background image

Lib
er

at

ors

Theory of Operation

VI

Filling

The Liberator is filled by connecting a pre-purged transfer line 

with a fill adapter from a larger liquid oxygen source to the 

Liberator side fill or top fill QDV. The Liberator vent valve is 

then opened. The pressure differential between the Liberator and 

source tank forces liquid oxygen through the transfer line and 

into the Liberator inner vessel.

There will be some oxygen vaporized during filling. This gas is 

discharged through the vent valve. When the Liberator is full, liq-

uid oxygen is expelled. Disconnecting the fill adapter from the 

Liberator QDV and closing the Liberator vent valve terminates 

the fill process.

Saturation Pressure

The saturation point of a liquid is a steady-state condition where 

the liquid has absorbed the maximum amount of heat possible. 

A liquid can be at its saturation point at a number of different 

pressures and temperatures, but each specific saturation pressure 

has a corresponding saturation temperature and vice-versa (see 

Figure 3).  This means that the final temperature of your liquid 

oxygen is dependent upon the pressure at which it is transferred 

from the storage system to the Liberator.  For the purposes of this 

manual, we will speak in terms of saturation pressure, since it is 

easier to control than temperature. Treat saturation temperature 

as a dependent variable of saturation pressure.

There are two conditions which can seriously affect the overall 

efficiency and operation of the system:

1. Saturation pressure of the liquid oxygen in the fill source is

substantially higher than the Liberator operating pressure

(oversaturated).

2. Saturation pressure of the liquid oxygen in the fill source is

substantially lower than the Liberator operating pressure (un-

dersaturated).

For example, when a Liberator is filled from a liquid source satu-

rated at 6,9 bar (100 psig), larger transfer losses will occur. This is 

because the Liberator is designed to operate at 1,4 bar (20 psig), 

and the liquid it is filled with is saturated at a much higher pres-

sure and at its correspondingly higher temperature. It is neces-

sary for this liquid to reach equilibrium at a lower pressure and 

temperature before the relief valve will close and the Liberator 

will operate properly.

In order to become saturated at 1,4 bar (20 psig), the liquid oxy-

gen must release enough heat for its temperature to be lowered to 

the temperature corresponding to a pressure of 1,4 bar (20 psig), 

as shown in the graph. The temperature is lowered through boil-

ing. All of the gas generated by this boiling is vented through the 

relief valve and/or primary relief valve and is lost.

If the saturation pressure of the liquid oxygen in the filling ves-

sel is lower than the normal operating pressure of the Liberator, 

oxygen vaporization within the dewar works to raise the system 

pressure to the required 1,4 bar (20 psig). This may require as 

long as a day. The time required for saturation to 1,4 bar (20 psig) 

depends on the initial liquid saturation pressure.

Vent Valve

Liquid

Fill Connection

(QDV)

Gas

Gas

0.0, -183.0

6.9, -157.4

1.4, -173.8

-190

-185

-180

-175

-170

-165

-160

-155

0

1

2

3

4

5

6

7

8

SATURATION PRESSURE (BAR)

LOX TEMPERATURE (°C)

FIGURE 2:

 Filling

FIGURE 3: 

Temperature vs. Saturation Pressure

Liberators Technical Service Manual • PN 13350704 Rev 

K

 

11

1

1

Содержание LIB20

Страница 1: ...Liberators G4 Technical Service Manual...

Страница 2: ...ic Rim Phone 770 721 7759 Fax 770 721 7758 Europe Phone 44 0 1189 367060 Fax 44 118 9799245 For Customer or Technical Service needs product assistance ordering part numbers specifications unexpected e...

Страница 3: ...ption of a condition that can result in equipment or component damage NOTE A statement containing information important enough to emphasize or repeat ITEM Item numbers used throughout this manual are...

Страница 4: ...ry of Operation 11 VII Unpacking and Setup 14 VIII Operation 15 IX Maintenance 17 X Troubleshooting 19 XI Troubleshooting Charts 20 23 XII Repair Procedures 24 XIII Service Tools Equipment Supplies 38...

Страница 5: ...tempera ture and regulates the flow of oxygen gas to the patient Any water that condenses on the cold coils is routed into the con densate bottle An economizer regulator is utilized to con serve LOX...

Страница 6: ...bar 23 2 psi 1 6 bar 23 2 psi Primary Relief Valve Reseat Pressure 1 4 bar 20 5 psi 1 4 bar 20 5 psi 1 4 bar 20 5 psi 1 4 bar 20 5 psi 1 4 bar 20 5 psi Secondary Relief Valve Opening Pressure 2 1 bar...

Страница 7: ...as Association as an oxygen concentration above 23 In an oxygen enriched atmosphere flammable items may burn vigorously and may ex plode Certain items considered non combustible in air may burn rapidl...

Страница 8: ...s are very low and are not likely to cause any interference in nearby electronic equipment RF emissions CISPR 11 Class B Harmonic emissions The Liberator is suitable for use in all establishments incl...

Страница 9: ...input output lines No data input output lines 1 kV line s Surge to line s Not Applicable Not Applicable IEC 61000 4 5 2 kV line s DC powered device to earth Voltage dips 5 UT 95 dip short interruptio...

Страница 10: ...nce level in each frequency rangeb Interference may occur in the vicinity of equipment marked with the following symbol NOTE 1 At 80 MHz and 800 MHz the higher frequency range applies NOTE 2 These gui...

Страница 11: ...2 3 P 0 01 0 12 m 0 12 m 0 23 m 0 1 0 38 m 0 38 m 0 73 m 1 1 2 m 1 2 m 2 3 m 10 3 8 m 3 8 m 7 3 m 100 12 m 12 m 23 m For transmitters rated at a maximum output power not listed above the recommended...

Страница 12: ...e is substantially higher than the Liberator operating pressure oversaturated 2 Saturation pressure of the liquid oxygen in the fill source is substantially lower than the Liberator operating pressure...

Страница 13: ...the bypass tee to the breathing coil the flow control valve and then the patient As the pressure in the container increases over 1 4 bar 20 psig the economizer valve opens and the cycle repeats mainta...

Страница 14: ...e meter is powered by an internal battery offering battery life of 5 years or more at 30 cycles per day The meter has a low battery LOW BATT indicator which signals the need for bat tery replacement T...

Страница 15: ...vel meter by depressing the operate button LEDs will light displaying the level of liquid oxygen If the unit is empty only the leftmost LED should light If it does not or if other erroneous indication...

Страница 16: ...transfer line adapter to transfer line d Fully open liquid valve on fill source e Purge transfer line for a minimum of 5 seconds ensuring gas is safely piped away from operator i Connect transfer hose...

Страница 17: ...tongs or tweezers 2 Wipe off the exterior of the unit with the cleaning solution us ing a lint free cloth The cloth should be damp but not drip ping Be as thorough as possible 3 Discard the cleaning c...

Страница 18: ...nual NOTE See the Troubleshooting and Repair section of the cor responding technical manual on the detailed procedures for the tests mentioned below 1 Visual Inspection a Remove any LOX prior to maint...

Страница 19: ...cator functionality d Presence of all required labels e Cryogenic reservoir damage dents dings f If LOX is still present in the unit inspect for heavy frost or condensation on the exterior of the unit...

Страница 20: ...mbly RR 31 RP18 Vent Valve RR 31 RP19 Twist Lock QDV Lip Seal RR 31 RP20 Twist Lock QDV RR 32 RP21 Push on QDV RR 32 RP22 Push on Portable Pop Off Assembly 32 RP23 Empty Unit 33 RP24 Warm Unit 33 RP25...

Страница 21: ...e QDVs are wiped clean and dry before filling b Dirty or damaged QDV poppet Replace the QDV cartridge RP20 or the entire QDV assembly RP21 5 Excessive venting from relief valves hissing sound a Satura...

Страница 22: ...ionsfor Excessive venting from relief valves hissing sound f Partial or complete loss of vacuum ConducttheNERtest RP32 andreturntheunittoCAIRE Inc ifnecessary 10 Unit will not maintain acceptable syst...

Страница 23: ...22 Liberators XI Troubleshooting Charts 8 Liberators Technical Service Manual PN 13350704 Rev K...

Страница 24: ...e Troubleshooting Chart Start at the upper left corner The top line shows the steps of routine maintenance Unless otherwise noted by the arrows the flow through the chart is down or to the right Liber...

Страница 25: ...attery WARNING Make sure the unit is empty and vent valve is open before replacing any component except shroud assembly compo nents or Lip Seals NOTE When assembling new compression fittings tighten 1...

Страница 26: ...n more accurate but re quires the dewar be vent full with LOX To start either procedure calibration mode must first be entered There is no need to per form both procedures for any given calibration Pr...

