UG-3-NS-AOS UNIGUARD SUPERFLOW

Analogue and addressable smoke detector for duct installation.
Optical function.

INSTALLATION

The tube is made of aluminium and can easily be shortened 
to suit the diameter of the duct. Hole diameter is 35 mm. With 
insulated or circular ducts - use the mounting bracket,  hole 
diameter is then 51 mm.

MAINTAINANCE

When the detector becomes contaminated, and when the 
detector no longer can compensate for it, the central panel 
will indicate a service alarm. This can be avoided for a 
considerable time by cleaning the detector once a year with 
a vacuum cleaner.

CHECKING AIR FLOW

The detector is equipped with a flow indicator which oscillates 
in the air stream when the detector is correctly installed. This 
gives simple confirmation that there is no leakage, and that air 
from the ventilation duct is flowing through the dete c tor.

FUNCTION TEST

When installation is complete, the detector should be tested. 
This can be carried out with smoke or suitable testspray for 
example RDP-300 (from Calectro), use the test hole on cover. 
Do not forget to refit the plastic plug after test.

NOTE!

 When installing outdoors or in cold attics etc., where 

there is a risk for condensation, this requires that the detector 
is insulated from the surrounding air by means of for example 
our waterproof housing UG-SH, and marked with an extra 
indicator lamp, LED-03 and a sign marked ”Hidden Detector”.

THE FUNCTION OF ANALOGUE DETECTORS

DIMENSIONS

(mm)

Signal 

Alarm from conventional 
smoke detector 

Time 

Alarm 
limit 

Alarm from analogue/
intelligent smoke detector

Evaluation period 

The analogue smoke detector controls the alarm signals from 
smoke in it´s chamber by measuring time, amplitude of signal 
and signal spread. Before transmitting a fire signal the smoke 
value must conform with preset data.

Signal 

Time 

Trancients, insects etc 

Alarm 
limit 

Alarm level 

Environment influence 

Signal 

Long 
term 

Service alarm 

Short duration, large signals from disturbances such as 
transients or small insects will not influence the analogue 
smoke detector. 

Reliable operation is ensured as the alarm limit of the analogue 
smoke detector is self compensating, i.e. it will always remain 
at the correct preset value due to the built-in intelligence 
compensating for environmental changes. 

Historical data storage: 

Each detector module maintains a historical database 
including the detector module identification number, number of 
alarms and faults and the date when the detector was placed in 
operation. 

150

146

180

27

85

154

35