Technical data

ME61

6.7.2 

Terminal strip

1

2

3

4

Image 3: 

Terminal strip pin assignment

Item

Assignment

Function

1

GND

Supply

2

CAN_L

büS communication

3

CAN_H

büS communication

4

24 V

Supply

Table 2: 

Terminal strip pin assignment

English

Содержание ProcessViewDisplay ME61

Страница 1: ...Operating Instructions Type ME61 ProcessViewDisplay ...

Страница 2: ...the right to make technical changes without notice Technische Änderungen vorbehalten Sous réserve de modifications techniques Bürkert Werke GmbH Co KG 2020 Operating Instructions 2009 00_EU en_00815341 Original DE ...

Страница 3: ...6 TECHNICAL DATA 9 6 1 Conformity 9 6 2 Standards 9 6 3 Operating conditions 9 6 4 Mechanical data 9 6 5 Electrical data 9 6 6 Type label device labelling 10 6 7 Pin assignment 10 6 7 1 M12 plug 10 6 7 2 Terminal strip 11 7 INSTALLATION 12 7 1 Safety instructions 12 7 2 Mounting onto the standard rail 12 7 3 Mounting with magnets 13 7 4 Mounting with a pipe clamp 13 7 5 Mounting in the control cab...

Страница 4: ...ice to the Bürkert Communicator 16 8 2 Configuration of views 16 8 3 Settings with Bürkert Communicator 17 8 3 1 Overview of device specific setting options 17 9 MAINTENANCE 20 10 TROUBLESHOOTING 21 10 1 Status indicators and measures 21 11 ACCESSORIES 22 12 DISASSEMBLY 22 13 PACKAGING TRANSPORT 23 14 STORAGE 23 15 DISPOSAL 23 English ...

Страница 5: ...ructions will result in death or serious injuries WARNING Warns of a potentially hazardous situation Failure to observe these instructions may result in serious injuries or death CAUTION Warns of a potential danger Failure to observe may result in moderate or minor injuries NOTE Warns of damage Failure to observe these instructions may result in damage to the device or the system Indicates importa...

Страница 6: ...and application conditions These specifications can be found in the contract documents the operating instructions and on the type label In the potentially explosive atmosphere only use devices that are approved for this purpose These devices are identified by a separate Ex type label Before use note the information on the separate Ex type label and the Ex additional information or the separate Ex ...

Страница 7: ...chnicians may perform installation and maintenance work Install the device according to the regulations applicable in the respective country After an interruption in the power supply ensure that the process is restarted in a controlled manner Observe the general rules of technology NOTE Electrostatically sensitive components and assemblies The device contains electronic components that are suscept...

Страница 8: ...ied ope rating conditions 4 3 Information on the Internet Operating instructions and data sheets for the Bürkert products can be found on the Internet at country burkert com 5 PRODUCT DESCRIPTION The ProcessViewDisplay Type ME61 serves to visualise process data The ProcessViewDisplay can depict up to 4 values simultaneously The software Bürkert Communicator is required to configure the ProcessView...

Страница 9: ...erating conditions WARNING Risk of injury due to malfunction if used outdoors Do not use the device outdoors and keep it away from heat sources that could cause the permissible temperature range to be exceeded Permitted ambient temperature range 10 C 60 C Altitude Up to 2000 m above sea level 6 4 Mechanical data Dimensions See data sheet for Type ME61 Housing material Polycarbonate 6 5 Electrical ...

Страница 10: ...protection CE mark Made in Germany 74563 Ingelfingen 24V T 20 C 60 C amb IP65 3 W ME61 ID 00368544 S N 001001 W08MN Image 1 Description of type label and device labelling 6 7 Pin assignment 6 7 1 M12 plug 1 4 3 2 5 Coding Image 2 M12 plug pin assignment Item Assignment Function Colour 1 FE CAN GND Shielding brown 2 24 V DC Supply white 3 GND Supply blue 4 CAN_H büS communication black 5 CAN L büS ...

Страница 11: ...E61 6 7 2 Terminal strip 1 2 3 4 Image 3 Terminal strip pin assignment Item Assignment Function 1 GND Supply 2 CAN_L büS communication 3 CAN_H büS communication 4 24 V Supply Table 2 Terminal strip pin assignment English ...

Страница 12: ...ystem against unintentional activation Following installation ensure a controlled restart 7 2 Mounting onto the standard rail 1 Tilt the device to the right and align it with the standard rail 2 Hook the device into the lower guide of the standard rail Push the device upward while tilting it to the left and lock it into the upper guide of the standard rail 3 Image 4 Mounting the device onto the st...

Страница 13: ...ge 5 Mounting the device with magnets 7 4 Mounting with a pipe clamp 1 Loosen the screws on the pipe clamp and open it 2 Fasten the pipe clamp to the pipe ø23 mm without elastomer compartment ø6 to ø19 mm with elastomer compartment Fasten the screws max 0 7 Nm 3 Image 6 Mounting the device with the pipe clamp English ...

Страница 14: ...rew Place the housing top with seal display and printed circuit board onto the housing bottom from the front Fasten the screws max 0 7 Nm Image 7 Mounting the device in the control cabinet 7 6 Connecting to the fieldbus gateway Connect the 5 pin plug of the ME61 to the socket of the fieldbus gateway ME63 in accordance with the assignment Connect the 5 pin socket of the USB büS interface set to the...

Страница 15: ...ware the USB büS interface available as an accessory is required This chapter describes the basic use of the Bürkert Communicator Detailed information on using the Bürkert Communicator software can be found on the Bürkert website at country burkert com 8920 Operating instructions downloads 8 1 User interface Menu bar Add interface connect to USB büS Interface Configuration areas of the device Menu...

Страница 16: ... The device is connected to the Bürkert Communicator and is displayed in the navigation area 8 2 Configuration of views Form a connection to the Bürkert Communicator software See chapter 8 1 1 Connecting the device to the Bürkert Communicator Select büS in the navigation area Select Detailed view Network configuration Image 9 Network configuration Parameterise the inputs and outputs via drag and d...

Страница 17: ...cator The device is set on the PC with Bürkert Communicator The upper part of the device display flashes while settings are made with Bürkert Communicator 8 3 1 Overview of device specific setting options The following overview of the setting options contains only the device specific settings for the ProcessView Display ME61 and not the description of the Bürkert Communicator software The detailed...

Страница 18: ...e Set operation mode of the büS interface Show errors from büS partners Set whether and from which consumer errors are displayed Deallocation delay Time from the loss of a consumer until deletion of its configuration Configuration client Operation mode defines whether the configuration will be managed by another device Changing operation mode Changing the operation mode between active inactive and...

Страница 19: ... Number since restart Max send errors Most serious send error that was issued in the same way as the device status is dis played The display can be reset to 0 Reset error counter CANopen status operational or pre operational Logbook The logbook lists all warning messages and error messages with details of the type time and signature The messages displayed in the logbook can be updated saved and de...

Страница 20: ...ce Serial number of the device Software identification number Software version büS version Hardware version Product type Manufacturing date eds version Device driver Driver version Firmware group DLL version Place of origin Reset device Restart Restart the device Factory reset Reset device to factory setting Table 6 Setting options in Bürkert Communicator configuration area General settings mainte...

Страница 21: ... büS participants Bus error e g short circuit Check cables The device has no connection to the PLC Check cables Check device description for the device connection to the PLC Device cannot find the assigned büS participant Check whether the büS participant is assigned to the device Orange Search for büS participants is active Status ends after a few seconds If the device status lasts longer than 4 ...

Страница 22: ...üS stick terminating resistor Y distributor 0 7 m cable with M12 plug 772551 büS extension cable 0 1 m 772492 0 2 m 772402 0 5 m 772403 1 0 m 772404 3 0 m 772405 5 0 m 772406 10 0 m 772407 20 0 m 772408 Magnet holder fastening set on request Pipe clamp fastening set on request Attachment set standard rail Table 9 Accessories 12 DISASSEMBLY WARNING Risk of injury due to improper disassembly Disasse...

Страница 23: ...serve permitted storage temperature 14 STORAGE NOTE Incorrect storage may damage the device Store the device in a dry and dust free location Storage temperature 30 80 C 15 DISPOSAL NOTE Damage to the environment caused by device parts contaminated with media Dispose of the device and packaging in an environmentally friendly manner Observe applicable disposal and environmental regulations Adhere to...

Страница 24: ...www burkert com ...