Страница 27: ...el 20 30 37 45 60 LED Min Max Min Max Min Max Min Max Min Max 1 17 6 20 6 22 0 24 7 22 7 27 9 24 9 31 3 34 2 38 1 2 20 6 23 5 24 7 28 9 27 9 33 1 31 3 37 6 38 1 46 3 3 23 5 26 5 28 9 33 2 33 1 38 3 37...

Страница 28: ...7 Range The new full cap value is less than empty cap value When calibrating full Empty unit and recalibrate TABLE 6 Calibration Errors TABLE 7 Operation Errors LEDs Name Reason Notes Solution 2 4 6 H...

Страница 29: ...e three bolts Item 31 that run through the FCV bracket Item 39 and through the manifold plate into the top of the dewar g Remove two remaining manifold mounting bolts Item 31 not visible in Figure 12...

Страница 30: ...l holding signal wire against the ca pacitance probe c Unsolder feed thru wire Item A from probe Item B d Loosen feed thru nut Item C and remove harness e To replace manifold harness reverse above pro...

Страница 31: ...Item 28 should open audible venting and or bubbling of leak test solution i Decrease pressure to 1 3 bar 19 psig Test relief valve with leak test solution A minimal amount of leakage bubbling is acce...

Страница 32: ...o humidifier adapter Item 26 on FCV outlet Open FCV Item 24 to 6 LPM setting d Assemble oxygen regulator pneumatic hose Item C with DISS fittings and male pneumatic test adapter Item D Connect as semb...

Страница 33: ...em 88 on tool f Install retaining ring Item 87 in QDV body Item15 by turning tool counter clockwise while pushing in on tool Torque retaining ring Item 87 to 225 280 N cm 20 25 in lbs RP17 Warming and...

Страница 34: ...e static seal Item 67 if needed FIGURE 21 Top Fill Push on QDV Assembly WARNING Liberator must be empty and vented before starting procedure WARNING Liberator must be empty and vented before starting...

Страница 35: ...g 4 Set Liberator FCV Item 24 to 6 LPM setting 5 Continue until Liberator is empty RP24 Warm Unit Figure 23 a Liberator may be allowed to sit FCV off vent closed a mini mum of 48 hours after emptying...

Страница 36: ...alues within tolerances listed in Table 9 or unit fails flow rate test NOTE Flow rates will only be accurate if the reservoir is filled properly Reference the filling section of this manual for the co...

Страница 37: ...ected to normal temperature and pressure 70 F 14 7 psig or 21 C and 1 01 Bar The above acceptable flow rates are intended for field testing only of flow control valves to account for variation in elev...

Страница 38: ...ator Item 35 c Follow RP29 to ensure proper settings on the replacement regulator d Reverse remainder of procedure to install new properly ad justed regulator RP29 Economizer Regulator Test a Follow s...

Страница 39: ...en in a full Liberator 45 reservoir 1 Empty weight of LIB 45 Reservoir 24 95 kg 55 00 lbs 2 Filled unit with properly saturated liquid oxygen 3 Full weight of LIB 45 Reservoir 74 99 kg 165 32 lbs 4 74...

Страница 40: ...uper Flex Liquid Oxygen Transfer Line 6 97406630 Dual Fill Head Tee 13350704 Service Manual 10661515 Conversion Kit TF to SF 10660361 Conversion Kit SF to Dual 10660344 Conversion Kit TF to Dual 10661...

Страница 41: ...40 Liberators Parts Price List XIV Contact Customer Service or visit www cairemedical com to obtain your parts list Liberators Technical Service Manual PN 13350704 Rev K...

Страница 42: ...Fax 44 0 1344 429224 4 Mail or fax the completed purchase order for confirmation to CAIRE Inc 2200 Airport Industrial Dr Ste 500 Ball Ground GA 30115 USA CAIRE Medical Ltd Unit 6 Ashville Way Wokingha...

Страница 43: ...ntenance performed Restocking Policy If it becomes necessary to cancel an order with CAIRE Inc af ter the shipment has been received use the following Restock Policy procedure 1 Notify the Customer Se...

Страница 44: ...Wokingham Berkshire RG41 2PL United Kingdom Ph 44 0 1189 367060 Fax 44 0 0118 979 9245 Copyright CAIRE Inc 2019 CAIRE Inc reserves the right to discontinue its products or change the prices materials...

Отзывы: