background image

CALogix 

installation 

sheet 

 

      Page 

of 

6

 

 

OUTPUT OPTIONS 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

EXAMPLE CIRCUIT 

The circuit below shows an example applicaion which includes a base-unit that has one PID module and 
one logic module fitted. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
It is strongly recommended that the power supply zero volts and all logic module zero volts are 
common to prevent ground loops. 

 

 

INPUT SENSOR SELECTION 

 
 
 
 
 
 
 
 
 

* Note

 : Type-B accuracy not specified below 100°C/212°F 

 

Configuring and Networking CALogix

 

 
CALogix is configured using Windows-based CALogix-sw software. Before using CALogix–sw, 
connect CALogix to a PC as shown below:  
 

CALOGIX NETWORK  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
CALogix uses RS485 full duplex serial communications link which is the standard most commonly 
used for industrial applications due to high noise immunity and multi-drop capability. It enables a PC to 
communicate with up to 31 CALogix base-units over distances up to 1200 metres, and requires the 
addition of an RS485 interface card, or a separate RS232 / 485 converter connected to the RS232 port 
of the PC. RS485 converters that derive power from the RS232 port must have all 9 pins (RS232) 
connected for full operation of the converter. 
 
RS485 cards and converters can differ greatly in their requirements and therefore the installation 
instructions supplied with the interface  should be read carefully. 
 
2m CALogix-PC cable (part number - CAB RJ45 2M 01) and a RS232/485 converter (part number - 
3C 25 000 K 3X) that fits directly on to the RS232 serial port on a PC are available from your nearest 
CAL Controls distributor.  
 
 
 

Thermocouple type 

Description 

Sensor Range (°C)  

Sensor Range (°F)  

Pt-30% Rh/Pt-6%Rh 

0 to1800°C* 

32 to 3272°F* 

Chromel/Con 

0 to 600°C 

32 to 1112°F 

Iron/Constantan 

0 to 800°C 

32 to 1472°F 

Chromel/Alumel 

-50 to 1200°C 

-58 to 2192°F 

Fe/Konst 

0 to 800°C 

32 to 1472°F 

Nicrosil/NiSil 

-50 to 1200°C 

-58 to 2192°F 

Pt-13%Rh/Pt 

0 to 1600°C 

32 to 2192°F 

Pt10%Rh/Pt 

0 to 1600°C 

32 to 2192°F 

Copper/Con 

-200 to 250°C 

-273 to 482°F 

Resistance Thermometer 

rtd 2/3 wire 

Pt100/RTD-2/3 

-200 to 800°C 

-273 to 1472°F 

7P111----- 
7L111----- 

7P211----- 
7L211----- 

7P221----- 
7L221----- 

7PB11----- 

= 4-20mA 

7PC11----- 

= 0-5V 

7PD11----- 

= 0-10V

 

7PB21 

= 4-20mA 

7PC21 

= 0-5V 

7PD21 

= 0-10V

 

 

FS1 Fuse = 1A time lag type to IEC127. CSA/UL rating 250V  
FS2 Fuse = 2A time lag type to IEC127. CSA/UL rating 250V 
FS3 Fuse = High rupture capacity (HRC). Suitable for maximum rated load current 
 
S1 switch = IEC/CSA/UL approved disconnection device must be used 
 

<15m 

<1200m 

RS232/485 converter

 

RS485 from PC  

To other 
CALogix 
controllers  