Burnham HF SERIES Скачать руководство пользователя страница 19

19

SOLID stream without air bubbles for approxi-
mately 10 seconds.

3. Close vent fitting and burner flame should start

immediately.

4. If the burner does not start immediately, check the

manual overload switch on the motor, if so
equipped, and the safety switch on the burner
primary control.

K.

ADJUST OIL PRESSURE

1. Locate oil pressure adjusting screw and turn

screw until Pressure Gauge reads the correct
pump pressure required for the specific boiler.
Refer to Table 4 .

2. DO NOT REMOVE PRESSURE GAUGE until

later.

L.

OTHER ADJUSTMENTS

1. ADJUST THE AIR BAND AND/OR AIR SHUT-

TER.

Beckett Burners:
a. Adjust air supply by loosening lock screws and

moving the air shutter and if necessary the air
band.  Refer to Table 4  preliminary settings.

2. ADJUST DRAFT REGULATOR for a draft of

-.02” (water gauge) over the fire after chimney has
reached operating temperature and while burner is
running.

3. READJUST AIR BANDS on burner for a light

orange colored flame while draft over the fire is
-.02” w.c.  Use a smoke test and adjust air for
minimum smoke (not to exceed #1) with a mini-
mum of excess air.  Make final check using suitable
instrumentation to obtain a CO

of 11.5 to 12.5%

with draft of -.02” w.c. in fire box.  These settings
will assure a safe and efficient operating condition.
If the flame appears stringy instead of a solid flame,
try another nozzle of the same type.  Flame should
be solid and compact.  After all adjustments have
been made, recheck for a draft of -.02” w.c. over the
fire.

4. TURN “OFF” BURNER and remove pressure

gauge.  Install gauge port plug and tighten.  Start
burner again.

M.

FLAME FAILURE

The HF boiler controls operate the burner automati-
cally.  If for unknown reasons the burner ceases to fire
and the rest button on the primary control has tripped,
the burner has experienced ignition failure.  Before
pressing the rest button, call your serviceman immedi-
ately.

N.

CHECK FOR CLEAN CUT OFF OF BURNER

1. AIR IN THE OIL LINE between fuel unit and

nozzle will compress when burner is on and will
expand when burner stops, causing oil to squirt
from nozzle at low pressure as burner slows down
and causing nozzle to drip after burner stops.
Usually cycling the burner operation about 5 to 10
times will rid oil line of this air.

2. IF NOZZLE CONTINUES TO DRIP, repeat step

N.1.  If this does not stop the dripping, remove cut
off valve and seat, and wipe both with a clean cloth
until clean.  Then replace and readjust oil pressure.
If dripping or after burn persist replace fuel pump.

O.

HINTS ON COMBUSTION

a. NOZZLES— Although the nozzle is a relatively

inexpensive device, its function is critical to the
successful operation of the oil burner.  The
selection of the nozzle supplied with the HF
boiler is the result of extensive testing to obtain
the best flame shape and efficient combustion.
Other brands of the same spray angle and spray
pattern may  be used but may not perform at the
expected level of CO

2

 and smoke.  Nozzles are

Table 4:  Beckett  AFG

Boiler

Model

No.

Firi ng

Rate

(GPH)

Burner

Nozzle Specificati ons

Static

Plate

Air Setti ngs

Head

Head

Setti ng

M anufacturer

Size

Angle

Type

Shutter

Band

HF98

.85

A FG

HA GO

.75

45°

B

3-3 /8"U

8

0

L1

0

HF122

1.10

A FG

HA GO

.90

45°

B

3-3 /8"U

10

2

L1

0

HF147

1.25

A FG

HA GO

1.0

45°

B

2-3 /4"U

10

0

V1

0

HF173

1.50

A FG

HA GO

1.25

45°

B

2-3 /4"U

10

2

V1

2

Содержание HF SERIES

Страница 1: ...is unit The manufacturer will not be responsible for improper installation or operation This manual and all associated instruction material should be conspicuously posted near the equipment For service or repairs to boiler call your heating contractor When seeking information on boiler provide Boiler Model Number and Serial Number as shown on Rating Label Boiler Model Number Boiler Serial Number I...

Страница 2: ... valid only if the boiler has been installed maintained and operated in accordance with these instructions All boilers must be installed in accordance with National State and Local Plumbing Heating and Electrical Codes and the regulations of the serving utilities These Codes and Regulations may differ from this instruction manual Authorities having jurisdiction should be consulted before installat...

Страница 3: ... knowledgeable in the layout and installation of hydronic heating systems should attempt installation of any boiler It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating properly when the installation is completed Installation is not complete unless a pressure relief valve is installed into the tapping located on top of appliance S...

Страница 4: ... vent system This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air The interior of the venting and air intake systems must be inspected and cleaned before the start of the heating season and should be inspected periodically throughout the heating season for any obstructions Clean and unobstructed venting and air int...

Страница 5: ... Firing Rate gal hr 85 1 10 1 25 1 50 Nozzle Specification 75 x 45 B 90 x 45 B 1 00 x 45 B 1 25 x 45 B Stack Diameter inch 6 6 7 7 Number of Tubes 12 12 18 18 Boiler Water Cap gal 20 20 40 40 Supply Size FPT 1 1 2 2 Return Size FPT 1 1 2 2 Tankless Heater Size gal min 4 5 Optional 4 5 Optional 5 5 Chimney Size min 8 x 8 x 15 8 x 8 x 15 8 x 8 x 15 8 x 8 x 15 Approx Shipping Wt lb 450 450 720 720 DI...

Страница 6: ...ombustible floor shield supplied by Burnham is used DO NOT install on carpeting 2 FORBASEMENTINSTALLATION providea concrete base if floor is not perfectly level or if water may be encountered on floor around boiler 3 PROVIDE SERVICE CLEARANCE of at least 48 from the front of the jacket for servicing of burner and removal of tankless heater For minimum clearances to combustible materials See Figure...

Страница 7: ...building the fresh air infiltration through cracks around windows and doors normally provides adequate air for combus tion and ventilation 5 For boiler located in a confined space or an uncon fined space in a building of unusually tight con struction provide outdoor air with the use of two permanent openings which communicate directly or by duct with the outdoors or spaces crawl or attic freely co...

Страница 8: ...e boiler is to be operated in a system which has a large volume or excessive radiation where low boiler water temperatures may be encountered i e converted gravity circulation system etc The bypass should be the same size as the supply and return lines with valves located in the bypass and return line as illustrated in Figure 4 in order to regulate water flow for maintenance of higher boiler water...

Страница 9: ...9 Figure 3 Recommended Piping for Combination Heating and Cooling Refrigeration System ...

Страница 10: ... L vent or a factory built chimney that complies with the type HT requirements of UL103 The chimney and vent pipe shall have a sufficient draft at all times to assure safe proper operation of the boiler See Figure 6 for recommended installation 1 Install a draft regulator following the instructions furnished with the regulator See Figure 7 for alternate draft regulator locations 2 Consider the chi...

Страница 11: ...11 Figure 6 Recommended Smokepipe Arrangement and Chimney Requirements Figure 7 Proper and Improper Locations of Draft Regulator ...

Страница 12: ...12 Figure 8 Recommended Boiler Piping for Circulator Zoned Heating Systems ...

Страница 13: ...13 Figure 9 Boiler Piping for Zone Valve Zoned Heating Systems ...

Страница 14: ...ided with the Honeywell R8888 control 7 Conventional Zone Valve Zoned System Locate C1 and C2 inside the L8124C Honeywell control Connect the two 2 terminals to the system circulator wire leads supplied with boiler Connect the H1 and H2 terminals inside the R8889 to the T T terminals in the L8124C Honeywell Control Connect the thermostat of each zone and the circulator for that zone to R8889 panel...

Страница 15: ...Figure 10 Wiring Diagram for Water Boilers with Beckett AFG Burner and Controls without Tankless Heater Figure 11 Wiring Diagram for Water Boilers with Beckett AFG Burner and Controls with Tankless Heater ...

Страница 16: ...tings 4 Use of a high efficiency micron filter Garber or equivalent in addition to conventional filter is highlyrecommended Figure 12 Single Pipe Installation NOTICE Oil piping must be absolutely airtight or leaks or loss of prime may result Bleed line and fuel unit completely K Single pipe Oil Lines 1 Standard burners are provided with single stage 3450 rpm fuel units with the bypass plug removed...

Страница 17: ... TABLE 2 SINGLE STAGE UNITS 3450 RPM TWO PIPE SYSTEMS Lift H See Figure Maximum Length of Tubing H R See Figure 3 8 OD Tubing 3 GPH 1 2 OD Tubing 3 GPH 0 84 100 1 78 100 2 73 100 3 68 100 4 63 100 5 57 100 6 52 100 7 47 100 8 42 100 9 36 100 10 31 100 11 26 100 12 21 83 13 62 14 41 TABLE 3 TWO STAGE UNITS 3450 RPM TWO PIPE SYSTEMS Lift H See Figure Maximum Length of Tubing H R See Figure 3 8 OD Tu...

Страница 18: ...alve for the next zone to be purged Repeat this step until all zones have been purged At completion open all zone valves or valves 9 Close bib cock continue filling the system until the pressure gauge reads 12 psig Close fill valve Note If make up water line is equipped with pressure reducing valve system will automatically fill to 12 psig 10 Open isolation valve in boiler supply piping 11 Remove ...

Страница 19: ...ug and tighten Start burner again M FLAME FAILURE The HF boiler controls operate the burner automati cally If for unknown reasons the burner ceases to fire and the rest button on the primary control has tripped the burner has experienced ignition failure Before pressing the rest button call your serviceman immedi ately N CHECK FOR CLEAN CUT OFF OF BURNER 1 AIR IN THE OIL LINE between fuel unit and...

Страница 20: ...be replaced If the condition persists look for fuel leaks air leaks water or dirt in the fuel as described below Figure 14 Electrode Head Setting c FUEL LEAKS Any fuel leak between the pump and the nozzle will be detrimental to good combustion results Look for wet surfaces in the air tube under the ignitor and around the air inlet Any such leaks should be repaired as they may cause erratic burning...

Страница 21: ... tank that is above grade or has fuel lines buried in the ground above the frost line is a good candidate for cold oil The best solution is to place the tank and oil lines in the ground below the frost line i HIGHALTITUDEINSTALLATIONS Typically the rule to use for high altitudes is to increase the air supply by 4 per each 1000 ft above 2000 ft altitude from sea level This means that the air settin...

Страница 22: ...ng open drain valve and slowlydrainboiler c Burner should stop when water level drops below low water cutoff probe Verify limit thermostat or other controls have not shut off boiler d Adjust thermostat to lowest setting Refill boiler Q FREQUENTWATERADDITION A leaky system will increase the volume of make up water supplied to the boiler which can significantly shorten the life of the boiler Entrain...

Страница 23: ...er wire brush 30 handle clean firetubes c Remove fasteners holding burner door Carefully remove door with burner still attached 2 CLEANTHECOMBUSTIONCHAMBER Using wire or fiber bristle brush clean inside of combustion chamber 3 AFTERCLEANING a Vacuum debris inside combustion chamber and vacuum remaining fireside of boiler as necessary NOTICE BUR NER S HU TD OWN Open S ervice Switch to turn off burn...

Страница 24: ...24 NOTE When ordering parts always give the serial number and model number shown on the boiler Also provide the name of the part s shown below Figure 15 HF Series Bare Boiler V Repair Parts ...

Страница 25: ...137010 7 Flue Box Door w Insulation D16850 D16800 I21350 I21400 8 Combustion Chamber Floor Insulation I21325 I21400 9 Jacket Lower Front Panel 70437038 70437047 10 Burner Door D15700 D15800 11 Burner Door Insulation I21300 I21375 12 Jacket Left Side Panel 70437032 70437041 13 Jacket Top Left Side Panel 604370361 604370451 Jacket Top Right Side Panel 704370371 704370461 14 Burner Spacer Plate 70237...

Страница 26: ...ure 16 Beckett AFG Oil Burner Repair Part For replacement oil burner parts contact your wholesaler or the burner manufacturer R W Beckett Co P O Box 1289 Elyria OH 44036 216 327 1060 or 800 OIL BURN 645 2876 ...

Страница 27: ...8 3488 8 Bulkhead Fitting Locknut 3666 3666 3666 3666 9 Connector Tube Assembly 5636 5636 5636 5636 10 Coupling 2454 2454 2454 2454 11 Electrode Clamp 149 149 149 149 Electrode Clamp Screw 4219 4219 4219 4219 12 Electrode Insulator Assembly 5780 5780 5780 5780 15 Spider Spacer Assembly 5503 5503 5503 5503 16 Escutcheon Plate 3493 3493 3493 3493 18 Flange and Air Tube Assembly 3146806 3146806 31468...

Страница 28: ...28 ...

Отзывы: