![background image](http://html.mh-extra.com/html/caleffi/fpc-n34-1618/fpc-n34-1618_instruction-sheet_483470019.webp)
19
Point Name
BACnet Object Type
BACnet Object ID
Description
Minute
AV
37
0...59
Check Battery
BV
38
1 = confirmed ; 0 = not confirmed
Day-hour
BV
39
1 = confirmed ; 0 = not confirmed
Daylight Saving Time
BV
40
1 = enabled ; 0 = not disabled
Time Format
BV
41
1 = 12H ; 0 = 24H
Temperature Unit
BV
42
1 = °F ; 0 = °C
U.S. daylight Saving Time
BV
43
1 = enabled ; 0 = disabled
Disinfection Control
BV
44
1 = on T2 ; 0 = on T1
Encoder Steps Acquisition
BV
45
1 = encoder steps acquisition
Set Point Temperature
AV
46
350...650 (°C/10)
Disinfection Type Mode
BV
47
00 = In1 ; 01 = In2 ; 10 = In3
Disinfection Type Propagation Time
BV
48
1 = fixed ; 0 = calculated
Disinfection Type ECO Function
BV
49
1 = enabled ; 0 = disabled
Disinfection Type Control on Temp
BV
50
1 = d1 ; 0 = d2
Minimum Disinfection Temperature
AV
51
500...850 (°C/10)
Minimum Disinfection Time
AV
52
1...600
Maximum Disinfection Time
AV
53
3...900
Disinfection Start Day Monday
BV
54
1 = enabled ; 0 = disabled
Disinfection Start Day Tuesday
BV
55
1 = enabled ; 0 = disabled
Disinfection Start Day Wednesday
BV
56
1 = enabled ; 0 = disabled
Disinfection Start Day Thursday
BV
57
1 = enabled ; 0 = disabled
Disinfection Start Day Friday
BV
58
1 = enabled ; 0 = disabled
Disinfection Start Day Saturday
BV
59
1 = enabled ; 0 = disabled
Disinfection Start Day Sunday
BV
60
1 = enabled ; 0 = disabled
Monday Disinfection Starting Minute
AV
61
0...59
Monday Disinfection Starting Hour
AV
62
0...23
Tuesday Disinfection Starting Minute
AV
63
0...59
Tuesday Disinfection Starting Hour
AV
64
0...23
Wednesday Disinfection Starting Minute
AV
65
0...59
Wednesday Disinfection Starting Hour
AV
66
0...23
Thursday Disinfection Starting Minute
AV
67
0...59
Thursday Disinfection Starting Hour
AV
68
0...23
Friday Disinfection Starting Minute
AV
69
0...59
Friday Disinfection Starting Hour
AV
70
0...23
Saturday Disinfection Starting Minute
AV
71
0...59
Saturday Disinfection Starting Hour
AV
72
0...23
Sunday Disinfection Starting Minute
AV
73
0...59
Sunday Disinfection Starting Hour
AV
74
0...23
Time Bands 1 Ric Start
BV
75
1 = enabled ; 0 = disabled
Time Bands 2 Ric Start
BV
76
1 = enabled ; 0 = disabled
Time Bands 3 Ric Start
BV
77
1 = enabled ; 0 = disabled
Time Bands 4 Ric Start
BV
78
1 = enabled ; 0 = disabled
Time Bands 5 Ric Start
BV
79
1 = enabled ; 0 = disabled
Time Bands 6 Ric Start
BV
80
1 = enabled ; 0 = disabled
Minimum Thermal Shock Temperature
AV
81
650...850 (°C/10)
Minimum Thermal Shock Time
AV
82
0...4320
Maximum Thermal Shock Time
AV
83
0...4320
Maximum Temperature Limit
AV
84
650...850 (°C/10)
Thermal Schock
BV
85
1 = Start ; 0 = Stop
Disinfection
BV
86
1 = Start ; 0 = Stop