State
State Condition
Hush-ActiV Indicators
What Happens at Hush-ActiV
1
Normal Operation
• Power is applied to the detection and sounder circuits which are monitored for open and short circuit faults.
2
Fire
A fire condition has been
activated from a fire detector.
• Beeper sounds.
• HUSH button press moves to State 3.
• Alarm sounders are activated.
• Detection zone resets every 60 seconds and requires a confirmation fire condition to stay in this state.
• If fire condition clears, system resets then automatically returns to State 1.
3
HUSH button
pressed when
in Fire
A fire condition has been activated
but then hushed (silenced).
A 120 seconds hushed (silenced)
period starts.
• Beeper pulse rate gradually increases during the hushed period (10 seconds
50 seconds
90 seconds elapsed).
• HUSH button press resets the hushed timer for another 120 seconds.
• If fire condition is cleared within 120 seconds automatically returns to State 1.
• After 120 seconds have elapsed (and HUSH button NOT pressed) moves to State 2.
4
HUSH button
pressed when
no Fire or Fault
A 15 minutes hushed (silenced)
period starts to allow ‘hot works’
or cooking by the resident.
• Beeper pulse rate gradually increases during the hushed period (10 minutes
15 minutes elapsed).
• HUSH button press returns to State 1 after a hushed period of 0 to 12 minutes have elapsed. After a hushed
period of 13 to 15 minutes have elapsed HUSH button press resets the hushed timer for an additional 15 minutes.
• After 15 minutes have elapsed automatically returns to State 1.
5
General Fault
A fault condition has been
activated (e.g. device fault, wiring
fault, battery fault, EOL missing).
• Beeper sounds.
• HUSH button press moves to State 6.
• If fault condition clears, system resets then automatically returns to State 1.
6
HUSH button
pressed when in
Fault
A fault condition has been
activated but then hushed
(silenced). A 24 hour hushed
(silenced) period starts.
• Beeper muted.
• HUSH button press resets the hushed timer for another 24 hours.
• Detection zone resets every 60 seconds and requires a confirmation fault condition to stay in this state.
• If fault condition clears, system resets then automatically returns to State 1.
7
Mains Fault
External PSU fails and the unit is
powered on battery only.
• Beeper sounds.
• HUSH button press moves to State 6.
• If fault condition clears, system resets then automatically returns to State 1.
8
To Enter Test Mode
Press and hold TEST button for >3 seconds.
• Beeper sounds.
• Alarm sounders are activated for 5 seconds then automatically returns to State 1.
HUSH-ACTIV OPERATION
Approved Document No. DFU0005086 Rev 3
FIRE ALARM
ancillaries
Hushed
Alarm
Fault
Supply
Hushed
Alarm
Fault
Supply
Hushed
Alarm
Fault
Supply
Hushed
Alarm
Fault
Supply
Hushed
Alarm
Fault
Supply
Hushed
Alarm
Fault
Supply
3 of 3
Hushed
Alarm
Fault
Supply
E&OE. No responsibility can be accepted by the manufacturer or distributors of these devices for any misinterpretation of this instruction, or for the compliance of the system as a
whole. The manufacturers policy is one of continuous improvement and we reserve the right to make changes to product specifications at our discretion and without prior notice.
Manufacturer: Computionics Limited (C-TEC), Challenge Way, Martland Park, Wigan, Lancashire WN5 0LD.
Hushed
Alarm
Fault
Supply