OPTION 3-0 EXIT TIME

  

5-105

 Seconds. DEFAULT. 30 secs.

Enter 3-0  - LED 6 will light up. This has been preset for factory default  - at
30 seconds. A new time may be programmed by entering the relevant
keys which total up to make the required time multiplied by 5. Once
program is set press * to confirm. The accept tone will sound.

Example of setting 30 seconds

6

 x 5 = 30

Example of setting 60 seconds

1+5+6

 x 5 = 60

Example of setting 105 seconds

1+2+3+4+5+6

 x 5 =105

OPTION 3-1 ENTRY TIME

 

 5 - 105

 seconds. DEFAULT 30 secs.

Enter 3-1 - LED 6 will light up. Again this has been preset  for factory
default at 30 seconds. To reprogram the entry time follow exactly the
same directions as the EXIT TIME. Again press * to confirm option. The
accept tone will sound.

OPTION 3-2 BELL DURATION

  1-21 minutes. DE FAULT 15 mins.

Enter 3-2 - LEDs 6,5 and 4 will light up. This has been  preset for factory
default at  15 minutes.  A new time may be programmed by entering the
keys which when totalled up come to the desired time. Once program is
set. Press * to confirm. The accept tone will sound.

Example to program 21 minutes

1+2+3+4+5+6

 = 21 minutes

OPTION 3-3

 

NIGHT SET EXIT TIME

  5 - 105 seconds. DEFAULT 15 secs.

Enter 3-3 - LED 3 will light up. This has been  preset for factory default  15
seconds.  A new time may be programmed by the same procedure as for
the other entry and exit timers. Press * to confirm. The accept tone will
sound.

OPTION 4-X. ZONE PROGRAMMING.

Enter 4 plus the zone number, for example 4-3 will allow programming for
zone number 3. Using the chart below program the desired options for
that zone. There are 6 primary zone types. Alarm, Full set entry zone,
Night set entry zone, 24 hour zone, Fire zone and Personal attack zone.
Working to the right of the zone type are zone attributes and one or more
can be added. If a zone is pre-programmed pressing the 0 key will clear
the entry.

Содержание ACTIVE 5

Страница 1: ...ACTIVE 5 ENGINEERING MANUAL C K Systems Ltd C031 066 Issue 3...

Страница 2: ...the alarm system Up to 3 remote keypads can be used on the system The positioning of these should be agreed with the user once the entry exit routes and the Part Set functions have been explained to t...

Страница 3: ...however if for some reason you find it not to be the same simply perform a factory reset and this will revert the panel to the above settings SPECIFICATION FOR SOFTWARE REVISION NUMBER V3 0 The softwa...

Страница 4: ...cable must be separate to all other wiring The cable MUST be earthed and we recommend power is taken from a 3 Amp fused spur and wired by a qualified electrician 2 Battery connection The Active 5 req...

Страница 5: ...m the AUX 12 6 Internal sounders Speaker The control panel is fitted with a 35 Ohm speaker in the housing to aid in audible alarms If an extra speaker s is required it should be connected to the termi...

Страница 6: ...be fitted mark the holes for the mounting position 2 Screw the backbox in the agreed position 3 Note the rear entry of cabling WIRING A REMOTE KEYPAD 1 The remote keypads require 6 core cable for the...

Страница 7: ...ur contact or shunt lock needs to go between S2 and the right hand terminal of the exit zone LINE FAULT INPUT If you are using the Active 5X which is a comms version of the Active 5 control panel you...

Страница 8: ...nds whereby the panel will jump out of engineering mode automatically Pressing the HASH key will manually exit engineering If for any reason you need to return to engineering mode you can enter your e...

Страница 9: ...4 will light up This has been preset for factory default at 15 minutes A new time may be programmed by entering the keys which when totalled up come to the desired time Once program is set Press to c...

Страница 10: ...ion In the day condition visual indication may be programmed option 7 4 1 FULL SET ENTRY ZONE This zone type controls the entry and exit to and from the alarm system When the control is armed tripping...

Страница 11: ...be selected with alarm type zones This will make the zone in operative during the Night set arming period Night set arming cannot be selected until one zone has had this option selected WALK THROUGH...

Страница 12: ...und Follow this procedure for all or any zones you want to program NOTE All entry zones are isolated in home set Full set entry acts as normal alarm in night set Night set entry acts as normal alarm i...

Страница 13: ...system may only be reset by the installer or his representative Entry of the Engineer code is required befo re the system will set again 72 2 Eng only PA reset Following a PA alarm which has been rem...

Страница 14: ...R H H RTN ACTIVEGUARD STB S 12V 12V RIGHT HAND TAMPER ACTIVE GUARD 3 ST SW V V RET SECURIGUARD STROBE S SUPPLY SUPPLY LEFT HAND TAMPER NOVA GUARD 2 T STROBE S 12V 12V R SPIRIT AU1000 STB TRG HOLD OFF...

Страница 15: ...ROPEAN OPTIONS BATTERY VOLTAGE V AUX VOLTAGE V INSTALLED BY THIS INFORMATION SHOULD BE KEPT EITHER INSIDE THE CONTROL PANEL OR WITH THE INSTALLER IT CAN BE USED TO REFER TO PROGRAMMING DETAILS WHEN NE...

Отзывы: