2. Other possible state codes

h

4

Pre-purge

System is purging before ignition trial; includes Pilot Valve circuit diagnostics.  On vent 

damper models, this is so quick it will typically be over before the display can flash 

this code, and therefore will rarely be visible.

i

9

Post-purge

System is purging after heat cycle. On vent damper models, this is so quick it will 

typically be over before the display can flash this code, and therefore will rarely be 

visible.

j

10

Retry Recycle 

Delay

5 minute delay after pilot signal is lost. 
Either:

1. 

Control failed to detect flame after spark period. Check pilot for 

contamination, check ignition wire; check electrical ground; Check pilot flame.

2. 

Control lost pilot flame signal AFTER main burners were lit.  Check for 

adequate draft and combustion air. Check gas line for adequate pressure.

k

13

Soft lock out

Soft lock out duration is one hour, may override with manual reset.  Appropriate error 

code will flash alternately.

l

14

Hard lock out

Requires manual reset.  Unacceptable high water temperature (err 65) and onboard 

electronics failure ( er 18) are the only two (2) hard lockouts on this model.

m

15

Wait for limit to 

close

One of the safety limits - rollout, vent spill, or low water cutoff (if one is field 

installed on the 24V safety circuit) has been activated.  Control will resume normal 

operation once limit is reset.  Underlying cause why the limit switch opened 

MUST be 

investigated.

n

16

Flame out of 

sequence

Flame signal sensed before trial ignition.  Appropriate alarm is sent.
OR
Flame signal sensed out of sequence during post purge
OR
Flame signal present when not expected.  Appropriate alarm is sent.

o

17

Diagnostics

Onboard self check performed at various points during the operation sequence.

p

19

Wait for damper  

switch to close

Damper is closed and control waits for damper switch to close.  Checked at beginning 

of heat cycle before opening damper. If damper does not open in 60 seconds, control 

goes to State 20. Control may also be in state 15 if one of the safety limits is open.

q

20

Wait for damper to 

open (Failed close) 

Damper has not opened (end switch not closed) at beginning of heat cycle.  Alarm 

message is sent, control is NOT in lockout.  Control will resume normal operation once 

the damper opens.

r

21

Wait for damper to 

close (Failed open)

Damper has not closed despite actuator de-energized.  Alarm message sent, control is 

NOT in lockout.

Table 6 conti. - Vent Damper Models Operation State Codes

APPENDIX A - CONTROL MODULE

Содержание BWBBAN000045

Страница 1: ...r Forced Hot Water INSTALLATION OPERATION MAINTENANCE MANUAL Models BWBBAN000045 BWBBAN000070 BWBBAN000096 BWBBAN000120 BWBBAN000145 BWBBAN000170 BWBBAN000195 BWBBAN000245 BWBBAN000295 P N IM BWBB 01 240011111 REV C 3 31 2017 ...

Страница 2: ...selected on basis of its heating capacity 3 Tank sized for non ferrous baseboard or radiant panel systems Increase size for cast iron baseboard and radiation STANDARD EQUIPMENT Boiler Jacket Cast Iron Boiler Battery High Limit Control Intermittent Electric Ignition Pilot System Vent Damper Relay Circulator With Return Piping To Boiler Main Gas Burners Gas Control Includes Automatic Gas Valve Gas P...

Страница 3: ...2015 16 415 16 1 BWBBAN000096 15 7 5 28 2015 16 415 16 1 BWBBAN000120 19 9 6 29 217 16 57 16 1 BWBBAN000145 19 9 6 29 217 16 57 16 1 BWBBAN000170 22 113 16 7 30 2115 16 515 16 1 BWBBAN000195 22 113 16 7 30 2115 16 515 16 1 BWBBAN000245 26 136 16 8 31 227 16 615 16 1 BWBBAN000295 30 155 16 9 32 2215 16 815 16 1 Propane Gas Inlet All Units 1 2 2 DIMENSIONS Dimensions Minimum Height for Low Water Cut...

Страница 4: ...ing Diagram 18 12 Lighting Instructions 20 13 Normal Sequence of Operation 21 14 General Instructions 21 15 Checking Gas Input Rate To Boiler 23 APPENDIX A CONTROL MODULE A 1 Installation Environment Considerations 24 A 2 Electrical Connections 24 A 3 Adjusting Settings 24 A 4 Display 24 A 5 Operation 25 A 6 Boiler High Limit Temperature Controller 27 A 8 Troubleshooting Error Codes 27 A 9 Intermi...

Страница 5: ...he boiler room Modification substitution or elimination of factory equipped supplied or specified components may result in personal injury or loss of life TO THE OWNER Installation and service of this boiler must be performed by a qualified installer TO THE INSTALLER Leave all instructions with boiler for future reference When this product is installed in the Commonwealth of Massachusetts the inst...

Страница 6: ...n etc during appliance operation and service circulator replacement condensate trap control replacement etc 6 Locate boiler on level solid base as near chimney as possible and centrally located with respect to heat distribution system as practical 7 When installed in utility room door should be wide enough to allow largest boiler part to enter or to permit replacement of another appliance such as ...

Страница 7: ...ate is less than 0 40 air changes per hour See Table 3 for space with boiler only Use equation for multiple appliances Volume 50 ft3 x Total Input Mbh о о Known Air Infiltration Rate See Table 3 for space with boiler only Use equation for multiple appliances Do not use an air infiltration rate ACH greater than 0 60 Volume 21 ft3 ACH x Total Input Mbh о о Refer to National Fuel Gas Code for opening...

Страница 8: ... than that of the relief valve outlet over the entire length of discharge line have no intervening shutoff valve between safety relief valve and discharge to atmosphere do not plug or place any obstruction in discharge line terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing allow complete drainage of the valve and the discharge line be independent...

Страница 9: ...ef valve Systems with automatic fill valves require back flow prevention device Install discharge piping from safety relief valve See Warning Page 8 When boiler is connected to heating system utilizing multiple zoned circulators each circulator must be supplied with flow control valve to prevent gravity circulation Hot water boilers and system must be filled with water and maintained to minimum pr...

Страница 10: ...RCULATOR A PRESSURE REDUCING VALVE PROPER BACKFLOW PROTECTION DEVICE GATE VALVE PURGE VALVE NOTICE Circulators in following illustrations are mounted on system supply side mounting on system return side is also acceptable practice Figure 2 Circulators Mounted on Supply System Boiler Used In Configuration to Chiller System See Special Conditions Page 9 P N IM BWBB 01 240011111 REV C 03 31 2017 ...

Страница 11: ...ge 9 5 CONNECTING SUPPLY AND RETURN PIPING Figure 3 Bypass Piping Automatic Mixing Valve See Bypass Piping Options Page 9 BOILER WATER INLET ALTERNATE CIRCULATOR LOCATION TO SYSTEM FROM SYSTEM CIRCULATOR SHUT OFF VALVE PRESSURE REDUCER VALVE CHECK VALVE BALL VALVE 3 WAY MIXING VALVE AIR SEPARATOR HOSE BIB EXPANSION TANK Note Bypass connection not showing primary secondary piping Note Bypass connec...

Страница 12: ...12 5 CONNECTING SUPPLY AND RETURN PIPING Figure 5 Single Zone System With DHW Priority Figure 6 Multi Zone System with Circulators and DHW Priority P N IM BWBB 01 240011111 REV C 03 31 2017 ...

Страница 13: ...UPPLY AND RETURN PIPING Figure 7 Multi zone System With Zone Valves And DHW Priority With Circulator Figure 8 Multi zone System With Zone Valves And DHW Priority With Zone Valve P N IM BWBB 01 240011111 REV C 03 31 2017 ...

