![CADEXAIR STADIUM Series Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/cadexair/stadium-series/stadium-series_operation-and-maintenance-manual_3054848011.webp)
CLEARANCE TO MATERIALS
Be sure to meet the clearance standards for semi-combustible and combustible materials. A
commercial range hood must be installed 3 inches (75mm) from materials classified as semi-
combustible and 18 inches (460mm) from combustible materials. This clearance applies to both
walls and ceilings.
WEIGHT VALIDATION
Confirming the weight of each hood is an important step to ensure that the anchors and fastening
methods used are appropriate for the weight of the hood. To verify this, refer to the hood weight
table provided by the manufacturer or calculate the weight of the hood based on its dimensions
and the materials used.
Once the weight of the hood has been determined, it is important to verify that the anchors and
fastening methods used are appropriate to support the weight of the hood. Anchors must be of the
proper size and load capacity and adapted to the supporting structure such as walls or ceilings.
Fastening methods must comply with building and safety regulations.
If there is any doubt as to the ability of the anchors and fastening methods to support the weight
of the hood, it is recommended to consult a qualified professional to perform an evaluation and
recommend appropriate solutions. This may include modifications to the support structure,
additional anchors or fastening methods to ensure the safety and stability of the hood.
IMPORTANT
The Stadium Series hood is heavier than standard hoods.
LIFTING, SUSPENSION AND LEVELING
Attach the anchor points to the building structure according to the position of the hood’s
suspension brackets and install a 7/16" (11mm) threaded rod in the anchor points according to the
position of the brackets. See below for typical hood anchor position without a spacer for clearance
from combustible materials.
Adjust the length of the threaded rods to meet the hood installation height standards.
9