locking screw at the top of the adjustment knob, 
remove the knob and then put it back on so that the internal 
groove couples with the protrusion on the knob holder nut. 
When this block is used, the reference of the indication of 
the temperature values on the knob is lost. To restore it, 
completely unscrew the lcoking screw. Reposition the knob 
on MAX value. Tighten the locking screw.

Maintenance

The balancing adjustment cartridge can be removed 
from the valve body for periodic inspection, cleaning or 

Insulation shell

The ThermoSetter 1164 series thermal balancing valve 
can be supplied with an optional insulation shell, code 

CBN116440

 purchased separately, to minimize heat loss. 

Содержание ThermoSetter 116010

Страница 1: ...uge w and w o check valve connections and NPT female www caleffi com The valve is ICC ES certified to NSF ANSI 61 180 F 82 C Commercial Hot and NSF ANSI 372 low lead laws It meets codes IPC IRC UPC and NPC for use in accordance with the US and Canadian plumbing codes NSF 61 Technical specifications Materials Body DZR low lead brass EN 12165 CW724R Adjustable cartridge PSU Springs Stainless steel E...

Страница 2: ...lubricity so that care must be exercised not to over tighten joints Failure to follow these instructions could result in property damage and or personal injury WARNING System fluids are under pressure or temperature can be hazardous Be sure the pressure has been reduced to zero and the system temperature is below 100 F 38 C Failure to follow these instructions could result in property damage and o...

Страница 3: ...a température peuvent être dangereux Être sûr que la pression a été réduite à zéro et la température du système est inférieure à 100 F 38 C Le non respect de ces instructions peut entraîner des dommages matériels et ou des blessures Le non respect de ces instructions peut entraîner des dommages matériels et ou des blessures ATTENTION Si le vanne d équilibrage Série ThermoSetter n est pas installé ...

Страница 4: ...130 140 180 150 160 170 Tset 2 1 0 35 Cvdesign 0 69 1 2 3 1 2 3 1 2 3 Thermostatic control 1164xxA series Thermostatic control with check valve 11614xAC series Installation Before installing the ThermoSetter flush the pipes to make sure that impurities in system will not interfere with valve performance Strainers of sufficient capacity at the inlet from the water main are highly recommended The Th...

Страница 5: ...loss calculations in the recirculation system follow traditional pipe sizing and head loss practices For pressurelosscalculations across the ThermoSetter valve use the design curve shown in the graph below This line represents a typical valve position under normal working conditions T 10 F Determinethepressure drop across the valve by selecting the branch design GPM on the graph X axis draw a vert...

Страница 6: ...it back on so that the internal groove couples with the protrusion on the knob holder nut When this block is used the reference of the indication of the temperature values on the knob is lost To restore it completely unscrew the lcoking screw Reposition the knob on MAX value Tighten the locking screw Maintenance The balancing adjustment cartridge can be removed from the valve body for periodic ins...

Страница 7: ...7 Application diagram 135 F 135 F 135 F 140 F 120 F NOTE Do not set at temperatures 120ºF if anti scald valves are not installed at the fixtures Hot water recirculation with thermal balancing valves ...

Страница 8: ...Caleffi North America Inc 3883 W Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 3 20 2020 NOTES 8 ...