C-TEC HUSH-ACTIV KITS Скачать руководство пользователя страница 2

State

State Condition

Hush-ActiV Indicators

What Happens at Hush-ActiV

1

Normal Operation

•  Power is applied to the detection and sounder circuits which are monitored for open and short circuit faults.

2

Fire

A fire condition has been 
activated from a fire detector.

•  Beeper sounds.
•  HUSH button press moves to State 3.
•  Alarm sounders are activated.
•  Detection zone resets every 60 seconds and requires a confirmation fire condition to stay in this state.
•  If fire condition clears, system resets then automatically returns to State 1.

3

HUSH button 

pressed when 

in Fire

A fire condition has been activated 
but then hushed (silenced).
A 120 seconds hushed (silenced) 
period starts.

•  Beeper pulse rate gradually increases during the hushed period (10 seconds 

 50 seconds 

 90 seconds elapsed).

•  HUSH button press resets the hushed timer for another 120 seconds.
•  If fire condition is cleared within 120 seconds automatically returns to State 1.
•  After 120 seconds have elapsed (and HUSH button NOT pressed) moves to State 2.

4

HUSH button 

pressed when

no Fire or Fault

A 15 minutes hushed (silenced) 
period starts to allow ‘hot works’ 
or cooking by the resident.

•  Beeper pulse rate gradually increases during the hushed period (10 minutes 

 15 minutes elapsed).

•  HUSH button press returns to State 1 after a hushed period of 0 to 12 minutes have elapsed. After a hushed  

 

  period of 13 to 15 minutes have elapsed HUSH button press resets the hushed timer for an additional 15 minutes.
•  After 15 minutes have elapsed automatically returns to State 1.

5

General Fault

A fault condition has been 
activated (e.g. device fault, wiring 
fault, battery fault, EOL missing).

•  Beeper sounds.
•  HUSH button press moves to State 6.
•  If fault condition clears, system resets then automatically returns to State 1.

6

HUSH button 

pressed when in 

Fault

A fault condition has been 
activated but then hushed 
(silenced). A 24 hour hushed 
(silenced) period starts.

•  Beeper muted.

•  HUSH button press resets the hushed timer for another 24 hours.
•  Detection zone resets every 60 seconds and requires a confirmation fault condition to stay in this state.
•  If fault condition clears, system resets then automatically returns to State 1.

7

Mains Fault

External PSU fails and the unit  is 
powered on battery only.

•  Beeper sounds.
•  HUSH button press moves to State 6.
•  If fault condition clears, system resets then automatically returns to State 1.

8

To Enter Test Mode
Press and hold TEST button for >3 seconds.

•  Beeper sounds.
•  Alarm sounders are activated for 5 seconds then automatically returns to State 1.

HUSH-ACTIV OPERATION

Approved Document No. DFU0005086 Rev 3

FIRE ALARM

ancillaries

Hushed

Alarm

Fault

Supply

Hushed

Alarm

Fault

Supply

Hushed

Alarm

Fault

Supply

Hushed

Alarm

Fault

Supply

Hushed

Alarm

Fault

Supply

Hushed

Alarm

Fault

Supply

3 of 3

Hushed

Alarm

Fault

Supply