Pic. 6 . Fan and feeder operation periods. 

 
Parameters  related  to  Operation  mode  are: 

Feeder  operating  time

  and 

blowing  power

 

located in: 

Menu 

 

Boiler  settings 

  Power 

modulation   

and 

Operation  time  period

  located  in      

Menu 

 

Service settings 

 Boiler settings.  

There are two regulation modes responsible 
for stabilization of boiler preset temperature: 

Menu 

 

Boiler  settings 

  Regulation 

mode  
 
Standard mode operation 

If  the  boiler’s  temperature  reach  preset  one 
then 

the 

controller 

switches 

of 

to 

SUPERVISION mode.  

Controller  is  equipped  with  boiler’s  power 
modulation  mechanism  –  which  allows  for 
gradual  power  reduction  when  approaching 
the preset temperature. 
There are three power levels: 
Maximal power 100% 
Medium power 50% 
Minimum power 30% 
Current  power  level  is  displayed  on  the 
screen  as  3-segmented  indications  rate  the 
left side of boiler’s icon. 

 

Pic. 7. Power level indicator in main window. 

 
 
Each level can be allocated with separate fuel 
feeding  times  and  blowing  power  which 

influence  on  actual  boiler’s  power  level. 
Power levels parameters are available in the 
menu: 
 

Menu 

 Boiler settings 

 Power 

modulation

.

 

The  controller  regulates  burner’s  power  with 
which  it  operates  depending  on  preset 
temperature 

and 

defined 

hysteresis 

Hysteresis  H2

  and 

Hysteresis  H1

 

Pic.  8 

Hysteresis 

H1 and H2 

 

It is possible to configure volumes H1 and H2 
in  such  a  way  that  modulation  is  done 
without  intermediate  position.  That  means 
switching  from  100%  to  30%  with  omission 
of  50%  power  (right  side  of  the  picture). 
 

 

 

 Pic. 8 Hysteresis H1 and H2 of power modulation 

 

Operation in Fuzzy Logic mode 

In  Fuzzy  Logic  mode  the  controller 
automatically  regulates  burner  power  to 
allow  boiler  operation  in  such  a  way  to 
maintain its temperature on preset level. The 
controller  uses  power  levels  defined  in 
Standard mode. In this mode the parameters 

Hysteresis H2

 and 

Hysteresis H1

 

do not have 

to be set.

 

The  Fuzzy  Logic  mode  unlike  the  Standard 
mode  is  not  faulty  in  respect  of  failing  to 
reach  the  preset  boiler  temperature  due  to 
incorrect  adjustment  of 

Hysteresis  H2

  and 

Hysteresis  H1. 

It  also  allows  for  quicker 

reach the preset temperature. 

Содержание RControl EM890

Страница 1: ...unctions available in additional module B functions available in additional module MX 03 room panel ecoSTER200 non standard option USER MANUAL FOR MAINTENANCE AND INSTALLATION EDITION 1 0 APPLIES FOR...

Страница 2: ......

Страница 3: ...ONDITIONS 22 12 CONTROLLER INSTALLATION 22 12 1 ENVIRONMENTAL CONDITIONS 22 12 2 INSTALLATION REQUIREMENTS 22 12 3 INSTALLATION 23 12 4 ELECTRIC CIRCUIT CONNECTION 23 12 5 SAFETY CONNECTIONS 24 12 6 E...

Страница 4: ...4 17 4 NETWORK FUSE REPLACEMENT 40 17 5 CONTROL PANEL REPLACEMENT 40 18 LAMBDA PROBE 41 19 POSSIBLE FAULTS DESCRIPTION 42 20 CONTROLLER CONFIGURATION BY BOILER PRODUCER 43 21 CHANGES REGISTER 43...

Страница 5: ...eder etc The controller is for boiler pellet burner producers The producer before its use should check if the cooperation between the controller and the boiler burner is correct and is not dangerous T...

Страница 6: ...ser s manual of the controller is divided into two parts for the user and for the installer However in both parts vital information concerning safety is included That is why the user should get acquai...

Страница 7: ...USER MANUAL FOR CONTROLLER R Control 890...

Страница 8: ...ion Automatic disinfection SUMMER Switch on temperature SUMMER Switch off temperature SUMMER Mixer settings 1 2 3 4 5 Mixer preset temperature Room mixer thermostat Mixer weather control Mixer heating...

Страница 9: ...iler preset temperature increase from mixer circulation P Weather control switch on for boiler circulation R Active return protection B Preset temperature increase to load the buffer 5 Symbol signalli...

Страница 10: ...TEMPERATURE SETTING The preset boiler temperature and preset circuits temperature can be set in the menu possible temperatures are restricted with range of respective service parameters of the contro...

Страница 11: ...lowing power which influence on actual boiler s power level Power levels parameters are available in the menu Menu Boiler settings Power modulation The controller regulates burner s power with which i...

Страница 12: ...temperature gradually decreasing Incorrect settings can cause boiler overheating Maximum time of boiler s operating in supervision mode is defined in parameter Supervision time If after this time in S...

Страница 13: ...flora It is absolutely important to inform all the inmates about activating the disinfection function There is a danger of scalding with HW hot water Once a week at night between Sunday and Monday at...

Страница 14: ...value when preset temperature in a room will be reached Similarly like it was described in previous point not recommended or automatically constantly correct heating cycle temperature It is not recom...

Страница 15: ...nsulated require setting heating curve with higher values and for better isolated buildings heating curve will have lower value Preset temperature counted according to heating curve can be decreased o...

Страница 16: ...Service settings Settings of CH and HW Settings of time control of circular pump are analogical to settings of night reductions In defined time periods circular pump is deactivated In omitted periods...

Страница 17: ...r connecting additional B module the controller can cooperate with low fuel level sensor in silo After activating sensor for Auxiliary feeder operation time controller will connect auxiliary feeder to...

Страница 18: ...18 USER MANUAL FOR INSTALLING THE CONTROLLER AND SERVICE SETTINGS R Control 890...

Страница 19: ...ely it is necessary to isolate it thermally from surroundings and improve thermal contact with pipe Preset silo temperature must be set so high to ensure thermal power for mixer cycle when at the same...

Страница 20: ...boiler settings Min preset boiler temperature 75 C menu service settings boiler settings CH pump activating temperature 55 C menu service settings CH and HW settings Activating operation buffer servic...

Страница 21: ...active menu service settings buffer settings Buffer loading start temperature 50 menu service settings buffer settings Buffer loading stop temperature 75 menu service settings buffer settings Mixer s...

Страница 22: ...The controller can not be exposed to immediate effects of atmospheric conditions i e rain or sunrays Temperature of storage and transport should be within scope 15 65 degrees C During transport the c...

Страница 23: ...troller on assembly surface where 1 cover 2 base 3 screw for cover 4 plug 5 screw for assembly surface 6 assembly surface 12 4 ELECTRIC CIRCUIT CONNECTION The controller is adapted to current 230V 50H...

Страница 24: ...is not acceptable to twist wires inside the device Wires inside the controller should be led through cable glands Cable glands should be screwed Make sure that glands are correctly screwed by pulling...

Страница 25: ...re sensor CT2S T7 mixer temperature sensor TB connection of mixer room thermostat P controlling panel ecoSTER200 room panel with room thermostat function replacing TB or TM D D connection to additiona...

Страница 26: ...n Wires of the sensors are resistant to temperature not exceeding 100 C 12 8 WEATHER SENSOR CONNECTION The controller cooperates solely with weather sensor type CT4 P The sensor should be installed on...

Страница 27: ...STAT CONNECTION Room thermostat for boiler circuit can switch off the burner operation or switch off the CH boiler pump In order to thermostat switch off boiler operation select Thermostat selection f...

Страница 28: ...rm signal codes causes activation of additional boiler When pellet boiler is fired up and its temperature exceeds preset value i e 25 degrees C then controller switches off additional boiler it will g...

Страница 29: ...roller 2 external alarm device 3 transmitter Then in order to operate correctly set proper code for active alarms signal in menu Menu Service settings Boiler settings Alarms Choosing value 127 causes...

Страница 30: ...rical power to mixer servomotor with the controller according to point 12 4 and value servomotor producer s documentation Do not confuse opening direction with closing direction Connect electrical pow...

Страница 31: ...nsulation which is thick enough to meet safety standards of the boiler 12 18 ROOM PANEL CONNECTION It is possible to equip the controller with room panel ecoSTER200 which has following functions Room...

Страница 32: ...me Cleaning blow Supervision Supervision time Feeding time Cycle time Blowing power Min blowing power Lack of fuel detection time Feeder max temperature Additional feeder operation time Boiler setting...

Страница 33: ...in bakery The burner operates with maximum power without modulation of power The burner deactivates with disconnecting thermostat joints 28 29 Boiler temperature sensor does not influence feeder opera...

Страница 34: ...3 failed attempts it reports alarm Failed firing up attempt Feeder max temperature Determines maximum temperature of feeder when there is alarm of exceeding maximum feeder temperature Additional feed...

Страница 35: ...e when HW loading Available after connecting HW sensor Prolonged feeding of HW silo during priority HW deactivated may cause to overcooling of the CH installation because CH pump is deactivated Parame...

Страница 36: ...re below which buffer feeding starts Buffer feeding process is finished when low temperature reaches value defined in parameter Buffer feeding end temperature Stop feeding temperature 14 5 MIXER SERVI...

Страница 37: ...xer setting activated FLOOR is also limit temperature of mixer sensor when mixer pump is deactivated For floor heating set the value below 45 degrees C 50 degrees C or other if producer of materials u...

Страница 38: ...vanced Options available YES displays hidden parameters which edition is not recommended NO hides hidden parameters 15 Default settings restoring Default settings restore Restoring service settings Se...

Страница 39: ...erature above service parameter MENU Service settings Burner settings Max feeder temperature If the feeder temperature increases above this value the controller will begin burning off procedure Alarm...

Страница 40: ...rm reminder It will take place by failed attempt of feeding fuel from additional silo In case when through configured time of feeding the silo installed sensor not detects increase of fuel the reminde...

Страница 41: ...n MENU Boiler settings Power modulation Boiler settings Power modulation 100 Blowing power 100 Feeder work 100 Oxygen 50 Hysteresis H2 50 Blowing power 50 Feeder work 50 Oxygen 30 Hysteresis H1 30 Blo...

Страница 42: ...nd or twisting the button according to documentation of boiler producer Check the fan and replace it if necessary 5 Additional feeder is not working module B Check if feeder wires are correctly connec...

Страница 43: ...ly made after closing the valve return temperature must increase above value of parameter Minimum return temperature The cause may be calibration of mixer valve wait until calibration is finished Acti...

Страница 44: ......

Страница 45: ......

Страница 46: ......

Отзывы: