Function

The automatic filling valve is a device consisting of a pressure reducing valve with 

compensating seat, visual system pressure setting indicator, an inlet filter, anti-scale 

internal parts, a shut-off valve and a check valve.
It is installed on the water inlet piping in sealed heating systems, and its main function 

is to maintain the pressure of the system stable at a set value, automatically filling up 

with water as required.

This valve has been designed as pre-adjustable, which means that it can be 

adjusted at the required pressure value before the system charging phase.

After installation, during the filling or topping-off phase, the water feed will stop when 

the set pressure is reached filling 50% faster than other valves. There are no levers to 

flip or valve to close.
Pre-assembled with the 573 series backflow preventer, the AutoFill™ Combo features 

an atmospheric vent which is designed to protect drinking water systems from return 

flow, caused by back-siphoning or back pressure, of contaminated fluids. The 573 

series has been specifically certified to standards CSA B64.3 and ASSE 1012.

Pre-adjustable filling units

 

 

553 Series

38467.03

www.caleffi.com

© Copyright 2015 Caleffi

553542A

 ½” M NPT inlet x ½" F NPT outlet 

 

553549A

 ½” sweat inlet x ½" F NPT outlet  

553642A

 ½” M NPT inlet x ½" F NPT outlet / gauge   

553649A

 ½” sweat inlet x ½" F NPT outlet / gauge

553

Filling unit
Materials

 - body:

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

brass

 

- cover:

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PA 66 GF 30

 

- seals:

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

NBR

Performance

Suitable fluids: 

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

water, glycol solution

Max. percentage of glycol:

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

50%

Max. inlet pressure:

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

230 psi (16 bar)

Preset outlet pressure:

  . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3–60 psi (0.2–4 bar)

Factory setting:

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15 psi (1.035 bar)

Indicator accuracy:

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

±2 psi (±0.15 bar)

Max. working temperature:

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

150°F (65°C)

Pressure gauge scale:

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

0–60 psi / 0–6 bar)

Connections 

- 553542A

  . . . . . . . .

1/2" male NPT inlet x 1/2" female NPT outlet

 

  

- 553549A 

  . . . . . . . . . .

1/2" sweat inlet x 1/2" female NPT outlet

 

  

- 553642A

  . . . . . . . .

1/2" male NPT inlet x 1/2" female NPT outlet

 

  

- 553649A 

  . . . . . . . . . .

1/2" sweat inlet x 1/2" female NPT outlet

Product Range

Technical 

Specifications

Содержание 553 Series

Страница 1: ...c vent which is designed to protect drinking water systems from return flow caused by back siphoning or back pressure of contaminated fluids The 573 series has been specifically certified to standards CSA B64 3 and ASSE 1012 Pre adjustable filling units 553 Series 38467 03 www caleffi com Copyright 2015 Caleffi 553542A M NPT inlet x F NPT outlet 553549A sweat inlet x F NPT outlet 553642A M NPT inl...

Страница 2: ...ll applicable codes and ordinances SAFETY INSTRUCTION This safety alert symbol will be used in this manual to draw attention to safety related instructions When used the safety alert symbol means ATTENTION BECOME ALERT YOUR SAFETY IS INVOLVED FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD CAUTION If the automatic filling unit is not installed commissioned and maintained properl...

Страница 3: ...lling the internal mechanism will automatically regulate the pressure until it reaches the required value without the need to oversee the filling operation itself This prevents the system being charged to a higher pressure than required 5 Given the pre calibrating function the presence of the downstream pressure gauge is not essential 6 When the system is filled the shut off valve can be closed In...

Страница 4: ...all valve BALLSTOP Thermometer Differential by pass valve Flow switch Zone valve Pump FlowCal Flow meter Temperature probe Safety thermostat Regulator Expansion vessel 3 way valve Pressure switch Control pocket Gas filter Gas regulator Air separator Fuel shut off valve Anti vibration joint Sensor pocket Safety valve Y strainer P A T F T T T T P A F BACKFLOW PREV Series 573 Sizes 1 2 3 4 S N VENT 4...

Страница 5: ...th atmospheric vent size 1 2 3 4 NPT female threaded connection with union size 1 2 sweat connection with union Backflow preventer with intermediate atmospheric vent 38517 05 Installation commissioning and servicing instructions Technical characteristics Connections 1 2 3 4 NPT female with union 1 2 SWT with union Materials Body low lead brass Filter stainless steel Check valve PSU Check valve ste...

Страница 6: ...ecting pipework is water tight ATTENTION S assurer que tous les raccordements sont étanches CAUTION When making the water connections make sure that the backflow preventer connecting pipework is not mechanically over stressed Over time this could cause breakages with consequent water losses which in turn could cause harm to property and or people ATTENTION Lorsque vous effectuez les raccordements ...

Страница 7: ...3 Flow rate graph 10 2 5 10 5 20 50 Dp psi G l min gpm 20 10 5 psi bar 20 1 0 5 10 2 5 15 1 0 5 0 3 Cv 0 7 VENT ...

Страница 8: ... horizontally and following the flow direction indicated by the arrow on the valve body The Caleffi 573 series backflow preventer must be installed with one isolating valve and a strainer upstream and one isolating valve downstream The Caleffi 573 series backflow preventer must be installed in an accessible location to facilitate testing and servicing The Caleffi 573 series backflow preventer must...

Страница 9: ...BACKFLOW PREVE Series 573 Sizes 1 2 3 4 S N VENT Heating system application MAINS SUPPLY Upstream test cock Upstream shut off valve Downstream shut off valve Downstream test cock Inlet test cock Backflow preventer 573 series Y strainer BACKFLOW PREV Series 573 Sizes 1 2 3 4 S N VENT Field testing installation ...

Страница 10: ...eam side of the valve the internal second check valve must close back drip tight on its seat a close shutoff valves upstream and downstream b open the upstream test cock c install a removable bypass hose connecting inlet test cock to downstream test cock and open them for admitting pressure to the downstream side of the internal second check valve Water must not drip from the vent port indicating ...