ACCESS LEVEL 2 (Authorised User) CONTROLS AND MENU OPTIONS
Access level 2 is available to authorised, trained personnel only. At this level, the panel’s
Silence/Resound Sounders, Control Panel Reset and Investigate buttons become active and you can:
• Scroll through any fire, pre-alarm or fault conditions that are displayed on the panel’s display
• View any disablements or zones that are being tested (if applicable)
• Enable or disable zones, sounders, outputs, relays and devices (as appropriate)
• Print, display and/or reset the panel’s event history
• Set the time and date
• Change the entry code to access level 2 from its factory default.
Details of how to use the panel’s Silence/Resound Sounders, Control Panel Reset and Investigate
buttons can be found below.
Entering access level 2 -
USING THE PUSHBUTTONS ON THE PANEL:
Entry to access level 2 requires the input of a special four digit code.
Press the MENU button on the panel’s front at access level 1. When the ENTER ACCESS LEVEL 2? prompt
appears, press the Accept
4
button and you will be asked to enter the code:
Enter the access level 2 code using the
5
(1),
4
(2),
6
(3),
3
(4) buttons as appropriate. The default
code to access level 2 is 3 3 3 3 (four presses of the
6
button). If this does not work, the code may have
been changed by an authorised user/engineer. A record of any changes should appear on the System
Set-Up Data Chart on page 20 of this user manual. If they do not, contact your maintenance company
for advice.
Entering access level 2 -
USING THE KEYSWITCH ON THE PANEL:
Entry to access level 2 is gained by turning the panel’s keyswitch to the armed position (I).
Silencing the alarm sounders
To silence any active alarm sounders, enter access level 2 (see above) and momentarily press the
Silence/Resound Sounders button. The alarm sounders will cease to sound and the panel’s general Fire
and relevant Fire Zone indicators will go steady.
Should a fire condition occur on another zone whilst the alarm sounders are silenced, the panel:
• Will sound the sounders programmed for activation by the new zone(s) in alarm
• Will flash its general Fire and appropriate Zone indicator(s) for any new zone(s) in alarm
• May, if programmed, automatically reactivate the silenced alarm sounders and flash any related Fire
Zone indicator(s).
Resounding the alarm sounders
Momentarily pressing the Silence/Resound Sounders button when the alarm sounders are silenced will
resound them. Pressing the Silence/Resound Sounders button again will silence the alarm sounders.
Resetting the panel
After the cause of an alarm has been cleared and the alarm sounders have been silenced (see above),
the panel can be reset by pressing the Control Panel Reset button.
The panel will give a double beep to indicate the reset process has started and, after a few seconds,
the Fire Zone indicators and general Fire indicator will go out to indicate the process is complete. If
there are still any fire conditions on any zones, the panel will go back into alarm as before.
Note that the panel’s Investigate button is only active if an engineer has programmed one or more
zones to operate with a 1st-stage investigation delay period (see page 10 for detailed information
on this feature).
Enter Access Level 2 code:
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000510 Rev 1 • Page 14 of 28