![Burkert Positioner TopControl Basic 8696 Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/burkert-0/positioner-topcontrol-basic-8696/positioner-topcontrol-basic-8696_quick-start-manual_2832396016.webp)
16
Start-up
9.2. electrical installation with circular
plug-in connector
→
Connect the positioner according to the table.
6
1
7
5
4
3
2
8
Fig. 8:
Circular plug M12 x 1, 8-pole
pin
Wire color
3)
configuration
1
white
Set-point value
+
(0/4 ... 20 mA)
2
brown
Set-point value
GND
3
green
Supply voltage
GND
4
yellow
Supply voltage
+
24 V DC
5
grey
Binary input
+
6
pink
Binary input
GND
7
blue
Analogue position feedback
GND
8
red
Analogue position feedback
+
Tab. 3: Connection with circular plug-in connector
When the supply voltage is applied, the positioner is operating.
→
Actuate the automatic adjustment of the positioner, as described
in the chapter entitled “10.2. Automatic adjustment X.TUNE”.
3)
The indicated colors refer to the connecting cable available as an
accessory (919061).
10. sTarT-up
10.1. safety instructions
Warning!
risk of injury from improper operation!
Improper operation may result in injuries as well as damage to the
device and the area around it.
• Before start-up, ensure that the operating personnel are familiar
with and completely understand the contents of the operating
instructions.
• Observe the safety instructions and intended use.
• Only adequately trained personnel may operate the equipment/
the device.
10.2. automatic adjustment
X.TUNE
To adjust the positioner to local conditions, the
X.TUNE
function must be run following installation.
Warning!
While the
X.TUNE
function is running, the valve automatically
moves from its current position!
• Never run
X.TUNE
while a process is running!
• Take appropriate measures to prevent the equipment from being
accidentally actuated!
english
Type 8696
Содержание Positioner TopControl Basic 8696
Страница 42: ...42 Transport Lagerung Verpackung Typ 8696 deutsch ...
Страница 63: ......