Страница 14: ...of the common venting system the common venting system should be re sized to approach the minimum size determined using the appropriate tables in Chapter 13 of the National Fuel Gas Code ANSI Z223 1 NFPA 54 and or the Natural Gas and Propane Installation Code CAN CSA B149 1 1 Vent pipe must slope upward from boiler not less then inch per 1 foot to the vent terminal 2 Horizontal portions of venting...

Страница 15: ...visible location following installation 5 Thermostat s heat anticipator must be adjusted to match total current draw of all controls associated with boiler during heating cycle 8 VENT DAMPER INSTALLATION INSTRUCTIONS Figure 9 Damper Installation Figure 10 Damper Location NOTE Refer to Figure 9 for steps 1 6 1 Place Vent Damper on or as close to vent outlet of boiler as possible Do not modify draft...

Страница 16: ...with hooks straps bands brackets hangers or building structure components to prevent or dampen excessive vibrations and prevent strain on gas connection Boiler will not support piping weight Use thread joint compound pipe dope suitable for liquefied petroleum gas Install field sourced manual main shutoff valve ground joint union and sediment trap upstream of gas valve See Figure 11 Table 5 Gas Pre...

Страница 17: ...nection 4 Line power connections 5 LWCO kit 550002998 includes wiring instructions and wiring diagrams If using a different LWCO refer to the specific instructions provided with that unit See wiring diagrams on the following two pages for details Thermostat Installation 1 Install thermostat on inside wall about four feet above floor 2 NEVER install thermostat on outside wall 3 Do not install a the...

Страница 18: ...tegrated High Limit Electronic Ignition Control WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal injury or loss of life P N IM BWBB 01 240011111 REV C 03 31 2017 ...

Страница 19: ...19 11 WIRING DIAGRAM Figure 13 Integrated High Limit Electronic Ignition Control P N IM BWBB 01 240011111 REV C 03 31 2017 ...

Страница 20: ...as To Appliance and call qualified service technician or your gas supplier TO TURN OFF GAS TO THE APPLIANCE 1 Set the thermostat to lowest setting 2 Turn off all electric power to the appliance if service is to be performed 3 Push in gas control knob slightly and turn clockwise to OFF DO NOT FORCE 4 Call qualified service technician WARNING If you do not follow these instructions exactly a fire or...

Страница 21: ... maintain circulators Refer to circulator manufacturer s instructions Inspect venting system at the start of each heating season Check vent pipe from boiler to chimney for signs of deterioration by rust or sagging joints Repair if necessary Remove vent pipe at base of chimney or flue and using mirror check vent for obstruction and verify vent is in good working order Inspect boiler flue gas passag...

Страница 22: ... corrosion rust or scale buildup Area around boiler must be kept clear and free of combustible materials gasoline and other flammable vapors and liquids Free flow of combustion and ventilating air to boiler and boiler room must not be restricted or blocked Inspect field sourced low water cutoffs annually or as recommended by low water cutoff manufacturer Flush float type low water cutoffs per manu...

Страница 23: ...column from specified pressure Primary air adjustment is not necessary therefore air shutters are not furnished as standard equipment Air shutters can be furnished on request where required by local codes or conditions CHECK SAFETY CONTROL CIRCUIT Ignition system safety shutoff device must be tested after placing boiler in operation Intermittent Pilot With main burner operating turn pilot gas adju...

Страница 24: ...g transit Check sensing bulb is fully inserted in well and is not loose Verify vent damper connection is made See page 13 A 3 Adjusting Settings To discourage unauthorized changing of settings procedure to enter adjustment mode is required To enter adjustment mode press UP DOWN and I buttons simultaneously for three seconds Press and release I button until parameter requiring adjustment is display...

Страница 25: ...t is open a switch closes to do this The control is waiting for this to occur This may last up to one minute If the vent damper switch has not closed after one minute ERR 55 will be displayed e 17 Diagnostics Another diagnostic check The control will also check the safety switches rollout and vent are closed This will be so quick the control may move on before the STA code is flashed Should the sa...

