background image

6

Installation

The Caleffi NA51 series spring check valve may be installed in either a vertical or horizontal position. 
Pipe lines should be thoroughly cleaned and flushed before installing the check valve. A strainer should 
be installed ahead of the check to prevent unnecessary malfunction. Install shutoff valves on inlet and 
outlet of check to facilitate servicing and maintenance. Install the check valve with the arrow on the valve 
body pointing in the direction of flow. Allow a minimum of 5 pipe diameters upstream straight pipe to 
reduce turbulence at the check valve.

Service and Maintenance

Turn off supply water, or make sure inlet and outlet shutoff valves are in closed position, before servicing. 
The Caleffi NA51 series check valves have union connections for easy removal to inspect, clean, and 
either replace the plastic check valve insert, or replace the entire check valve altogether. The check 
valve may be disassembled and cleaned to remove dirt, debris or scale. Always use new washers when 
reassembling and do not over tighten the union nuts. The plastic check valve insert can be replaced, if 
necessary, using a hammer and punch; it cannot be re-used, a new check valve insert will be necessary.

Содержание NA51 Series

Страница 1: ...ion connections flowing Cv 30 sizes 1 and 1 NA5214 series with NPT female and male threaded press PEX crimp and expansion and sweat dual union connections flowing Cv 75 sizes 1 and 2 Technical specifi...

Страница 2: ...e must be exercised not to over tighten joints Failure to follow these instructions could result in property damage and or personal injury WARNING System fluids under pressure or temperature can be ha...

Страница 3: ...pect de ces instructions peut entra ner des dommages mat riels et ou des blessures AVERTISSEMENT Les liquides du syst me sont sous pression ou de la temp rature peuvent tre dangereux tre s r que la pr...

Страница 4: ...A C B A A A A A NPT female sweat press PEX crimp A A PEX expansion A A Dimensions Lay length press 2 7 16 inch press 2 5 16 inch 1 press 4 inch 1 press 5 7 8 inch 1 press 5 1 8 inch 2 press 7 7 8 inch...

Страница 5: ...16 NA51257 PEX crimp 4 15 16 NA51258 PEX expansion 5 5 8 NA51300 1 metric no fittings 1 1 1 5 NA51360 1 NPT Male 4 1 8 1 1 8 2 0 NA51369 1 SWT 3 7 8 NA51363 1 NPT Female 3 7 8 NA51366 1 press 5 7 8 NA...

Страница 6: ...iameters upstream straight pipe to reduce turbulence at the check valve Service and Maintenance Turn off supply water or make sure inlet and outlet shutoff valves are in closed position before servici...

Страница 7: ...NOTES 7...

Страница 8: ...ulation circulator on each branch return cold water check valves Caleffi North America Inc 3883 West Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 05 2023 For Technical Support call...

Отзывы: