background image

Doc150313-01 

Installation and maintenance manual 

 

www.cadexair.com 

1010, Boulevard Lionel Boulet 

1-800-461-0668 

 

Varennes, Québec, Canada J3X 1P7

 

 

 

It is possible to connect the kitchen exhaust hood collar 
according to the following figure from NFPA96. 

 

Exhaust hood collar joint and air supply collar joint 
on PE series 

Type 2, C3 series exhaust hood are note regulated by 
NFPA 96 standards.  A welded duct is not mandatory. 
The junction can be soldered by point to intervals from 
1 to 2 inch (25 to 50 mm) or with metal screws every 3 
to 6 inch (75 to 150 mm). 

Self-cleaning hood CA1M series plumbing fitting 

Self-cleaning  hood  series  are  equipped  with  a  NPT 
type  3/8  brass  fitting  for  each  hood  section.    CA-W 
exhaust hood series are equipped with 2 connections. 
Single  and  double  hoods  will  be  provided  with  a 
connection for a 2 inch male NPT drain. 

Electrical wiring 

Hoods are frequently equipped with lighting. 
Depending on the product, the lighting is pre-wired by 
hood section to a junction box. Certain model 
requires that each fixture to be connected. Refer to 
the schematic of this control provided on the 
manufacturing plans to ensure that the wiring is done 
properly. 

Access on top of exhaust hoods 

Provide  an  access  on  top  of  the  hood  to  perform 
maintenance,  electrical  wiring  and  access  control 
components,  plumbing  fittings,  and  fire  suppression 
system  components  even  after  the  installation  and 
construction is completed. 

Exhaust hood skirting 

It  is  possible  to  install  a  hood  skirting  provided  by 
Cadexair  or  not  above  the  hood.    The  installation 
method  may  vary  according  to  the  exhaust  hood 
model.  The hood skirting can be installed with a “Z” 
component  installed  on  the  back  panel  of  the  hood 
skirting.  Depending on the height of the hood skirting, 
tracks  or  any  other  methods  might  be  necessary  to 
support  the  hood  skirting.    An  assembly  with  screws 
allow keeping corners together. 

 

 
 

IMPORTANT 

Never pierce the hood for installation of 
hood  skirting,  suspended  ceilings  or 
other.    This  will  void  the  exhaust  hood 
homologation 

Silicone usage 

Once the exhaust hood is in place, it is recommended 
to  apply  a  silicone  joint  between  different  hood 
sections or between the exhaust hood and walls. 
Recommended silicone: Kason RubbaSeal, aluminum 
color 

Seismic performance 

It  is  the  buyer’s  responsibility  to  perform  a  seismic 
installation  according  to  plans  provided  by  a  seismic 
specialized engineer. 

Fire suppression system 

According  to  NFPA  96,  a  fire  suppression  system  is 
mandatory  with  this  type  of  hood  above  cooking 
equipment  for  the  exhaust  ducts  and  cooking 
equipment.  This system is activated by fusible links or 
thermal  detectors integrated to the exhaust hood.  In 
case of fire, the air exhaust is maintained and the air 
supply is stopped.  Filters housing, exhaust collar and 
cooking surface are sprayed with a chemical product.  
Energy sources like gas and electricity are interrupted 
for the cooking equipment and hood lightings and an 
alarm system sounds. 

Содержание CA Series

Страница 1: ...User Manual CA Series Version V1 0...

Страница 2: ...ds IMPORTANT ATTENTION DANGER A commercial kitchen hood must always be installed by professionals according to the local construction codes in force A commercial kitchen hood ventilation system can ha...

Страница 3: ...f the kitchen exhaust hood collar 5 Exhaust hood collar joint and air supply collar joint on PE series 6 Self cleaning hood CA1M series plumbing fitting 6 Electrical wiring 6 Access on top of exhaust...

Страница 4: ...exhaust system 9 Inspection and maintenance of the exhaust hood fire suppression system 9 Tips and tricks 10 Problems and solutions 11 ANNEX 1 Exhaust hood weight evaluation table 14 ANNEX 2 Assembly...

Страница 5: ...e exhaust kitchen hood to the sun and to a temperature above 35 Celsius These conditions can affect the adherence of the protective film glue protecting the exhaust kitchen hood and may damage the sta...

Страница 6: ...haust hood height installation Lift the kitchen exhaust hood and fix the hood with the threaded rods All of the kitchen exhaust hood mounting brackets must be held by a threaded rod Adjust the height...

Страница 7: ...he installation and construction is completed Exhaust hood skirting It is possible to install a hood skirting provided by Cadexair or not above the hood The installation method may vary according to t...

Страница 8: ...s adding the 5 speed values then divided by 5 Then multiply the average speed value by an effective area factor according to the filters size refer to table below Size Effective Area H x W in SQ FT SQ...

Страница 9: ...be used the same way to facilitate the balancing of many exhaust hoods on the same exhaust fan The air flow will adjust according to the opening of the Geo Vary grease extractor If modifications are t...

Страница 10: ...ractor Weekly maintenance Remove baffle filters and clean or soak with a hot water and degreaser solution Empty all grease cups located under modular extraction baffles Monthly maintenance Remove and...

Страница 11: ...ial kitchen operates usually out of standard working hours evenings and week end It is recommended to have in inventory replacements exhaust and air supply fan motor belts Furthermore for critical com...

Страница 12: ...Verify if the magnetic started is powered on the primary side if not verify the power system of the disconnect and the fuse on the distribution panel contact an electrician if needed If the magnetic s...

Страница 13: ...ED Clean as fast as possible the suppression liquid Call the company in charge of you fire suppression system maintenance to put the system back in operation If the system is equipped with a rearming...

Страница 14: ...50313 01 Installation and maintenance manual www cadexair com 13 1010 Boulevard Lionel Boulet 1 800 461 0668 Varennes Qu bec Canada J3X 1P7 water valves and change them if necessary then contact Cadex...

Страница 15: ...1 7 6 1 85 6 5 2 7 2 15 7 5 2 3 8 2 45 8 5 2 6 9 2 75 9 5 2 9 10 3 05 Width CA S 27 12 30 14 33 15 36 16 39 18 42 19 45 20 48 22 Weight CA S PE 50 23 55 25 60 27 65 29 70 32 75 34 80 36 85 39 CA S M...

Страница 16: ...dexair com 15 1010 Boulevard Lionel Boulet 1 800 461 0668 Varennes Qu bec Canada J3X 1P7 ANNEX 2 Assembly diagram of an exhaust hood with mecanical joints CA W series NOTE Verify carefully the install...

Страница 17: ...t may cause performance issues Cleaning of the Geo Vary grease extractor When necessary remove the Geo Vary from the exhaust hood filter cage carefully noting the guillotine adjustment and position fo...

Страница 18: ...ule According to the cooking type Frequency Systems serving solid fuel cooking operations Monthly Systems serving high volume cooking operations such as 24 hour cooking charbroiling or wok cooking Qua...

Отзывы: