background image

Document:  

Date

Created By: 

 

 

LPN00703X0001A0_A 

  08-16-2021

TMT 

  

INSTALLATION INSTRUCTIONS

C-WP-A-TWP Series

http://lighting.cree.com/warranty      |     866.924.3645     

1.  Remove lens assembly by loosening screws on side of frame. 

Swing lens assembly open, disconnect quick-connect wiring 

connector, and slide lens assembly on hinges to remove from 

mounting box. See 

Figure 1.

2.  Remove appropriate conduit plug from back wall or side of 

mounting box.

3.  Drill holes at knockout locations in the four corners of the mounting 

box for attachment of fixture to mounting surface. See 

Figure 4.

4.  Attach conduit to mounting box at chosen threaded opening. 

NOTE: To ensure a watertight seal, teflon tape should be used on 

conduit threads.

5.  Attach the mounting box to the mounting surface using customer 

supplied fasteners appropriate for the mounting surface. Fasteners 

should be passed through the knockout holes removed in Step 3 

and threaded into mounting surface. 

NOTE: 

A high grade caulking material, such as silicone rubber, 

should be used between the four gaskets in the corners and the 

mounting surface to prevent water entry into the fixture or junction 

box.

6.  Use switch inside moutning box to set desired color temperature. 

See 

Figure 5.

 

NOTE:

 Power must always be OFF when adjusting color 

temperature.

7. 

Rotate knob to select desired wattage for fixture. See 

Figure 6.

 

NOTE:

 Power must always be OFF when adjusting wattage.

8.  Make wiring connections per the Electrical Connections section.

9.  Replace the lens assembly on hinges, re-connect quick-connect 

wiring connectors, and swing lens into place. Retighten screws 

that were loosened in Step 1 above.

MOUNTING USING CONDUIT

Fixture is equipped with universal volt driver 120-277V 

(ie. 120V, 208V, 240V or 277V)

PHASE TO NEUTRAL WIRING 120/277V

1.  Connect supply ground to driver ground (green) lead 

and ground (green) lead attached to housing.

2.  Connect supply common to fixture neutral (white) lead.
3.  Connect supply Vin to fixture hot (black) lead.

Tuck all wires carefully into wiring chamber ensuring that no 

wires are pinched.

PHASE TO PHASE WIRING 208/240V

1.  Connect supply ground to driver ground (green) lead 

and ground (green) lead attached to housing.

2.  Connect supply L1 (Hot) to fixture neutral (white) lead.
3.  Connect supply L2 (Hot) to fixture hot (black) lead.

Tuck all wires carefully into wiring chamber ensuring that no 

wires are pinched.

ELECTRICAL CONNECTIONS

CAUTION:

 Changes or modifications not expressly approved could 

void your authority to use this equipment. 
This device complies with part 15 of the FCC Rules. Operation is 
subject to the following two conditions: (1) This device may not cause 
harmful interference, and (2) this device must accept any interference 
received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits 
for a Class A digital device, pursuant to part 15 of the FCC Rules. 
These limits are designed to provide reasonable protection against 
harmful interference when the equipment is operated in a commercial 
environment. This equipment generates, uses, and can radiate radio 
frequency energy and, if not installed and used in accordance with 
the instruction manual, may cause harmful interference to radio 
communications. Operation of this equipment in a residential area 
is likely to cause harmful interference in which case the user will be 
required to correct the interference at his own expense.
CAN ICES-005 (A)/NMB-005 (A)

FCC NOTICE Class A

FIGURE 5

FIGURE 6

FIGURE 4

Отзывы: