Maintenance

Both the balancing adjustment cartridge and the disinfection control cartridge can be removed from 
the valve body for periodic inspection, cleaning or replacement.

Innsulation shell

The ThermoSetter thermal balancing valve can be supplied with an optional insulation shell, code 
CBN116140 purchased separately, to minimize heat loss. 

Содержание ThermoSetter 116 Series

Страница 1: ...actuator disinfection function models w and w o temperature gauge w and w o check valve connections NPT female 1166 series ThermoSetter w disinfection function by pass cartridge 140 F 60 models w and...

Страница 2: ...ubricity so that care must be exercised not to over tighten joints Failure to follow these instructions could result in property damage and or personal injury WARNING System fluids are under pressure...

Страница 3: ...la temp rature peuvent tre dangereux tre s r que la pression a t r duite z ro et la temp rature du syst me est inf rieure 100 F 38 C Le non respect de ces instructions peut entra ner des dommages mat...

Страница 4: ...C Factory setting 130 F 55 C Disinfection temperature 1162xx series 160 F 70 C 1166xx series 140 F 60 C Closing temperature 1162xx series 170 F 75 C 1166xx series 150 F 65 C Max inlet temperature 195...

Страница 5: ...using flow and thus temperature to increase back to the set temperature as shown in curve 1 If temperature exceeds the set point the plug stays in the minimum closed position as shown in curve 2 The b...

Страница 6: ...ath up until the by pass temperature is attained shown in curve 3 If the temperature continues rising beyond this point the flow is reduced through the by pass port to allow thermal balancing even dur...

Страница 7: ...case the minimum head loss is produced during this thermal disinfection process Installation Before installing the ThermoSetter flush the pipes to make sure that impurities in system will not interfe...

Страница 8: ...NPT F 4 5 7 16 3 1 7 0 75 116150A C NPT F 4 5 5 8 3 1 5 0 70 116151A C NPT F 4 5 5 8 3 1 5 0 70 Models with check valve tail piece C end to end dimension is B with integral outlet temperature gauge B...

Страница 9: ...mal working conditions T 10 F Determine the pressure drop across the valve by selecting the branch design GPM on the graph X axis draw a vertical line up to the design curve then go across to the Y ax...

Страница 10: ...e this is the minimum flow rate at the mixing valves in the central heating system Adjustment locking After adjusting the temperature the setting can be locked at the desired value using the adjustmen...

Страница 11: ...ion control cartridge can be removed from the valve body for periodic inspection cleaning or replacement Innsulation shell The ThermoSetter thermal balancing valve can be supplied with an optional ins...

Страница 12: ...0 F 130 F 140 F 120 F NOTE Do not set at temperatures 120 F if anti scald valves are not installed at the xtures Hot water recirculation with thermal balancing valves 230 V 50 Hz THERMAL DISINFECTION...