Страница 26: ...ckouts on this model m 15 Wait for limit to close One of the safety limits rollout vent spill or low water cutoff if one is field installed on the 24V safety circuit has been activated Control will resume normal operation once limit is reset Underlying cause why the limit switch opened MUST be investigated n 16 Flame out of sequence Flame signal sensed before trial ignition Appropriate alarm is se...

Страница 27: ...ay On retry models wait for retry or reset at thermostat Check for correct installation and wiring before replacing any component Control module cannot be repaired If it malfunctions it must be replaced Use only qualified service agent to service ignition systems 1 Perform checkout as first step in troubleshooting Check troubleshooting guide to pinpoint cause of problem See Table 7 page 28 2 If tr...

Страница 28: ... providing expected reading 1 Check sensor is plugged into control board 2 Check sensor wiring is not damaged 3 Scroll display reading to bt and hold sensor bulb securely in you hand It should read a temperature close to body temperature If not replace sensor 55 Damper end switch failed to close Vent damper must confirm it is open switch closes to do this Control did not receive this signal after ...

Страница 29: ...2095 1 Check gas valve gas supply 2 Check all electrical connections are tight 3 Check pilot rod is clean 4 Check for adequate draft 5 Check for adequate combustion air 64 Soft Lockout Internal failure Control is sensing something wrong with electrical circuitry 1 Check all wiring is correct Refer to wiring diagram 2 Check there is a good ground to pilot bracket 65 Hard Lockout Temperature above l...

Страница 30: ... is required for module and pilot burner igniter sensor Check for good metal to metal contact between pilot burner bracket and the main burner Check ground lead from GND BURNER terminal on module to pilot burner Verify connections are clean and tight If wire is damaged or deteriorated replace with No 14 18 gauge moisture resistant thermoplastic insulated wire with 105 C 221 F minimum rating Check ...

Страница 31: ...heck for cracked ceramic insulator which can cause short to ground and replace igniter sensor if necessary At gas valve disconnect main valve wire from MV terminal Turn on power and set thermostat to call for heat Pilot should light main burner will remain off because main valve actuator is disconnected Check pilot flame Verify it is blue steady and envelops 3 8 to 1 2 in 10 to 13 mm of flame rod ...

Страница 32: ...r AC volts 24 volts should be present i IF NOT source of the problem is not in damper check line voltage and 24 volt supply ii If 24 volts is present across brown and black continue to step iii iii Reconnect thermostat wires and turn up heat setting iv Check voltage across black and orange wires in Molex plug 24 volts AC should be present IF NOT source problem is not the damper If 24 volts is pres...

Страница 33: ...le Cause Recommended Solution NO POWER Between 4 1 1 Off on limit 120VAC 2 Bad transformer 3 Loose or broken connections 4 Blown fuse or circuit breaker 5 Disconnect switch off 6 Harness not plugged into receptacle 1 turn limit on 2 Replace transformer 3 Tighten repair or replace connection 4 Replace fuse or reset circuit breaker 5 Turn switch on 6 Plug harness in NO POWER Between 4 2 POWER Betwee...

Страница 34: ...r the obstruction 2 Restore to damper pipe to round verify not binding 3 Correct the condition Damper Rotates Continuously 1 Defective damper motor assembly 1 Replace damper motor assembly Note For troubleshooting only Verify damper is in open position Use service switch to keep damper in open position Place jumper between 2 3 If appliance fires remove jumper and plug receptacle back into damper c...

Страница 35: ...35 Company Address Phone Company Name Tech Initials Service Performed Date SERVICE RECORD P N IM BWBB 01 240011111 REV C 03 31 2017 ...

Страница 36: ... an override which is provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating load decreases This boiler is not used for any space heating This boiler is p...