background image

9

PVC jumper nipple with male union 

thread. The length of the jumper nipple 

matches the 535H valve face-to-face 

dimension, allowing the piping to be 

completed prior to the installation of valve 

and permitting quick change out from the 

jumper to the valve.

Code

Description

Face-to-Face 

Dimension

NA11304

Jumper nipple for 535H ½" series

3"

NA11305

Jumper nipple for 535H ¾" series

9/16

"

NA11306

Jumper nipple for 535H 1" series

3 ¾"

NA11307

Jumper nipple for 535H 1¼" series

5/16

"

NA11308

Jumper nipple for 535H 1½" series

4 ¾"

NA11309

Jumper nipple for 535H 2" series

5 ¼"

Содержание PresCal 5355H Series

Страница 1: ...SE 1003 CSA B356 NSF ANSI 61 180 F 82 C Commercial Hot NSF ANSI 372 low lead laws and listed by ICC ES It meets codes IPC IRC and UPC for use in accordance with the US and Canadian plumbing codes Prod...

Страница 2: ...maintenance of the 535H PRV take the necessary precautions to ensure that such temperatures do not endanger people Leave this manual for the user SAFETY INSTRUCTION This safety alert symbol will be u...

Страница 3: ...en service et l entretien de le r ducteur de pression S rie 535H prendre les precautions n cessaires afin de s assurer que de tells temp ratures ne compromettent pas les gens LAISSEZ CE MANUEL AVEC L...

Страница 4: ...actory setting 45 psi 3 bar Max working temperature 180 F 80 C Pressure gauge scale 0 100 psi 0 7 bar Filter mesh size 0 51 mm 35 mesh Suitable fluids water Main connections NPT female and sweat union...

Страница 5: ...1 2 3 4 1 1 1 1 4 1 1 2 2 0 45 5 V m s 0 1 4 3 0 3 1 1 4 535074 5 1 1 1 4 1 2 3 4 1 2 5 0 2 10 20 20 50 00 Flow rate min m 3 h 00 5 10 1 5 V f s 0 3 15 10 1 8 20 90 Flow rate s gpm 30 40 10 5 2 1 0 9...

Страница 6: ...noise in the pipes and rapid wear of appliances The correct diameter of the pressure reducing valve is taken from graph 1 on the basis of the design flow rate taking into account an ideal flow velocit...

Страница 7: ...pressure reducing valve to be set to the required value in the system prior to installation The pressure indicator features incremental step movement so that the pressure can be adjusted continuously...

Страница 8: ...is highly recommended to refer to the working conditions represented in the above diagram Due to the numerous factors and variable conditions experienced such as system pressure water temperature air...

Страница 9: ...llation of valve and permitting quick change out from the jumper to the valve Code Description Face to Face Dimension NA11304 Jumper nipple for 535H series 3 NA11305 Jumper nipple for 535H series 3 9...

Страница 10: ...and clean the cartridge at least every 12 months The cartridge containing the diaphragm strainer seat valve plug and compensating piston is pre assembled as a self contained unit with a cover and can...

Страница 11: ...etween the pressure reducing valve and the water heater to absorb the increased pressure caused by water expansion from heating 2 The pressure reducing valve does not maintain downstream setting value...

Страница 12: ...Caleffi North America Inc 3883 W Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 12 Leave this manual at the service of users for their use 04 6 19...