background image

AIR-EAGLE

®

 

XLT 

900 MHz RF Receiver 

MODEL 44UL-2000-DC 

 

RELAY MODES OF OPERATION 

 

Auto Reset (Maintained Momentary)

 

When signal is received from an authorized transmitter, the relay will 
energize. The relay will maintain the energized state as long as the 
transmitter is sending the signal. The relay de-energizes when the 
transmitted signal stops. 

Toggle Reset (Toggle Latch)

 

When a signal is received from an authorized transmitter, the relay will 
energize and latch. The relay stays energized until the same signal is 
received again, at which time it unlatches and de-energizes. 

Latching Reset (True Latch)

 

When a signal is received from an authorized transmitter, the relay will 
energize and latch. The relay stays energized until a different signal is 
received from the transmitter, at which time it unlatches and de-energizes. 
i.e. 

– Transmission from Input 1 of authorized transmitter energizes and 

latches relay 1. Transmission from Input 2 of an authorized transmitter de-
energizes relay 1. 

 

RELAY & FREQUENCY SET-UP 

 

 
The unit is shipped from the factory with SEL1 switches in the open 
positions. All four relays will operate as maintained momentary and unit is 
receiving commands on frequency one.  If you wish to change these 
default settings, follow the instructions on the table below. 
 

 

1)  Remove power from unit 

2)  Remove top cover. 

3)  Select desired relay operation and/or network frequency using table 

below. 

4)  Reattach cover and apply power. 

5)  Programming is now complete.  

RELAY CONFIGURATION 

SEL1 

SWITCH 

NUMBER 

OPEN 

CLOSED 

SW1 

Relay #1 momentary 

(default)

 

Relay #1 toggle/latch 

SW2 

Relay #2 momentary 

(default)

 

Relay #2 toggle/latch 

SW3 

Relay #3 momentary 

(default)

 

Relay #3 toggle/latch 

SW4 

Relay #4 momentary 

(default)

 

Relay #4 toggle/latch 

FREQUENCY SET-UP 

SEL1 

(SW5-7) 

Network 

Frequency 

SW5 

SW6 

SW7 

(default)

 

OPEN 

OPEN 

OPEN 

CLOSED  

OPEN 

OPEN 

OPEN 

CLOSED 

OPEN 

CLOSED  

CLOSED 

OPEN 

OPEN 

OPEN 

CLOSED 

CLOSED 

OPEN 

CLOSED 

OPEN 

CLOSED 

CLOSED 

 

 
 
 

UL SPECIFICATIONS & CLASSIFICATIONS 

 

SPECIFICATIONS 

DC Input 

10 

– 24 VDC @ 10 Watts 

Relay Contacts  

SPDT 5 amp @ 120VAC or 30VDC 

Fuse Protected 

1 amp 

Receiver Frequency 

900 MHz Spread Spectrum 

Receiver Range 

Approximately 2500 feet (Up to 4 miles 
with external high gain antenna) 

Receiver Channels 

Seven independent network frequencies 

Operating Temperature 

-10

o

 C to +55

o

 C 

Altitude 

Under 2000 meters 

Enclosure 

Polycarbonate, IP66 Approved  

Weight 

Approx 2 lbs. 

CLASSIFICATIONS 

Automatic Control and Electrically Operated Control 

Incorporated Control and an Independently Mounted Control 

Type 1.C Action; Micro-Interruption 

PTI of Materials Used for Insulation: Material Group IIIb 

Electrical Shock Risk: Class II Control 

Period of Electrical Stress Across Insulating Parts Supporting Live 
Parts: Long Period 

Pollution Degree 2 

Number of Cycles of Activation: 30,000 (Relay) 

 
DIMENSIONS 

 

 

Page 2 

 