Caleffi 142 series low lead manual balancing valves are used to measure and adjust 

the fluid flow rate in hydronic or plumbing circuits. Characterized flow plug which 

provides precise system balancing valves and highly accurate flow compared to 

other setters with ball valve control. Turning the knob moves a plug within the fluid 

stream which varies the flow rate. The flow rate is determined according to the 

pressure drop value measured by a differential pressure meter connected to the 

pressure test ports, included. The flow rate is directly determined from the pressure 

differential created across the two test ports as fluid passes the adjustment plug. The 

valve design is variable orifice with pressure ports located upstream and downstream 

of the adjustment plug. Compared to fixed orifice designs where both test ports are 

located upstream of the adjustment plug, for a given size and flow rate, the variable 

orifice design produces a greater differential pressure value. In very low flow rate 

applications and with good fluid quality, this larger differential pressure signal can 

result in more accurate balancing. A memory stop feature allows the valve to be 

closed, and later reopened to the original set position. Insulation shells are available, 

purchase separately.

       

Material:  Body: 

DZR low-lead brass

Bonnet: 

DZR low-lead brass

Control stem: 

DZR low-lead brass

Hydraulic seals: 

peroxide-cured EPDM

Knob: PA6G30

Pressure test ports: 

 DZR low-lead brass body, EPDM seal elements

 

NSF/ANSI 372-2011, Drinking Water System Components-Lead Content

 

Reduction of Lead in Drinking Water Act, California Health and Safety Code

 

116875 S.3874, Reduction in Drinking Water Act, certified by ICC-ES, file

 PMG-1360.        

 

Suitable fluids: 

Water and glycol solutions 

Max. percentage of glycol: 

50%

Maximum working pressure: 

232 psi (16 bar)

Working temperature range: 

14–250°F (-10–120°C)

Accuracy: ±15%

Number of adjustment turns: 

4

Number of regulating positions: 

8

Connections: Main: 1/2”–2” 

NPT female

 Valve body pressure test ports: 

1/4“ NPT female

Material:  

EPP

Thickness:  

½ inch (15 mm)

Density:  

2.8 lb/ft

3

 (45 kg/m

)

Thermal conductivity (ISO 2581):   - at 50°F (10°C): 0.257 BTU·in/hr·ft

2

·°F (0.037 W/(m·K))

Working temperature range: 

23 - 250°F (-5 - 120°C)

Variable Orifice Balancing Valve

 

18204.02

www.caleffi.com

© Copyright 2018 Caleffi

142

241A 

1/2” NPT Female

142

251A 

3/4” NPT Female

142

261A 

1” NPT Female

142

271A 1 

1/4” NPT Female

142

281A 1 

1/2” NPT Female

142

291A 

2” NPT Female

Insulation code:

CBN142241A
CBN142251A
CBN142261A
CBN142271A
CBN142281A

142

Cv

3.4
5.0
7.5

12.9
16.8
22.0

1

Содержание 142 Series

Страница 1: ...te balancing A memory stop feature allows the valve to be closed and later reopened to the original set position Insulation shells are available purchase separately Material Body DZR low lead brass Bonnet DZR low lead brass Control stem DZR low lead brass Hydraulic seals peroxide cured EPDM Knob PA6G30 Pressure test ports DZR low lead brass body EPDM seal elements NSF ANSI 372 2011 Drinking Water ...

Страница 2: ...ystem temperature is below 100 F 38 C Failure to follow these instructions could result in property damage and or personal injury SAFETY INSTRUCTION This safety alert symbol will be used in this manual to draw attention to safety related instructions When used the safety alert symbol means ATTENTION BECOME ALERT YOUR SAFETY IS INVOLVED FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HA...

Страница 3: ...ème sont sous pression ou de la température peuvent être dangereux Être sûr que la pression a été réduite à zéro et la température du système est inférieure à 100 F 38 C Le non respect de ces instructions peut entraîner des dommages matériels et ou des blessures Le non respect de ces instructions peut entraîner des dommages matériels et ou des blessures ATTENTION Si le vanne d équilibrage Série 14...

Страница 4: ...icated by the arrow on the valve body fig B Can be installed in any orientation fig C In order to ensure measuring accuracy the balancing valve must be installed by keeping an upstream straight section of at least five diameters increased to at least ten diameters if the nearest device upstream is a pump fig D PSI A B C D Installation Tip Scan to view 142 Balancing Valve 4 ...

Страница 5: ...ss kg 69 69 69 B C A DN 15 20 25 A 1 2 3 4 1 Code 142140 142150 142160 B 65 75 85 C 64 64 64 0 434 0 523 0 677 Mass kg Code A B C Wt lb 142241A 2 9 16 2 1 0 142251A 2 15 16 2 1 2 142261A 1 3 7 16 2 1 5 142271A 1 3 3 2 3 142281A 1 3 15 16 3 3 8 3 0 142291A 2 4 3 3 8 3 5 5 ...

Страница 6: ...e differential is to be measured For the connection of the pressure test ports of the valve 2 with a differential pressure measuring device 3 use a pair of fittings with a measuring probe fig F F 2 4 3 1 a As the thermal fluid passes measure the Δp of the valve with any suitable differential pressure measuring device fig G b Using the Hydraulic characteristics sheet sheet code 18203 supplied in th...

Страница 7: ...imum stroke position if necessary it is possible to shut off the balancing valve in the circuit by turning the knob fully clockwise manually To restore the valve to its preset position turn the adjustment knob fully counter clockwise fig J H I J Locking sealing the setting position fig K K Installing Insulation Join the size specific insulation shells on the 142 series balancing valve sold under s...

Страница 8: ...Caleffi North America Inc 3883 West Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 5 30 18 8 ...

Отзывы: