Repeaters with same address

Symptoms:

General Fault LED + Beeper on front of MFP Main panel, Repeater Transmitter PCB indicator LD3 lights
periodically and indicator LD4 flashes once. Repeaters otherwise function correctly.

Cause: 

Two or more Repeaters with SW4 set with same address.

Solution

: Remove power from the system, alter addresses accordingly and power up again.

Repeaters with Aux PSU Fault

Symptoms:

General Fault LED + PSU Fault LED + Beeper on front of MFP Main panel.

Repeater Transmitter PCB indicator LD3 lit periodically and indicator LD4 flashes ‘n’ times, where n = the
address of the Repeater with the Fault.

Repeater indicators Power Supply Healthy and Local and General Fault LEDs flashing, otherwise responds
to system state changes correctly.

Cause: 

Aux PSU sense link omitted from Repeater.

Solution: 

Refit link.

Keyswitch buttons inoperative

Symptoms:

Buttons inoperative on Repeater otherwise Repeater responds to system state changes.

Cause 1: 

Keyswitch loom has become dislodged.

Solution 1:

Refit loom.

Cause 2: 

Repeater’s Main Receiver PCB has partially failed.

Solution 2: 

Replace PCB.

Failure of the Repeater Transmitter PCB

Symptoms:

MFP Main panel may indicate a fault condition.

Repeaters do not respond to button presses, or changes of system state.

Repeater has local Fault LED flashing, Power Supply Healthy LED lit steady.

Cause: 

Repeater Transmitter PCB failure.

Solution: 

Change Repeater Transmitter PCB.

FF596 MFP Repeater Panel

Installation Instructions 

Approved Document No. DFUR50010A Rev 2

Errors & Omissions Excepted. The manufacturer of this product operates a policy of continuous improvement and reserves the right to alter product specifications at its
discretion and without prior notice. All of the instructions covered in this manual have been carefully checked prior to publication. However, no responsibility can be accepted
by the manufacturer for any inaccuracies or for any misinterpretation of an instruction or guidance note.

Содержание FF596

Страница 1: ...ay be run in any convenient way that complies with the relevant Fire and Electrical Regulations for the site The wiring may also be spurred if required see Figure 1 below The Repeater system is implem...

Страница 2: ...locally then this link must be removed If the link is removed and the Auxiliary Power Supply fails or is not fitted then the Repeater will sense a Fault condition and indicate this appropriately PLK2...

Страница 3: ...ector PL3 KEY PL1 Loom to Base Main Receiver PCB SW4 8 4 2 1 ADDRESS PLK1 PL2 EXPANSION PL1 INPUT 8 Zone Extender PCB PL1 INPUT 8 Zone Extender PCB PL2 OUTPUT PL1 INPUT 8 Zone Extender PCB PL2 OUTPUT...

Страница 4: ...links on Main Control PCB Repeater Transmiter PCB FF596T PLK1 AUX PLK2 LOCAL SW1 ON VR1 VR2 Main Control PCB mounted in MFP Main Panel Long 10 way loom to Zone Cards if fitted Repeater Network Connec...

Страница 5: ...of eight zones up to a maximum of 32 zones by the addition of an Extender kit Part No FF596R This kit consists of an 8 Zone Extender PCB looms and mounting hardware see Repeater Panel Installation se...

Страница 6: ...in panel and the MFP Repeater s Setting the Repeater Addresses Each Main Receiver PCB must have a unique address to enable the system to be monitored The addresses are set up by fitting the supplied l...

Страница 7: ...ily Pressing the Reset button on a Repeater whilst the keyswitch is in Arm Controls will also cause the MFP Main panel to execute a Reset cycle If there is no Fire Condition and no faults present afte...

Страница 8: ...rative on Repeater otherwise Repeater responds to system state changes Cause 1 Keyswitch loom has become dislodged Solution 1 Refit loom Cause 2 Repeater s Main Receiver PCB has partially failed Solut...

Отзывы: