background image

1. General function

VI-D4 meter calculates humidity of analyzed material by measuring its electrical impedance. The 
relation between humidity of certain material and its impedance is directly proportional. Impedance
is measured through generating low frequency electric field between electrodes. The meter 
measures low intensity alternating current flowing through electric field and on that basis 
calculates moisture of tested material.

2. Constraints

Concrete Moisture Meter VI-D4 does not detect concrete humidity through electricity conducting 
materials like metal coverings/ linings, PE-rubber or any wet surfaces. Moisture Meter VI-D4 
should not be used to measure concrete humidity on surfaces which are topped with a thick layer of
floor covering material like wood. Meter measurement outcomes show the actual humidity at a 
time of measurement. 

To turn on the meter press ON/HOLD button.

To set the scale press SET button. There are 7 available scales:

1 - Concrete (0-6%H2O)
2 - Cement Screed (0-6%H2O)
3 - Cement Screed (0-4% CM)
4 - Anhydrite Screed (0-3.5% H2O)
5 - Anhydrite Screed (0-1.9% CM)
6 - Caisson 0.3-15.3 Scale (0.3-15.3m)
7 - Relative Scale (0-100%)

CAISSON Elektronik GmbH 

Boschstrasse 16, D-47533 Kleve, Deutschland 

tel: +49(0)2821-894390   

[email protected]

   

www.caisson-gmbh.de

Отзывы: