Roller Door Remote Control
ROLLER868
User Manual
Connection Details
1
Live
Power supply 230Vac
2
Neutral
3
Motor common
Motor 230Vac
Maximum power 0.75Hp, 550W
4
Motor close
5
Motor open
6
12Vac output
Auxiliary power output
12Vac 130mA max
7
8
Common
Common connection of safety and start push button
9
Safety
Safety input for connection of safety edge or photocells. If a non-resistive safety edge or
photocells are used an 8k2 resistor must be connected in series (see diagrams). Resistor
taped to enclosure cover
10 Start push button
Start push button, normally open (N.O)
1 2 3 4 5
Motor
Live
Neutral
Earth
Mains supply
230Vac
* connections for right hand mounted motor.
Swap brown and black if left mounted
6 7 8 9 10
1 2
ON
Close
(Deadman)
Open
Dipswitch 2 ON
1B bridged
J1
Push buttons, rocker or keyswitch
6 7 8 9 10
1 2
ON
1B bridged
J1
Start push button
8k2 resistor
To photocell
normally closed
contact (N.C)
12Vac to power
photocell
Resistive safety edge
connects directly to
8 & 9 with no resistor
FIG1. Push to run open, deadman close
FIG2. Push to run open & close with
photocells and/or safety edge
6 7 8 9 10
1 2
ON
2B bridged
J1
Start push
button
FIG3. Push to run open & close without
photocells or safety edge