POWER SUPPLY : 3P+T DIN43650 CONNECTOR
N
-
Ph
+
1 2
3
TP/PE
3
2
1
15V-30V 50/60Hz (12V-48V DC)
100V-240V 50/60Hz (100V-350V DC)
1 2
3
18
17
TP/PE
r
SNAA690000
F
CF
F
C0
+
—
~
~
FC2
F
C1
FEEDBACK
SIGNAL
SETPOINT
SIGNAL
SN
A
A
380000
16
15
14
13
+
0-20mA / 4-20mA / 0-10V
17
18
–
–
+
C
P6
POSI
A
B
9
8
7
6
5
4
FEEDBACK
CO
M
M
O
N
F
C1
CO
M
M
O
N
F
C2
FE
ED
B
ACK
F
C
1
FE
ED
B
ACK
F
C
2
D2
D1
A
Motor
=
The control voltage must be S.E.L.V. (Safety Extra Low Voltage).
The terminal temperature can reach 90°C.
The feedback must be connect with rigid wires. If the applied voltage is higher than 42V, the user must foresee a fuse in the power
supply line.
For a use with a long power supply wiring, the induction current generated by the wires mustn't be higher than 1mA.
The used wires must be rigid (feedback voltages: 4 to 250V AC/DC).
The card resolution is 1°
10 kOhm input impedance if control with voltage (0-10V)
100 Ohm input impedance if control with current (0-20mA ou 4-20mA)
REP
DESIGNATION
FC0
Open limit switch
FCF
Close limit switch
FC1
Auxiliary limit switch 1
FC2
Auxiliary limit switch 2
D1/D2 Failure report Terminal strip (24V DC / 3A max)