FAULT DESCRIPTION

ALERTS

POSSIBLE CAUSE OF FAULT

OPERATIONS TO BE PERFORMED

The room 

does not reach

the desired

temperature

blinking 

icon

   

 

 

   

 

 

 

 

 

 

heating cycle temperature set point too low

increase set point

chrono-thermostat temperature setting incorrect

check programming of chrono-thermostat

HIU strainer clogged

call qualified personnel to have it serviced

primary return temperature limitation intervention (the

following icon appears 

)

   

 

 

   

 

 

 

 

 

 

change the return temperature set

point/disable the function

primary flow rate in heating mode set at an excessively

low limit

change heating valve opening limit

heating valve actuator faulty

call qualified personnel to have it replaced

heating valve obturator blocked

call qualified personnel to have it replaced

modulating valve actuator connector disconnected

reconnect actuator connector

DHW temperature probe cable inverted with heating probe

restore correct connection

presence of air in the system

vent the system

pump not working

call qualified personnel to have it replaced

pump cable not connected

restore connection

possible system shut-off valves/terminals closed

open the valves

centralised system temperature insufficient

contact person in charge of system

electronic regulator not working

call qualified personnel to have it replaced

primary circuit flow rate insufficient

contact person in charge of system

centralised system not working

contact person in charge of system

thermostat function enabled on the remote user interface

when it should be disabled

contact person in charge of system

fixed 

icon 

   

 

 

   

 

 

 

 

 

 

chrono-thermostat time setting incorrect

check programming of chrono-thermostat

chrono-thermostat not working

check chrono-thermostat

thermostat function disabled on the remote user interface

contact person in charge of system

display is off

Electric supply cut off

restore HIU electric supply

Protection fuse burnt out

call qualified personnel to have it replaced

icon 

absent

   

 

 

   

 

 

 

 

 

 

Heating not enabled (summer mode)

enable heating by means of heat interface

unit

error code 4 active

heating circuit pressure too low

restore system pressure

error code 5 active

heating temperature probe faulty

call qualified personnel to have it replaced

error code 15 active

compensation temperature probe faulty

call qualified personnel to have it replaced

error code 38 active

external temperature probe faulty/not connected

call qualified personnel to have it replaced

error code 69 active

safety thermostat cut-out

press the reset button/call qualified

personnel to have it serviced

error code 80 active

no credit

top-up prepaid system

Содержание SATK32105

Страница 1: ...de 10 Commissioning 9 Electrical installation 8 Hydraulic installation 5 Hydraulic components and diagram 4 Dimensions Technical specifications 3 Safety instructions 2 DHW function Comfort functions P...

Страница 2: ...k must be carried out on the device cut off the electric supply first Do not use devices with automatic or time reset or which may be reset accidentally 4 Use suitable automatic protection devices in...

Страница 3: ...nimum flow rate to activate domestic water flow meter 2 l min 0 3 Electric supply 230 V ac 10 50Hz Max power consumption 80 W Protection class IP 40 Pump UPM3 15 70 Actuators 24 V stepper motor Probes...

Страница 4: ...be 10 Pressure gauge 11 Safety thermostat 12 130 mm heat meter template 13 1 4 F pressure test port 14 Connection for M10x1 heat meter return probe 15 Primary drain cock 16 Connection for M10x1 heat m...

Страница 5: ...kflow preventer code 572120 proceed as follows remove the nuts shown in the figure with letter A Hydraulic installation Preliminary operations installation without template After having established th...

Страница 6: ...tem in order to remove any residue or impurities that could endanger correct operation of the HIU In order to facilitate these operations a manual bypass flushing valve is available code 789110 N B In...

Страница 7: ...pipe To tighten the nuts apply maximum tightening torque of 25 Nm taking account of the indications of the heat meter manufacturer install the flow probe in the M10 pocket B Please refer to the heat m...

Страница 8: ...directed toward the exterior of the HIU using the pathways provided in the insulation and on the frame All the low voltage lines must be routed through a single dedicated cable raceway using the path...

Страница 9: ...necessary restore the pre charge value shown in the technical specifications Filling the user system SATK32 series HIU can be fitted with a charging unit equipped with a backflow preventer F check va...

Страница 10: ...ng modes OFF DHW only summer mode Heating DHW winter mode Heating only Selecting set points current time and comfort function Press the set key repeatedly to set the current time set point temperature...

Страница 11: ...arious parameters which can then be edited pressing and rotating knob R Technical parameter t00 Primary limit set return temperature in heating mode Primary limit set return temperature in DHW mode Co...

Страница 12: ...ng To set the flow temperature press the SET key until the symbol in the red circle appears for the return temperature limit press the key until the symbols in the green circle are displayed Use the R...

Страница 13: ...7 1 freezes the operating set points to prevent inadvertent modifications by the user The comfort function can be alternatively preheating of the DHW plate heat exchanger or management of DHW recircul...

Страница 14: ...posed by controlling the maximum opening of the primary circuit modulating valve Since latter is controlled by a differential pressure limiter it is possible to supply direct correspondence between th...

Страница 15: ...es a sequence of LEDs showing the instantaneous power consumption 1 yellow LED lit power between 0 and 25 of Pmax 2 yellow LEDs lit power between 25 and 50 of Pmax 3 yellow LEDs lit power between 50 a...

Страница 16: ...must be set to 1 2 4 7 This value t05 7 is set by default example 2 Distinction of consumption for DHW production from total consumption in combination with heat meter equipped with dedicated function...

Страница 17: ...ire twisted cable Compliance with this requirement becomes even more significant the more extensive the RS 485 network If alternatively a shielded wire is used the shield must be connected solely on t...

Страница 18: ...nd disabled Any requests to run cycles not associated to the previous one will continue to run normally Heating flow probe fault Error code 5 Domestic hot water probe fault Error code 6 Return probe f...

Страница 19: ...o be interfaced with controllers managing the heating and DHW production services by means of pre paid type logic The HIU interprets an open contact as credit available Closing the contact disables th...

Страница 20: ...ween 0 9 and 1 2 bar Restore the pressure value if necessary Re open the shut off valves and restore secondary circuit pressure to a value between 1 3 and 1 7 bar Check for the absence of any liquid d...

Страница 21: ...tuator see previous paragraph Extract the obturator unscrewing the locking nut F Replace the obturator screw on the locking nut F and then fit the actuator Insert the fixing clip respecting the correc...

Страница 22: ...r partly clogged call qualified personnel to have it serviced modulating valve actuator faulty call qualified personnel to have it replaced DHW temperature probe cable inverted with heating probe rest...

Страница 23: ...in charge of system electronic regulator not working call qualified personnel to have it replaced primary circuit flow rate insufficient contact person in charge of system centralised system not work...

Страница 24: ...s external sensor prepayment auxilliary microswitch Modbus if required been carried out 15 Has the remote user interface been configured for installation on board thermostat function disabled inside t...

Отзывы: