
11
STUFE A PELLET
4.2
COMBUSTIBLE AIR INLET FOR SEALED-CHAMBER INSTALLATION
Fig. 11 - Air inlet for sealed-chamber installation
LEGEND
Fig. 11
1
≥ 1,5 mt
2
≥ 0,3 mt
3-3
Sectional view
4
Shield grid
5
Curve inlet to turn downwards
Check if the purchased stove has a sealed-chamber. If the stove is endowed with a sealed-chamber and you want also the whole
installation with sealed chamber, please read the following instructions:
• It is necessary to extract the air for combustion directly from outside.
• Use a tube with minimum Ø60 mm and maximum 2 meters lenght; to connect see the back of the stove.
• French standards require installation in double-walled flues (concentric system). The combustion air is drawn from the cavity.
• During installation step is necessary to verify the minimum distances required for the combustible air inlet as (for example)
an open door or window causes a vortex which could remove the combustible air necessary to the stove (see the underlying
scheme).
• On the external wall it is necessary to install a curve at 90° to protect the combustible air inflow from wind effects: turn the
curve inlet downwards, see
Fig. 11
.
• Endow the curve with an external shield grid against birds in such a way that it cannot be obstructed by any object.
Check with your local authorities if exists any restrictive regulation regarding the combustible air inlet: if pre-
sent, they must be applied
In some countries and/or regions the installation with sealed-chamber is obligatory: in case of doubt, please
follow the most restrictive regulations.
Содержание LORD 7
Страница 39: ...NOTE ...