background image

Function

The Caleffi  MixCal™ three-way thermostatic mixing valve is used in systems 
producing domestic hot water or in hydronic and radiant heating systems. 
It maintains the desired output temperature of the mixed water supplied to 
the user at a constant set value compensating for both temperature and 
pressure fl uctuations of incoming hot and cold water. 

Product range

521A Series Three-way thermostatic mixing valve: 
“C” models include inlet check valves “419, 519, 619” models include 
outlet gauge adapter. Union thread NPT Male, sizes ½”, ¾”, 1”; Union 
sweat, size ½”, ¾”, 1”. Press connection ¾”.

Technical Characteristics

Materials:     -Body:                        low-lead brass (

<

0.25% Lead content)

                    -Shutter, seats and sliding guides:                                  PPO
                    -Springs:                                                         Stainless steel
                    -Seals:                                                                         EPDM
Suitable fl uids:                                           water, 30% max glycol solution    
Setting range (outlet temperature):                             85–150

°

F (30–65

°

C)

Tolerance:                                                                               ±3

°

F

 

(±2

°

C)

Max working pressure (static):                                           200 psi (14 bar)
Max working pressure (dynamic):                                          75 psi (5 bar)
Hot water inlet temperature range:                          120–185

°

F (49–85

°

C) 

Cold water inlet temperature range:                         39–80

°

F (3.9–26.6

°

C)

Maximum  inlet  pressure  ratio  (H/C  or  C/H)  for  optimum  performance:              2:1                                      
Minimum temperature difference between hot water inlet and mixed
  water outlet for optimum performance:                                  27ºF (15ºC)
Minimum fl ow rate to ensure optimal performance:       1.3 GPM (5 L/min)
Lay length (¾” press connection), hot to cold inlet:                            3

7

/8”  

Maximum fl ow rate:    

 

                15 GPM(57 L/min)

Certifi ed to:                                 cUPC listed to ASSE 1017/CSA B125.3 
Reduction of Lead in Drinking Water Act compliant:        0.25% Max. weighted 
 

 

 

                                  average lead content

Reduction of Lead in Drinking Water Act Certifi ed by IAPMO R&T. Meets 
requirements of ANSI/ NSF 372-2011.

MixCal™ adjustable three-way thermostatic mixing valve

 

 

521 Series

38476.08

www.caleffi.com

© Copyright 2015 Caleffi

Installation, commissioning and service instructions

Содержание MixCal 521400A

Страница 1: ...et temperature 85 150 F 30 65 C Tolerance 3 F 2 C Max working pressure static 200 psi 14 bar Max working pressure dynamic 75 psi 5 bar Hot water inlet temperature range 120 185 F 49 85 C Cold water in...

Страница 2: ...thermostatic mixing valve take the necessary precautions to ensure that such temperatures do not endanger people CAUTION In the case of highly aggresive water arrangements must be made to treat the w...

Страница 3: ...hot or cold water for other uses or variations in the incoming temperature the thermostatic mixing valve automatically regulates the water flow to obtain the required temperature COLD HOT MIX Inlet p...

Страница 4: ...the system must be inspected to ensure that it s operating conditions are within the range of the thermostatic mixing valve checking for example the supply temperature supply pressure etc Systems wher...

Страница 5: ...19A and 521619A with integral outlet port temperature gauges provide a time saving temperature setting process to get close to the desired temperture Use of a digital thermometer is recommended for de...

Страница 6: ...k valves MIX 3 2 4 SUPPLY HOT COLD MIX BOILER SUPPLY MIX 3 2 4 MIX 3 2 4 Safety relief valve Check valve Isolation valve Expansion vessel Filter Pump WATER HEATER WATER HEATER CALEFFI CALEFFI CALEFFI...

Страница 7: ...caused by impuritites 3 Limescale can be removed from internal components of the thermostatic mixing valve by immersion in a suitable de scaling fluid 4 When the components which can be maintained hav...

Страница 8: ...Restore inlet conditions within the limits of the valve Erratic flow of water from the valve a Insufficient water supplies b Fluctuations in the supply pressures temperatures c Adverse effect created...

Отзывы: