6–2
Chapter 6: PLC Communications
6
®
EA1-TCL-M Hardware User Manual, 1st Ed., 12/09
Introduction
The
C-more®
6” Color Micro-Graphic panels are capable of communicating with
AutomationDirect CLICK and the entire
Direct
LOGIC family of PLCs. The panel is capable
of communicating using RS232, RS422 or RS485 on Port2.
The
C-more®
6” Micro-Graphic panel communicates using the following cables.
• EA-2CBL - connects to CLICK, DL05, DL105, DL205, DL350, DL450, H2-WINPLC phone jack:
RJ12 - 15 pin D-sub.
• EA-2CBL-1 - connects to D2-250, D250-1, D2-260, DL06 VGA connector: 15-pin HD - 15 pin
D-sub.
The panel also has the ability to communicate with Allen-Bradley PLCs that support the Allen-
Bradley DF1 and DH485 protocols. Use Port2 with the following cables to connect the panel
to a majority of Allen-Bradley PLCs.
• EA-MLOGIX-CBL – connects to AB MicroLogix 1000, 1100, 1200 1400 & 1500:
15-pin D-sub - 8-pin DIN
• EA-SLC-232-CBL – connects to AB SLC 5/03, /04, /05, ControlLogix, CompactLogix, FlexLogix:
15-pin D-sub - 9-pin Dshell female
• EA-PLC5-232-CBL – connects to AB PLC5: 15-pin Dshell - 25-pin Dshell
• EA-DH485-CBL – connects to AB MicroLogix, SLC500, and any PLC using AB AIC device:
15-pin Dshell - RJ45 8-pin
The PLC Compatibility and Connection Chart tables on the following pages list all of the
various PLCs and protocols that can be configured. Other third party PLCs include GE,
Mitsubishi, Omron, Modicon and Siemens. The rest of this chapter shows the pin to pin
connections of all the available cables plus wiring diagrams to construct cables.
NOTE:
Refer to the PLC Compatability and Connection Charts beginning on page 6-8 for a complete listing of
PLC connections for the C-more 6” Micro-Graphic panel.
NOTE:
When the panel is powered through Port1 from a connected PC, the screen brightness is diminished
because the panel is running in
Low-Power Mode
. Connect an external 12-24 VDC power source when the
panel is installed in its application for full brightness.
Содержание EA1-T6CL
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 14: ......
Страница 60: ......
Страница 66: ......
Страница 118: ......
Страница 125: ...Notes 7 7 Chapter 7 Maintenance 7 EA1 TCL M Hardware User Manual 1st Ed 12 09 ...
Страница 126: ......
Страница 169: ......
Страница 170: ...B B C MORE MICRO GRAPHIC PANEL RUNTIME ERRORS AP APPENDIX APPENDIX In This Appendix Introduction B 2 Panel Errors B 2 ...
Страница 179: ......