14 — ElectriCalc Pro
Fuse/Breaker Keys
The
ElectriCalc Pro
has special keys
that automatically calculate the Amp
ratings of the following over-current
protection devices: Dual Element Fuses
(Time Delay), Single Element Fuses
(Non-Time Delay), Instantaneous Trip
Breakers (Type 1), Inverse Time
Breakers (Type 2), and Overload
Protection Devices.
These fuse and circuit breaker sizes
are derived using the “Percent of Full-
Load Current” multipliers listed in NEC
Table 430-52.
You can also calculate the full Voltage
starter size for non-plugging and non-
jogging duty motors based on phase,
Voltage, motor HP and NEMA table
specifications.
If a parameter is missing or invalid, the
calculator will display “
nonE
.”
S L
—
Motor Type (M-Type)
Based on NEC Table 430-52, this key
selects the motor type used to define
the percent factors for breakers/fuses.
Once set, the motor type remains fixed
until you change it or perform a Clear All
(
S x
).
♦
First Press
Displays the current motor type. Note
there is no motor type in single-phase
mode.