Maintenance

Both the balancing adjustment cartridge and the disinfection control cartridge can be removed from 
the valve body for periodic inspection, cleaning or replacement.

Innsulation shell

The ThermoSetter thermal balancing valve can be supplied with an optional insulation shell, code 
CBN116140 purchased separately, to minimize heat loss. 

Содержание ThermoSetter 116 Series

Страница 1: ...and w o temperature gauge w and w o check valve connections and NPT female 1163 series ThermoSetter w actuator disinfection function models w and w o temperature gauge w and w o check valve connection...

Страница 2: ...ubricity so that care must be exercised not to over tighten joints Failure to follow these instructions could result in property damage and or personal injury WARNING System fluids are under pressure...

Страница 3: ...la temp rature peuvent tre dangereux tre s r que la pression a t r duite z ro et la temp rature du syst me est inf rieure 100 F 38 C Le non respect de ces instructions peut entra ner des dommages mat...

Страница 4: ...table temperature range 95 140 F 35 60 C Factory setting 130 F 55 C Disinfection temperature 160 F 70 C Closing temperature 170 F 75 C Max inlet temperature 195 F 90 C Cv Kv max 2 1 1 8 Cv Kv dis 1 2...

Страница 5: ...3 5 4 6 7 8 1 Function B Automatic thermostatic disinfection The 1162xx series operating characteristic curves for operating mode B are curves 1 2 3 and 4 When a temperature higher than about 155 F 68...

Страница 6: ...case the minimum head loss is produced during this thermal disinfection process Installation Before installing the ThermoSetter flush the pipes to make sure that impurities in system will not interfe...

Страница 7: ...750 0 700 15 20 B B Code A B B C D Wt lb kg 116140A C NPT F 4 5 7 16 3 1 7 0 75 116141A C NPT F 4 5 7 16 3 1 7 0 75 116150A C NPT F 4 5 5 8 3 1 5 0 70 116151A C NPT F 4 5 5 8 3 1 5 0 70 Models with c...

Страница 8: ...mal working conditions T 10 F Determine the pressure drop across the valve by selecting the branch design GPM on the graph X axis draw a vertical line up to the design curve then go across to the Y ax...

Страница 9: ...e this is the minimum flow rate at the mixing valves in the central heating system Adjustment locking After adjusting the temperature the setting can be locked at the desired value using the adjustmen...

Страница 10: ...ion control cartridge can be removed from the valve body for periodic inspection cleaning or replacement Innsulation shell The ThermoSetter thermal balancing valve can be supplied with an optional ins...

Страница 11: ...120 F if anti scald valves are not installed at the xtures Hot water recirculation with thermal balancing valves 230 V 50 Hz THERMAL DISINFECTION CONTROL UNIT B A S INTERFACE Master mixing valve for...

Страница 12: ...Caleffi North America Inc 3883 W Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 4 3 19...