XFP ENGINEERING MANUAL • Approved Document No. DFU2200502 Rev 1 • Page 7 of 8
XFP 32 ZONE REPEATER PANEL
Installing the standby battery supply
Two new, good quality and fully charged 12V 3.2A Hr valve regulated lead acid batteries are required
as the emergency stand-by power supply for the panel. The batteries should be connected in series
and located in the panel’s enclosure as shown in Fig. 4 .
The battery leads, link wire and nylon cable ties are provided in the panel’s accessory pack.
The panel’s sophisticated battery monitoring unit protects the batteries against deep discharge by acti-
vating a cut off circuit when the stand-by supply voltage reaches 21V approx. If batteries are not fit-
ted, are discharged or in poor condition, a PSU fault will show at the panel.
Always dispose of used batteries according to the battery manufacturer’s instructions.
Fault relay output wiring
The repeater’s failsafe fault relay output switches for any fault condition and is
capable of switching 1A @ 30Vdc. It must NOT be used for switching mains voltages.
GENERAL
FIRE
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
Z
ZONE 9 ZONE 10 ZONE 11 ZONE12 ZONE 13 ZONE 14 Z
D45
SUPPLY
PRESENT
TEST
ACCESSED
GENERAL
DISABLEMENT
PHASED
EVACUATION
GENERAL
FAULT
PSU
FAULT
SYSTEM
FAULT
SOUNDER
STATUS
DELA
RUNNING
Auxilliary
+24V I/P1 I/P2 0v
Relay 1
NC C NO
Relay 2
NC C NO
Relay 3
NC C NO
Fault
NC C NO
Sounder Circuits
+ 1 -
+ 2
REMOVING THIS CIRCUIT
BOARD EXPOSES HAZARDOUS
VOLTAGES - PLEASE REFER TO
INSTALLATION INSTRUCTIONS
WARNING
SENSITIVE TO STATIC
ELECTRICITY - OBSERVE
PRECAUTIONS BEFORE
HANDLING
CAUTION - RISK OF EXPLOSION IF
INCORRECT TYPE OF BATTERIES FITTED.
DISPOSE OF USED BATTERIES ACCORDING
TO THE MANUFACTURERS INSTRUCTIONS.
Mute
Beeper
4
3
Repeater network wiring
The repeater network should be wired in two-core 1.5mm
2
fire resistant screened cable.
Fig. 5: Typical repeater network wiring
At
ONE
panel only (repeater or
main), connect A to A,
B to B and terminate incoming
and outgoing earth screens to
the panel’s side earth post.
This earth post must also be
connected to terminal C on the
network communication card’s
connector block as shown.
IMPORTANT: At all other panels,
connect A to A, B to B and
terminate earth screens to
terminal C only.
TO NEXT
REPEATER
PANEL IF
REQUIRED
NETWORK
COMMUNICATION
CARD
NETWORK
COMMUNICATION
CARD
REPEATER 1
MASTER
REPEATER 2
REPEATER 5
REPEATER 8
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED
=
XFP
MAIN
XFP
REPEATER
XFP
REPEATER
XFP
REPEATER
XFP
REPEATER
Fig. 4 : Battery location and connection details
TO NEXT
REPEATER
PANEL IF
REQUIRED
Red wire from panel
Shorting link (supplied in panel accessory pack)
Black wire from panel
12V battery
–
–
12V battery
+
+