The Power Button on the front of the unit.
The MCB protecting the Normal circuit and the EPS circuit.
Any relevant switches, MCBs or other isolators used in the Backup Circuit.
Show the owner the location of the Shutdown Procedure labels.
VI. Frequently Asked Questions and Maintenance
The personnel safety shall be ensured during product troubleshooting.
1 Frequently Asked Questions and Solutions
Question description
Solutions
Failure of Energy Pod to start up
Check whether the power grid wire is correctly
connected to the reliable power grid
Check whether the fuse at the bottom is installed
correctly
Check whether the BMS circuit breaker is closed
Fault prompt during startup of Energy Pod
Check whether the power grid wiring is correctly
carried out
Check whether the Battery is connected reliably
Check whether the CT is installed in the correct
direction
Check whether the external communication
interface is connected correctly
2 Fault Code
■ When the product fault cannot be judged by direct observation, the hardware is
detected to be free of faults (including PCS and BMS communication line, BMS
and BIC communication line, BA Switch closed and CT correctly installed), and
the fault cannot be cleared after re-power-on and restart (i.e., shut down by
pressing the button and disconnect the power grid, and then reconnect the power
grid and start up by pressing the button), the fault information of the relevant
equipment may be viewed through the fault code or monitoring website.
■ The upper computer is connected by use of the 485 interface to obtain the fault
code.
■ Fault Code List.
The fault light will be on when the system fault as listed in the following table.
Generally, the fault will be automatically cleared within 30s~180s. If the fault cannot
be automatically cleared for a long time, the system needs to be cut off and restarted.
If the fault still exists, please contact the dealer.
S/N
Code
Fault Item
BMS
1
15000
No battery pack available
2
15001
Failed to activate
3
15002
Stop failed
4
15003
Disconnection from PCS_CAN
5
15004
Disconnection from DCDC_CAN
6
15200
Disconnection of BIC_CAN
7
15201
BIC fault
8
15202
Serious overvoltage
9
15203
Serious undervoltage
10
15204
Serious high temperature