background image

Function

Pressure reducing valves are devices which, when 
installed on water systems, reduce and stabilize the 
pressure of the water entering from the water supply 
main. This pressure, in general, is too high and 
variable for domestic systems to operate correctly.

The 535H series pressure reducing valves, ideal for 
residential and commercial applications, feature a dial 
indicator with direct readout allowing easy pressure pre-
adjustment. After installation, the valve will control at the 
pre-adjusted pressure setting.

The valve is constructed of DZR low-lead forged brass 
and incorporates a unique noise reducing and high 
flow seat design, is easily serviced with a replaceable 
cartridge and has an integral stainless steel filter 
(35 mesh), suitable for water systems that may 
contain sediment and debris.

The valve is ICC-ES certified to ASSE 1003, CSA B356, 
NSF 61, NSF 372, low lead laws and listed by ICC-ES. 
It meets codes IPC, IRC and UPC for use in accordance

                                                                             with the US and Canadian plumbing codes.

 

Product range

5353H Series 

Pre-adjustable pressure reducing valve with or without pressure gauge and NPT female  

 

threaded union connections, sizes ½", ¾”, 1", 1¼", 1½" and 2". 

5356H Series 

Pre-adjustable pressure reducing valve with or without pressure gauge and union press  

 

connections, sizes ¾” and 1".

5357H Series 

Pre-adjustable pressure reducing valve with or without pressure gauge and union PEX 

 

crimp connections, sizes ¾” and 1".

5359H Series 

Pre-adjustable pressure reducing valve with or without pressure gauge and union sweat  

 

connections, sizes ½", ¾”, 1", 1¼", 1½" and 2".

535H series pressure reducing valve

Installation, commissioning and servicing instructions

NA10397.02

www.caleffi.com

1

© Copyright 2018 Caleffi

535H Series

ASSE 1003

NSF 61

Содержание 535H Series

Страница 1: ...r systems that may contain sediment and debris The valve is ICC ES certified to ASSE 1003 CSA B356 NSF 61 NSF 372 low lead laws and listed by ICC ES It meets codes IPC IRC and UPC for use in accordanc...

Страница 2: ...maintenance of the 535H PRV take the necessary precautions to ensure that such temperatures do not endanger people Leave this manual for the user SAFETY INSTRUCTION This safety alert symbol will be u...

Страница 3: ...en service et l entretien de le r ducteur de pression S rie 535H prendre les precautions n cessaires afin de s assurer que de tells temp ratures ne compromettent pas les gens LAISSEZ CE MANUEL AVEC L...

Страница 4: ...ange 15 90 psi 1 6 bar Factory setting 45 psi 3 bar Max working temperature 180 F 80 C Pressure gauge scale 0 100 psi 0 7 bar Filter mesh size 0 51 mm 35 mesh Suitable fluids water Main connections NP...

Страница 5: ...1 2 3 4 1 1 1 1 4 1 1 2 2 0 45 5 V m s 0 1 4 3 0 3 1 1 4 535074 5 1 1 1 4 1 2 3 4 1 2 5 0 2 10 20 20 50 00 Flow rate min m 3 h 00 5 10 1 5 V f s 0 3 15 10 1 8 20 90 Flow rate s gpm 30 40 10 5 2 1 0 9...

Страница 6: ...noise in the pipes and rapid wear of appliances The correct diameter of the pressure reducing valve is taken from graph 1 on the basis of the design flow rate taking into account an ideal flow velocit...

Страница 7: ...to the required value in the system prior to installation The pressure indicator features incremental step movement so that the pressure can be adjusted continuously and the value displayed at 15 psi...

Страница 8: ...is highly recommended to refer to the working conditions represented in the above diagram Due to the numerous factors and variable conditions experienced such as system pressure water temperature air...

Страница 9: ...llation of valve and permitting quick change out from the jumper to the valve Code Description Face to Face Dimension NA11304 Jumper nipple for 535H series 3 NA11305 Jumper nipple for 535H series 3 9...

Страница 10: ...s pre assembled as a self contained unit with a cover and can be removed for inspection and maintenance When checking cleaning or replacing the cartridge 1 Shut off the inlet and outlet isolation valv...

Страница 11: ...etween the pressure reducing valve and the water heater to absorb the increased pressure caused by water expansion from heating 2 The pressure reducing valve does not maintain downstream setting value...

Страница 12: ...Caleffi North America Inc 3883 W Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 12 Leave this manual at the service of users for their use 04 20 18...

Отзывы: