B
attery
-Box LV User Manual
Page 5
3 Technical Data
When B-Box works in different temperatures, the current of charge and discharge will be
adjusted automatically, battery will permit lower current when operating temperature gets
lower. Please refer to below table for the detail parameters setting:
Parameter setting of charge current in various temperatures
Protect temp. /Resume temp. (
℃
)
Normal current(A)
-7~2
0.06C*N
2~12
0.12C*N
12~50
0.7C*N
Remark:
1. It will take 2 minutes for the charge current adjustment.
2. N= Quantity of B-Plus 2.5 battery
Discharge current control under different temperatures?
Protect temp. / Resume temp.(
℃
)
Normal current(A)
-10~50
0.7~1C*N
Remark:
1.N= Quantity of B-Plus 2.5 battery
B-Box Res 2.5
B-Box Res 5.0
B-Box Res 7.5
B-Box Res 10.0
Battery Type
Lithium Iron phosphate battery
Battery module
B-Plus 2.5
Max Output power(kW)
2.5
5.0
7.5
10.0
Usable battery energy(kWh)(0.2C
charge &discharge @+25
℃
)(kWh)
2.56
5.12
7.68
10.24
Nominal voltage(V)
51.2
Operating Voltage Range(V)
43.2~56.4
Operating Temperature Range[
℃
]
-10~+50
Communication
RS485/CAN
Cabinet Net Dimension(W*D*H
mm)(Without ground feet)
620* 335* 1650
Net Weight(Kg)
103
137
171
205
Enclosure Protection
IP55