Motion detector flush-mounted installation

C-LOGIC 645-MD

SKU: CLOGIC645MD230VCBINT

INSTRUCTIONS MANUAL

ENGLISH 

EN

The product adopts good sensitivity detector and integrated circuit. It gathers automatism, 

convenience, safety, saving-energy and practicality functions. The wide detection field con

-

sists of up and down, left and right service field. It works by receiving human motion infrared 

rays. When one enters the detection field, it can start the load at once and identify automati

-

cally day and night. Its installation is very convenient and its using is very wide.

SPECIFICATION:

•  Power Source: 220-240V~                   

•  Detection Range: 180°

•  Power Frequency: 50/60Hz                       

•  Detection Distance: max. 9 m (<24ºC)

•  Ambient Light: <3-2000LUX (adjustable)         

• 

Working Temperature: -20~+40ºC

•  Time Delay: 

 • Min.10sec±3sec                  

 • Max.7min±2min 

• 

Working Humidity: <93%RH                  

•  Power Consumption: approx. 0.5W

•  Rated Load: 

 • Max.500W (incandescent lamp)    

 • *200W (energy-saving and LED lamps)

 

*Minimum power requirement: 5W 2-wire

•  Detection Moving Speed: 0.6 - 1.5 m/s    

•  Installation Height: 1 - 1.8 m

•  Protection degree: IP 20

FUNCTION:

• 

Can identify day and night: The consumer can adjust working state in different ambient 

light. It can work in the daytime and at night when LUX knob is adjusted on the “sun” 

position (max). It can work in the ambient light less than 3LUX when it is adjusted on the 

“moon” position (min). As for the adjustment pattern, please refer to the testing pattern. 

•  Time-Delay is added continually: When it receives the second induction signals within the 

first induction period, it will compute time once more on the basic of the first time-delay rest.

•  The switch: “ON”, “OFF”, “PIR”.

INSTALLATION ADVICE:

As the detector responds to changes in temperature, avoid the following situations:

• 

Avoid pointing the detector towards objects with highly reflective surfaces, such as mirrors 

etc.

•  Avoid mounting the detector near heat sources, such as heating vents, air conditioning 

units, light etc.

•  Avoid pointing the detector towards objects that may move in the wind, such as curtains, 

tall plants etc.

CONNECTION:

¡Warning! ¡Danger of death through electric shock!

•  Must be installed by professional electrician.

•  Disconnect power source.

•  Cover or shied any adjacent live components.

•  Ensure device cannot be switched on.

• 

Check power supply is disconnected.

• 

Unload the faceplate of sensor and adjust the time and LUX knob.(refer to figure 1)

•  Loose the screws in the connection terminal, and then connect the power to connection 

terminal of sensor according to connection-wire diagram. (according to your actual 

situation, here you can connect three wire or two wire)

•  If you want to install it in circular hole, put the sensor into the hole and tighten the splay 

bolt on both sides. If you want to install in quadrate hole, put the sensor into the hole, fix 

the screw through the mounting hole.

• 

Install back the faceplate, switch on the power and then test it.

TEST:

• 

Set the function switch to “ON”, set “TIME” anti-clockwise to minimum, “LUX” clockwise 

to maximum.

•  Switch on the power, the lamp should be on.

•  Set the function switch to “OFF”, the lamp should be off immediately.

•  Set the function switch to “PIR”, the sensor and its connected lamp will have no signal 

at the beginning. After Warm-up 30sec, the sensor can start work. If the sensor receives 

the induction signal, the lamp will turn on. While there is no another induction signal any 

more, the load should stop working within 10sec±3sec and the lamp would turn off. 

• 

Turn LUX knob anti-clockwise on the minimum (moon). If the ambient light is more than 

3LUX, the sensor would not work and the lamp stop working too. If the ambient light is 

less than 3LUX (darkness), the sensor would work. Under no induction signal condition, 

the load should stop working within 10sec±3sec.

Note: when testing in daylight, please turn LUX knob to 

 (SUN) position, otherwise 

the sensor lamp could not work! 

If the lamp is more than 60W, the distance between lamp and sensor should be 60cm at least.
SOME PROBLEM AND SOLVED WAY:

• 

The load do not work:

a. Please check if the connection-wiring of power and load is correct.

b. Please check if the load is good.

c. Please check if the working light sets correspond to ambient light.

•  The sensitivity is poor:

a. Please check if there has any hindrance in front of the detection window to affect to re

-

ceive the signal.

b. Please check if the ambient temperature is too high.

c. Please check if the induction signal source is in the detection fields.

d. Please check if the installation height corresponds to the height showed in the instruction.

e. Please check if the moving orientation is correct.

•  The sensor can not shut off the load automatically:

a. Please check if there is continual signal in the detection field.

b. Please check if the time delay is the longest.

c. Please check if the power corresponds to the instruction.

SENSITIVITY

   

 

    

                    

Good sensitivity          

                       Poor  sensitivity

CONDITIONS TO AVOID

 

 

 

 

MOUNTING

 

2 wires

3 wires

    

              Fig. 1

CONNECTION-WIRE 

  TEST

      

 

2 wires           

3 wires

 

MANUFACTURER: MGL International

APAC: 

MGL GLOBAL SOLUTIONS LTD

[email protected]

Flat 4-1, 4/F, No. 35, Section 3 Minquan 

East Road. Taipei, Taiwan.

Tel: +886 2-2508-0877

EMEA: 

MGL EUMAN S.L.

[email protected]

Parque Empresarial Argame, 33163 

Morcín. Asturias, Spain.

Tel: +34 985-08-18-70

AMERICAS: 

MGL AMERICA, LLC.

[email protected]  

US East Coast:

 2810 Coliseum Centre 

Drive, Ste. 100. Charlotte, North Carolina, 

28217 USA

Tel: +1 833 533-5899

US West Coast:

 760 Challenger Street. 

Brea, California 92821 USA

Tel: +1 310-728-6220

www.mgl-intl.com

Содержание 645-MD

Страница 1: ...ponga el detector en el agujero y fíjelo con los tornillos a través de los orificios de montaje Vuelva a instalar la placa frontal conecte la alimentación y luego pruebe su funcionamiento TEST Ubique el interruptor de función en ON el interruptor TIME en sentido antihorario al mínimo y el interruptor LUX en sentido horario al máximo Conecte la alimentación la lámpara debería encenderse Ubique el i...

Страница 2: ...f you want to install it in circular hole put the sensor into the hole and tighten the splay bolt on both sides If you want to install in quadrate hole put the sensor into the hole fix the screw through the mounting hole Install back the faceplate switch on the power and then test it TEST Set the function switch to ON set TIME anti clockwise to minimum LUX clockwise to maximum Switch on the power ...

Страница 3: ...haitez installer dans un trou carré placer le détecteur dans le trou et fixer le détecteur avec des vis à travers les trous de montage Réinstaller la façade connecter l alimentation et tester son fonctionnement TEST Placez le sélecteur de fonction en ON l interrupteur TIME En sens antihoraire au minimum Y l interrupteur LUZ en sens horaire au maximum Connectez l alimentation la lampe doit allumer ...

Страница 4: ...so de separação de ambos os lados Se você deseja instalar em um buraco quadrado colocar o detector no orifício e fixe com parafusos através dos furos de montagem Reinstalaropainelfrontal conecteaalimentaçãoe emseguida testaroseufuncionamento TESTE Coloque a chave de função para ON o interruptor TIME anti horário para o mínimo e interruptor LUX no sentido horário até o máximo Ligue a alimentação a ...

Отзывы: