SENSONICAL ULTRA heat meter

1

CAL19185M series

©  Copyright  2014  Caleffi

Technical specifications

Connection

3/4’’ M

Probe connection

M10x1

Nominal pressure

PN 16

Measurable working temperature range

3–90°C

Type of probes

Pt 1000 with platinum precision resistance element 

Probe cable length

1,5 m

Type of volume meter

ultrasonic

Nominal flow rate

2,5 m

3

/h

Sensitivity

12 l/h

Protection class

IP 54

Power supply

3V lithium battery, life > 6 years

Data reading

via button-activated LCD

Data transmission interface

M-Bus

Data memory

E

2

PROM

Working ambient temperature

5–55°C

Storage temperature and conditions

5–45°C without humidity

Accuracy class

Dir.2004/22/EC - class 2

Marks

CE for measuring instruments and electromagnetic compatibility

Manufacturer certificate

ISO 9001 

Dimensions

78234EN

www.caleffi.com

110

75

E

F

E

F

Product range

CAL19185M M-bus heating/cooling energy meter.
CAL19185MI M-bus heating/cooling energy meter with 2 pulse inputs.
CAL19185MU M-bus heating/cooling energy meter with 2 pulse outputs.

Содержание SENSONICAL ULTRA CAL19185M Series

Страница 1: ...ly 3V lithium battery life 6 years Data reading via button activated LCD Data transmission interface M Bus Data memory E2 PROM Working ambient temperature 5 55 C Storage temperature and conditions 5 4...

Страница 2: ...g the hydraulic section 6 The correct positioning of the hydraulic section of SENSONICAL ULTRA is on the return pipe attention must be paid to observe the correct direction of the flow The temperature...

Страница 3: ...the ball valve TEE d Insert the probe and adjust its depth of immersion by means of the nipple e Tighten until it stops Commissioning the meter a Slowly open the shut off device check the hydraulic t...

Страница 4: ...n be displayed are split into three levels and can be viewed using the selection button The standard mode without pressing the button shows the total heating and cooling energy consumption since the s...

Страница 5: ...and pulse input meters 1 4 Total volume in m3 5 Instantaneous power in kW 6 Instantaneous flow rate in m3 h 7 Current date in format DD MM YY 8 Error Message alternating binary and hexadecimal display...

Страница 6: ...g item 8 error message on the main level The instrument detects eight causes of error indicated by the number 1 in the eight digit code of the error message These causes of error can also occur togeth...

Страница 7: ...nergy logs are not updated the new data are not saved No calculations are performed The flow rate and energy logs are not updated the new data are not saved No calculations are performed The flow rate...

Страница 8: ...master as an additional protective measure The instruments can be installed in an M Bus network by authorized and qualified personnel only Make sure that the structure of the M Bus network length and...