CONNECTION

 

 

BEFORE CARRYING OUT ANY OPERATION, DISCONNECT THE UNIT FROM 

THE NETWORK AND ENSURE THAT THE POWER SUPPLY CANNOT BE 

SWITCHED ON ACCIDENTALLY. 

This equipment must be installed by suitably qualified personnel. The installation must comply 

with standard NFC15-100 and industry best practice. Each product or component used in this 

installation must also comply with the applicable standards. 

 

THE INSTALLATION MUST BE PROTECTED UPSTREAM BY A 

 

SUITABLE MAGNETOTHERMAL CIRCUIT BREAKER.

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Connecting to an ECM motor with 0-10

 

V input

 

- Connect the 0-10 V output 

S1

 and the 

GND

 reference of the controller to a 0-10 V analogue input on 

the ECM motor. 

 

Connecting to an ECM motor with PWM input

 

- Connect the PWM output 

S2

 and the 

GND

 reference of the controller to the "Rx" input on the ECM 

motor. 

- Place a bridge between the 0-10 V 

S1

 output of the controller and the 

V+

 input on the controller. 

- In product settings, activate the option "FORCE S1 to 10V". This mode forces the 

S1

 output to 10.5 V 

which will serve as the power supply for the PWM output 

S2

 to limit the amplitude of the PWM signal. 

 

 

!

!

!

!

 

Mains power input 

 Pressure alarm dry contact output. 
 Fault contact output. 

 

S1:

 

0-10 V

 

output

 

for

 

the

 

ECM

 

motor

 

control.

  

      S2: PWM output for the ECM motor control 

 

24 V: +24 VDC/100 mA power supply. 

      GND: Common reference for 0-10 V and PWM 
      V+: PWM output power supply source. 
      A - B - GND: Modbus RTU 

 Positive pressure measurement input.

 

 Negative pressure measurement input.

 

Содержание REM-REGU

Страница 1: ...to 1000 Hz Max output current 20 mA Protection Short circuit Differential pressure measurement Measuring range 980 Pa Accuracy 1 of range Climatic environment Storage temperature 10 C to 60 C Operatin...

Страница 2: ...the differential pressure between the environment and the ventilation box intake and adjusts the box s motor speed to maintain a constant pressure set by the user All the product parameters are define...

Страница 3: ...the controller to a 0 10 V analogue input on the ECM motor Connecting to an ECM motor with PWM input Connect the PWM output S2 and the GND reference of the controller to the Rx input on the ECM motor...

Страница 4: ...u of the REM REGU displays the current operating parameters which have been defined in the settings menu Reminder depending on the operating mode chosen certain menu inputs may be deactivated The only...

Страница 5: ...INPUT SEUIL THRESHOLD RAZ DU TEMPS TIME RESET MODE FEU FIRE MODE REGLAGE INSTALL INSTALL SETTING REGLAGE MODBUS MODBUS SETTING CAL CAP PRESSION PRESSURE SENS CAL CALIBRER PA MAXI MAX AP CALIBRATION AD...

Страница 6: ...ximum speed for 3 minutes to determine and adjust the maximum pressure of the installation 5B This function is used to determine the maximum flow rate which can be reached by the installation When thi...

Страница 7: ...structions in this manual any improper use or repair operations attempted by unqualified personnel In the event of a problem please contact your installer or failing that your retailer RS 485 SERIES C...

Страница 8: ...1 62 5 Hz 2 125 Hz 3 250 Hz 4 500 Hz 5 1000 Hz 9 30010 40010 MIN OUTPUT Minimum output PWM Voltage Default 000 of output 0 VDC or PWM of 0 10 30011 40011 MAX OUTPUT Maximum output PWM Voltage Default...

Отзывы: