FAULT DESCRIPTION

ALERTS

POSSIBLE CAUSE OF FAULT

OPERATIONS TO BE PERFORMED

Domestic hot 

water is not 

heated

blinking 

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

  

icon

 primary circuit shut-off valves closed

open the valves

modulating valve actuator disconnected from valve body

reconnect actuator

modulating valve actuator faulty

call qualified personnel to have it replaced

DHW temperature probe cable inverted with heating probe

restore correct connection

presence of air in the system

vent the system

electronic regulator not working

call qualified personnel to have it replaced

valve obturator blocked in closed position

call qualified personnel to have it replaced

centralised system not working/cold

contact person in charge of system

error code 6 active

DHW temperature probe disconnected

reconnect probe

DHW temperature probe faulty

call qualified personnel to have it replaced

error code 80 active

incorrect wiring/no credit

check electrical connections/top up credit

fixed 

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

  

icon

DHW priority flow meter disconnected

reconnect flow meter

DHW priority flow meter faulty

call qualified personnel to have it replaced

icon 

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

 absent

DHW production not enabled

enable DHW production by means of HIU 

interface

display is off

electric supply cut off

restore HIU electric supply

protection fuse burnt out

call qualified personnel to have it replaced

The water is 

hot but does 

not reach 

the desired 

temperature

blinking 

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

  

icon

domestic water cycle temperature set point too low

increase set point

primary return temperature limitation intervention

change the return temperature set point/

disable the function

primary circuit strainer of the HIU clogged

call qualified personnel to have it serviced

exchanger partly clogged

call qualified personnel to have it serviced

modulating valve actuator faulty

call qualified personnel to have it replaced

DHW temperature probe cable inverted with heating probe

restore correct connection

excessive demand for DHW

decrease demand

electronic controller not working

call qualified personnel to have it replaced

centralised system temperature insufficient

contact person in charge of system

primary circuit flow rate insufficient

contact person in charge of system

primary flow rate limit too low

contact person in charge of system

Hot water 

temperature is 

too high

blinking 

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

  

icon

domestic water cycle temperature set point too high

decrease set point

DHW temperature probe cable inverted with heating probe

restore correct connection

modulating valve actuator faulty

call qualified personnel to have it replaced

valve obturator blocked in intermediate or open position

call qualified personnel to have it replaced

electronic regulator not working

call qualified personnel to have it replaced

primary circuit excessive flow rate due to DPCV valve 

malfunction

call qualified personnel to have it replaced

Antilegionella cycle in progress

contact person in charge of system

Hot water 

flow rate is 

insufficient

blinking 

mandata a punto fisso

impostazione temperatura di 

mandata

limite temperatura ritorno

alta/bassa temperatura

compensazione

intervento limite temperatura ritorno

climatica

 

icon

HIU strainer clogged

call qualified personnel to have it serviced

possible domestic water system shut-off valves 

partially closed

open the valves

insufficient pressure in centralised domestic water circuit

call qualified personnel to have it serviced

Hot water flow 

rate is zero

-

possible domestic water system shut-off valves closed

open the valves

no cold water in centralised domestic circuit

call qualified personnel to have it serviced

HIU strainer completely clogged

call qualified personnel to have it serviced

exchanger completely blocked

call qualified personnel to have it serviced

Troubleshooting

Содержание SATK32107 Series

Страница 1: ...stallation 5 Hydraulic components and diagram 4 Dimensions Technical specifications 3 Safety instructions 2 DHW function Comfort functions Primary flow rate limitation Circulator curves and setting Au...

Страница 2: ...lled and in compliance with current legislation 5 The device must always be earthed before it is connected to the electric supply If the device must be removed always disconnect the earth connection a...

Страница 3: ...nimum flow rate to activate domestic water flow meter 2 l min 0 3 Electric supply 230 V AC 10 50Hz Max power consumption 80 W Protection class IP 40 Pump UPM3 15 70 Actuators 24 V stepper motor Probes...

Страница 4: ...9 Return temperature probe 10 Pressure gauge 11 Safety thermostat 12 130 mm heat meter template 13 1 4 F pressure test port 14 Connection for M10x1 heat meter return probe 15 Primary drain cock 16 Con...

Страница 5: ...aulic installation Preliminary operations installation without template After having established the point of installation of the appliance perform the following operations Mark the holes required for...

Страница 6: ...m in order to remove any residue or impurities that could endanger correct operation of the HIU In order to facilitate these operations a manual bypass flushing valve is available code 789110 N B In t...

Страница 7: ...pipe To tighten the nuts apply maximum tightening torque of 25 Nm taking account of the indications of the heat meter manufacturer install the flow probe in the M10 pocket B Please refer to the heat m...

Страница 8: ...ctric supply Remote user interface connection The HIU user interface has the dual function of control device and room thermostat The remote user interface can be installed on board the HIU or in the r...

Страница 9: ...to the HIU and check for the presence of any error signal If there is any eliminate the fault indicated see page 18 and proceed with setting the set point of the domestic water and heating cycles pro...

Страница 10: ...rature compensation day night Daytime night time setting temp Temperature display ambient set point probes prog Heating hourly programming and comfort function reset Resettable error reset floor slab...

Страница 11: ...on day night Daytime night time setting temp Temperature display ambient set point probes prog Heating hourly programming and comfort function reset Resettable error reset floor slab heating function...

Страница 12: ...e the modulating valve is opened gradually until the set point temperature is reached if the return temperature is lower than or equal to the set limit value In case this condition is not met the flow...

Страница 13: ...es is 42 60 C while the range of possible return temperatures is 15 45 C if these set points cannot be changed you must set parameter t07 to value 0 in the technical menu see access to technical menu...

Страница 14: ...DHW production The flow rate limitation is imposed by controlling the maximum opening of the primary circuit modulating valve Since latter is controlled by a differential pressure limiter it is possib...

Страница 15: ...two seconds and then press the same key repeatedly until reaching the required characteristic refer to the figure below Having identified the required characteristic head flow rate chart shown below w...

Страница 16: ...ow pump normally OFF The contact must be closed if any HIU function is active DHW production heating pre heating Parameter t05 must be set to 1 2 4 7 This value t05 7 is set by default example 2 Disti...

Страница 17: ...ire twisted cable Compliance with this requirement becomes even more significant the more extensive the RS 485 network If alternatively a shielded wire is used the shield must be connected solely on t...

Страница 18: ...m an external device indicating zero credit Corrective action Check the electrical connections or in the case of zero credit top up the external device contact the service supplier Heat interface unit...

Страница 19: ...RT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT T ORT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT T LAVORATI ANGOLI 30 TOLLERANZA GENERALE ANGOLI EXP PORT OTS RT PREPAID AUX RS 485 BUS IN IN IN OUT IN OU...

Страница 20: ...ween 0 9 and 1 2 bar Restore the pressure value if necessary Re open the shut off valves and restore secondary circuit pressure to a value between 1 3 and 1 7 bar Check for the absence of any liquid d...

Страница 21: ...tuator see previous paragraph Extract the obturator unscrewing the locking nut F Replace the obturator screw on the locking nut F and then fit the actuator Insert the fixing clip respecting the correc...

Страница 22: ...ature set point disable the function primary circuit strainer of the HIU clogged call qualified personnel to have it serviced exchanger partly clogged call qualified personnel to have it serviced modu...

Страница 23: ...in charge of system electronic regulator not working call qualified personnel to have it replaced primary circuit flow rate insufficient contact person in charge of system centralised system not worki...

Страница 24: ...ernal sensor prepayment auxilliary microswitch Modbus if required been carried out 15 Has the remote user interface been configured for installation on board thermostat function disabled inside the ap...

Отзывы: